You are on page 1of 7

QUOTATION

Ref: Q-MKT/TN/JSC/38/4/18-19 13 April 2018


To
M/s. JS Consultancy,
Chennai.

Dear Sir,

Sub. : Your requirement of 1600 KVA, 11000/433V Transformers with On Load Tap Changer.
Ref:- Telephonic Enquiry.

We thank you for the above enquiry by email on 11/4/2018 and wish to enclose our offer.

1. KVA : 1600 KVA - IS : 1180 (Part I) : 2014 Level-2


2. Voltage Ratio : 11000/433V
3. Type of Tap changer : On Load Tap Changer with tapping range
+ 5% to – 15% in steps of 1.25%
4. Winding Material : Copper

For your kind consideration, please find enclosed,

Technical details : Page 2


Page 3
Routine tests : Page 4
List of Fittings and Accessories : Page 5
Price ,Terms and condition : Page 6
Page 7

We hope you will find our offer technically acceptable and commercially economical to meet your requirement. We now look
forward to receive your valued order and assure you of our best service all the time.

Thanking You,

Yours faithfully,
for ESENNAR TRANSFORMERS (P) LTD. UNIT - II,

T. VENKATESAN
SENIOR MARKETING - ENGINEER
TAMILNADU
CELL: 08608000797

R. SATHEESH
MARKETING MANAGER
COIMBATORE
CELL: 090031 90009

Encl. a/a
(ET/MKT/F001)
TECHNICAL SPECIFICATIONS

Make : ESENNAR
Reference Standard : Transformer - IS : 1180 (Part I) : 2014 Level-2
Oil - IS : 335 : 1993

Rated KVA HV : 1600 KVA


LV : 1600 KVA
Phases : 3

Service : Outdoor
Mounting : Plinth
Wound : Double

Temp. Rise in Oil [Degree C.] : 40


By Resistance [Degree C.] : 45
Ambient temperature : 45

Winding Material : Copper


Type of Cooling : ONAN
Class of Insulation : Class “A”

Vector Group : Dyn11


Frequency [Hz.] : 50
Phase : 3
Insulation Level [kV/Kvp] H.V. : 28 / 75
L.V. : 3/---

Primary Connection [HV] : Delta


Primary Volts : 11000V
Primary Wires : 3
Primary rated current : 83.98 A

Secondary Connection [LV] : Star


Secondary Volts : 433V
Secondary Wires : 4
Secondary rated current : 2133.40 A

Taps on Primary /Secondary Winding for : +5% to –15% in steps of 1.25%


Primary /Secondary Voltage Variation On Load Tap Changer
No. of switch positions : 17

Terminal Arrangement H.V. : Cable Box


L.V : Bus Duct
Losses
At 50% Loading : 4200 W (Max.)
At 100% Loading : 11800 W (Max.)

Impedance (Z) [Percentage]


* HV - LV : 6.25%

* No Load Current (% of Rated Current) : Less than 1.5 %

* SUBJECT TO IS : 2026 TOLERANCE

Page 2 of 7
Weights & Dimensions (Approx.)

1) Core & Windings with clamps (Untanking Weight) : 3650 Kgs.


2) Tank & Fittings : 2100 Kgs.
3) Oil : 2200 Ltrs. (1870 Kgs.)
4) Total Weight : 7620 Kgs.
Overall dimensions of the transformer (mm)
Length : 3100
Breadth : 2620
Height : 2820

HV - LV Orientation : 180 deg.

Bushing - IS : 2099 & IS: 3347


Porcelain Bushings HV : 3
Epoxy Bushing LV : 4

Painting [Finish] : Light Grey


Polyurethane Paint

Note 1: The Specifications including the physical weights mentioned in this offer are indicative in nature.
Due to Continuous improvement in design, these parameters may vary in the final product.
However the performance (NLL & LL) and warranty parameters would be intact. Exact weights and sizes
will be submitted along with GA drawings after receipt of P.O.

Page 3 of 7
TESTS - Routine Tests as per IS : 1180 (Part 1) : 2014

1 Ratio test

2 Polarity

3 Phase angle error measurement

4 I R Values

5 Winding resistance

6 Open circuit test

7 Short circuit & Impedance test

8 Separate source voltage test

9 Induced over voltage test

10 Pressure Test

11 Oil Leakage Test

12 BDV Oil

NOTE:
1. We offer only Routine Tests as per IS-2026 and IS : 1180 for customer inspection at our works on NO CHARGE BASIS.
All other tests like type tests & special tests is required would be charged extra. Please note that all test charges would
attract GST at the same rate as that of main Transformer.

2. Temperature rise test - extra each test.


[Please note that the Temperature rise Test will be carried out at our modern ,automated Computerized Test Lab.
Which is second of its kind test lab in India.]
3. Short Circuit & Impulse Tests charges extra.

4. We have already done short circuit test on 12500 KVA, 33/11 KV, 10000 KVA, 33/11 KV, 3000 KVA, 6.6/2.3 KV,
2000 KVA, 33/3.3 KV, 1600 KVA, 33/3.3 KV, 630 KVA, 33/0.433 KV and Impulse test on 11 MVA, 66/11KV,
6000 KVA, 33/6.9 KV, 3000 KVA, 11/0.380X4 KV, 3 MVA, 6.6/2.3KV, 1600 KVA, 33/3.3 KV, 1000 KVA,
11/0.433 KV, 800 KVA, 11/0.350V, 750 KVA, 6.6/3.3 KV, 500 KVA, 3.3/0.550 KV Transformers.
5. Measurement of HV and LV Winding Resistance on all taps charges extra.

