You are on page 1of 4

SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 1 of 4
-
A. General Data and Information

SITE CT RATIO 3600/1 A

MAKE PT RATIO 13.8/0.120 KV

MODEL ACCURACY CLASS 0.2

SERIAL NO. FEEDER GT1

B. Function Test
NO FUNCTIONS
1 Physical /Visual Inspection.
2 Electrical check.
3 Metering Minimum Current
4 Current Measurement
5 Voltage Measurement
6 POWER(MW-MVAR) Measurement
7 Accuracy Test
8 Maximum Demand

1. Mechanical Check and Visual Inspection


Item Description Remark

1 Inspect for physical damage and defects. 

2 All connection check according to the wiring diagram. 

3 Verify tightness for external wiring. 

2. Electrical Checks:
Item Description Remark

1 Wiring check as per Ref (approved) Drawing 

2 Auxiliary power supply checked for rating and polarity 

3 Test Switch checked for correct function 

3. Metering
TEST PERFORMED BY TEST WITNESSED BY DATE
NAME
SIGNATURE
TEST EQUIPMENT Calibration Due:10 MAY Serial No:RJ921T
File : 505771608.doc
SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 2 of 4
-
CREEP TEST

APPLIED
APPLIED VOLTAGE REMARKS
CURRENT
69.28 0.0 A No Increment In Energy Values

69.28 0.001A Minimum current value.

4- Current Measurements:

Current (A) measurement Current (A) measurement


3 ph Secondary Expected Actual
Current injected (A)
A B C A B C

0.00 0.00 0.00 0.00 0.001 K 0.001 K 0.002 K

0.25 0.9 K 0.9 K 0.9 K 0.899 K 0.900 K 0.901 K

0.50 1.8 K 1.8 K 1.8 K 1.799 K 1.800 K 1.800 K

1.00 3.6 K 3.6 K 3.6 K 3.599 K 3.600 K 3.600 K

5- Voltage Measurements:

3Ph Phase Voltage (KV) meas. Phase Voltage (KV) meas


Secondary Expected Actual
Voltage applied
(V) PH-N VA VB VC VA VB VC

0.00 0.00 0.00 0.00 0.002 K 0.002 K 0.002 K

90%
7.17 7.17 7.17 7.169 7.167 7.167
62.355 V
100%
7.967 7.967 7.967 7.965 7.964 7.963
69.28 V
110%
8.764 8.764 8.764 8.759 8.758 8.764
76.212 V

TEST PERFORMED BY TEST WITNESSED BY DATE


NAME
SIGNATURE
TEST EQUIPMENT Calibration Due:10 MAY Serial No:RJ921T
File : 505771608.doc
SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 3 of 4
6- Power Measurements: (+VE IMPORT & -VE EXPORT) -

3 Ph Power factor MW meas. MVAR meas.


3 ph
Voltag Phase
current
e Angle
injected
applie set @ Actual Exp Actual Exp Actual
(A) Exp
d (V)

69.28 1.00 0.0 1 1 86.045 86.019 0 0

69.28 1.00 45 0.707 0.707 60.834 60.837 60.834 60.811

69.28 1.00 90 0 0 0 0 86.045 86.016

69.28 1.00 180 -1 -1 -86.045 -86.000 0 0

69.28 1.00 270 0 0 0 0 -86.045 -86.006

69.28 1.00 315 0.707 0.707 60.834 60.807 -60.834 -60.832

7. Accuracy Test

Accuracy Test of Meter (Active Energy)


Result Result
Test # Test Description IEC 62053-22 Import Export
Limitations (Error %) (Error %)
1 10% In, 100%Vn UPF ± 0.2 -0.0457 -0.0429
2 100% In, 100%Vn UPF ± 0.2 -0.0363 -0.0169
3 300% In, 100%Vn UPF ± 0.2 -0.0570 -0.1322
4 600% In, 100%Vn UPF ± 0.2 -0.0570 -0.1495
5 10% In, 100%Vn 0.5Lag ± 0.3 -0.0156 0.0151
6 100% In, 100%Vn 0.5Lag ± 0.3 -0.0109 -0.0141
7 300% In, 100%Vn 0.5Lag ± 0.3 -0.0224 0.0495
8 600% In, 100%Vn 0.5Lag ± 0.3 -0.0122 0.0408
9 10% In, 100%Vn 0.8Lead ± 0.3 -0.0700 -0.0692
10 100% In, 100%Vn 0.8Lead ± 0.3 -0.0560 -0.0595
11 300% In, 100%Vn 0.8Lead ± 0.3 -0.0597 -0.0595
12 600% In, 100%Vn 0.8Lead ± 0.3 0.0013 -0.0457

Accuracy Test of Meter (Reactive Energy).


TEST PERFORMED BY TEST WITNESSED BY DATE
NAME
SIGNATURE
TEST EQUIPMENT Calibration Due:10 MAY Serial No:RJ921T
File : 505771608.doc
SITE TEST REPORT

Description: Contractor.: Record No.:

Accuracy Testing of Ibn Omairah Co. STR-4619-20


Energy Meter – Elster Contract No.: Sheet:
4400007162 4 of 4
Result Result
-
Test # Test Description IEC 62053-23 Import Export
Limitations (Error %) (Error %)

1 10% In, 100%Vn UPF ± 2% -0.0480 -0.0224


2 100% In, 100%Vn UPF ± 2% -0.0340 -0.0340
3 300% In, 100%Vn UPF ± 2% -0.0570 -0.0570
4 600% In, 100%Vn UPF ± 2% -0.0570 -0.0570
5 10% In, 100%Vn 0.5Lag ± 2% -0.1057 -0.0607
6 100% In, 100%Vn 0.5Lag ± 2% -0.0801 -0.0812
7 300% In, 100%Vn 0.5Lag ± 2% -0.0570 -0.0570
8 600% In, 100%Vn 0.5Lag ± 2% 0.0122 -0.0501
9 10% In, 100%Vn 0.8Lead ± 2% -0.0331 -0.0405
10 100% In, 100%Vn 0.8Lead ± 2% -0.0209 -0.0578
11 300% In, 100%Vn 0.8Lead ± 2% 0.0013 -0.0597
12 600% In, 100%Vn 0.8Lead ± 2% 0.0013 0.0013

8.Maximum Demand Test:

3 Ph Phase MW meas. MVAR meas.


3 ph current
Voltage Angle
injected (A)
applied (V) set @
Exp Actual Exp Actual

69.284 0.5 60 21.511 21.489 37.257 37.258

69.284 1.00 60 43.022 43.056 74.515 74.478

TEST PERFORMED BY TEST WITNESSED BY DATE


NAME
SIGNATURE
TEST EQUIPMENT Calibration Due:10 MAY Serial No:RJ921T
File : 505771608.doc

You might also like