Type : ATSR31A

Trip Circuit Supervisory Relay


ASHIDA

Features :
• Sensing points are high impedance type and can
be used on any type of trip circuits.
• Supervises both pre closing and post closing
conditions.
• Checks ON : Control voltage, Interlocks, Solenoid
Coil wiring and TRIP coil healthiness.
• Checks the Trip coil loose connection (>300 ohm)
or shorting (< 10 ohms).
• Supervises the link cable between C.R. Panel and
C.R. Panel Trip circuit connections.
• Very low burden on Aux. supply. (Less than 3VA).
• Self function TEST facility for routine maintenance
check.
• Immune to momentary dips in control voltage.

Control and Indications :


• ON : TRIP SUPPLY INDICATOR.
• FAULT : TRIP CIRCUIT FAULTY INDICATORS.
• TEST : SELF TEST OF RELAY.

Operation :
The trip circuit of circuit breaker is normally wired through the protection relay contacts, interlocked with C.B.
auxiliary contacts, and other interlocks (like spring charging full etc.) and then connected to Trip solenoid coil of
circuit breaker and control voltage source through fuse links. ATSR relay continuously senses the voltage at these
junction points. Absence of the required voltage (as per the logic), immediately triggers the internal timer (1.0sec
time delay). After time delay, it is reported as fault by relay operation. The LED lamp “FAULT” gives visual
annunciation and relay contacts (2NC and 1NO) operate. The relay is ON in normal condition and Trips to OFF on
fault annunciation conditions. In Normal Condition NO is shorted and NC is open.

Trip Circuit Faulty Condition:


I. Link between Protection Relay NO and CB Aux. Contact is open
II. TC coil is open or short.
III. Control supply is less than 50%

Technical Specifications:
Sr. No. Specification Particulars
I. Control Supply : 24 / 30 / 110 / 220VDC. Specify while ordering.
II. Aux. annunciation Supply : 24 / 30 / 110 / 220VDC. Specify while ordering.
III. Trip coil DC Resistance : To be less than 200 Ohm. If higher to be specified.
IV. Burden on Aux. supply : Aux. Burden less then 3VA.
V. Control Contacts : 2NC - 1NO SR.
VI. Contact Rating : Alarm Duty - 10 Amp AC at 230VAC.
VII. Operating Time : 1.0 Sec. (± 0.1 Sec.)
VIII. Drawing Reference : For Cabinet Type - CSB ( MAC00202 )
: For Electrical Connection - AXL00602

Note: Due to our policy to upgrade our products constantly, we reserve the right to supply products which may vary
slightly from that indicated above

ASHIDA ELECTRONICS PVT LTD.


Plot No. A-308, Road No. 21,
Wagle Industrial Estate, Ref.: ATSR31A
Thane (W)-400 604. INDIA. Issue: 6 01.12.09
E-mail: sales@ashidaelectronics.com Page 1/1