Page 4 of 7
STANDARD FITTINGS AND ACCESSORIES
S. NO. DESCRIPTION QTY
NO.S
1 Rating & Terminal Marking Plate One
2 Earthing Terminals Two
3 Lifting Lugs Four
4 Drain Valve with blanking plate One
5 Filter Valve with blanking plate One
6 Conservator One
7 Conservator Oil filling hole with cap Two
8 Oil Level indicator with min. marking One
9 Dehydrating Breather One
10 Conservator Drain Plug Two
11 Air Release Device One
12 Thermometer Pocket One
13 Explosion vent One
14 Roller Bi directional Four
15 Radiators (Detachable Type) Six
16 Cable Box HV One
17 Bus Duct LV One
18 Separate Neutral Terminal One
19 On Load Tap Changer One
20 O.T.I with Alarm & Trip Contacts One
21 Buchholz relay with Alarm & Trip Contacts One
22 Radiator Valves Twelve
23 Marshalling Box One
24 Drain Valve with blanking plate (OLTC) One
25 Filter Valve with blanking plate (OLTC) One
26 Current Transformer One
27 OLTC surge relay One
28 RTCC Panel with 12 window Annunciation
29 AVR One
30 W.T.I with Alarm & Trip Contacts One
31 W.T.I. Pocket One
32 Inspection Cover One
33 M.O.G. with LOLA Contacts One
34 Buchholz relay shut off valve One
35 Jacking Pads Four
36 Sampling Valves Two

NOTE :

For all brought out components, test certificates received from our sub supplier only will be submitted for your records.

2. For Oil Cooled Transformers, We will provide Class of Insulation – “A”.


3. Drawings will be submitted on event of order.
4. Civil works is not in our scope.

Page 5 of 7
PRICE, COMMERCIAL TERMS & CONDITIONS

SL. NO. QTY KVA RATIO WINDING UNIT PRICE

01 One 1600 11000/433V Double wound Rs. 28,45,000/-


[On Load Tap Changer] Copper
DISCOUNT Rs. 2,55,000/-
--------------------
AFTER DISCOUNT PRICE Rs. 25,90,000/-
---------------------

[Rupees Twenty Five Lakhs Ninety Thousand Only.]

PRICE : Ex-Works.

GST : EXTRA AS APPLICABLE AT THE TIME OF SUPPLY. Current rate is @18%.

DELIVERY : Within 8-9 weeks from the date of receipt of final drawing approval at our end with
unconditional manufacturing clearance and receipt of advance payment whichever is later..
Please note that above delivery is given in good faith, not guaranteed under any penalty and
subject to force majeure condition. However to meet your actual delivery period, we request
you to discuss with our Marketing Department. Please note that in case of delay in lifting the
Transformer against agreed delivery period, an interest of 24% per annum will be chargeable
on pro rata basis.

VALIDITY : This offer will be kept open for 15 days from the date of this offer and thereafter subject to
our confirmation in writing.

PAYMENT : 50% of basic price along with taxes and duties with order and balance along with all taxes and
duties after inspection at our works but before despatch against Proforma Invoice. Inspection
can be done by you or your appointed third party at your cost. Prior intimation will be given by
us for inspection.

ENTRY TAX, OCTROI : Entry tax , Octroi and other levies if any will be charged extra at actual to your account.

SPARES : Spares, if any required will be supplied at extra cost

GUARANTEE : 12 months from the date of commissioning or 18 months from the date of despatch which ever
is earlier, under proper usage for any manufacturing defects. Further details are available in our
Operating Manual supplied along with Transformer.

TRANSPORTATION : Transportation is not included in our scope of work. Unloading at site, subsequent
safe storage, erection, Site Testing and Commissioning etc. are not included in our scope.

TESTS : We offer only Routine Tests as per IS-2026 for customer inspection at our works on
NO CHARGE BASIS. All other tests like type tests & special tests is required would
be charged extra. Please note that all test charges would attract GST at the same rate as that of
main transformer.

DISCLAIMER : While all efforts are made to check pricing & other error inadvertent error do occur from time to
time and ESENNAR reserve the right to decline the order arriving from such error.

JURISDICTION : Any disputes in connection with this transaction shall be addressed in court of competent
jurisdiction In HYDERABAD only.

Page 6 of 7
We hope our offer is in line with your requirement and looking forward to receive your valuable order.

Thanking You,
Yours faithfully,

for ESENNAR TRANSFORMERS (P) LTD. UNIT - II,

T. VENKATESAN
SENIOR MARKETING - ENGINEER
TAMILNADU
CELL: 08608000797

R. SATHEESH
MARKETING MANAGER
COIMBATORE
CELL: 090031 90009

In the event of order, PO to be addressed: RTGS DETAILS

M/s. ESENNAR TRANSFORMERS (P) LTD. UNIT-II, Name of the Bank : ICICI Bank Ltd.
Plot No 2, Phase-1, IDA, Pashamailaram Branch : KHAIRATABAD,HYDERABAD
Sangareddy (Dt.)-502 307,Telanagana (State), India. Bank A/C. No. : 000851000301
RTGS : ICIC0000008

(ET/MKT/F001)

Page 7 of 7