Site Acceptance Test Report Date :

Contractor’s Name: Customer: NGSA

Name Of Substation: SEC Contract No.:


ENERGY METER Page 1 of 5
Panel/Bay No:GT3 Equip. No.: Dwg. Ref.: Record No.:

A. General Data and Information

MAKE CT RATIO 2000/1A


MODEL PT RATIO 33/0.120KV
ACCURACY CLASS 0.2S HZ 60 HZ
SERIAL NO.

B. Function Test

NO FUNCTIONS
1 Physical /Visual Inspection.
2 Electrical check.
3 Metering Minimum Current
4 Current Measurement
5 Voltage Measurement
6 POWER(MW-MVAR) Measurement
7 Accuracy Test
8 Maximum Demand

1. Mechanical Check and Visual Inspection

Item Description Remark


1 Inspect for physical damage and defects. DONE

2 All connection check according to the wiring diagram. DONE

3 Verify tightness for external wiring. DONE

2. Electrical Checks:
Date :
TESTING ENGINEER SEC- CSD - Engineer

Signature: ___________________ Signature: ________________


Name : Name :
Site Acceptance Test Report Date :

Contractor’s Name: Customer: NGSA

Name Of Substation: SEC Contract No.:


ENERGY METER Page 2 of 5
Panel/Bay No:GT3 Equip. No.: Dwg. Ref.: Record No.:

Item Description Remark


1 Wiring check as per Ref (approved) Drawing DONE

2 Auxiliary power supply checked for rating and polarity DONE

3 Test Switch checked for correct function DONE

3. Metering

- CREEP TEST

APPLIED
APPLIED VOLTAGE REMARKS
CURRENT
69.28 0.0 A No Increment In Energy Values
69.28 0.1A Minimum current value.

4- CURRENT MEASUREMENTS:

Current (KA) measurement Current (KA) measurement


3 ph Secondary Expected Actual
Current injected (A)
A B C A B C

0.00 0.00 0.00 0.00 0 0 0

0.25 0.5 0.5 0.5 0.5 0.5 0.5

0.50 1 1 1 1 1 1

1.00 2 2 2 2 2 2

5- Voltage Measurements:

Date :
TESTING ENGINEER SEC- CSD - Engineer

Signature: ___________________ Signature: ________________


Name : Name :
Site Acceptance Test Report Date :

Contractor’s Name: Customer: NGSA

Name Of Substation: SEC Contract No.:


ENERGY METER Page 3 of 5
Panel/Bay No:GT3 Equip. No.: Dwg. Ref.: Record No.:

3Ph Phase Voltage (KV) meas. Phase Voltage (KV) meas


Secondary Expected Actual
Voltage applied
(V) PH-N VA VB VC VA VB VC

0.00 0.00 0.00 0.00 0.3 0.3 0.3

34.64 9.5 9.5 9.5 9.5 9.5 9.5

51.96 14.2 14.2 14.2 14.2 14.2 14.2

69.28 19.05 19.05 19.05 19 19 19

6- Power & Energy Measurements:

3 ph
3 Ph Phase Power factor MW meas. MVAR meas.
current
Voltage Angle
injected
applied (V) set @ Exp Actual Exp Actual Exp Actual
(A)

69.28 1.00 0.0 1 0.99 114.312 114.309 0 0

1.00 45 0.707 0.70 80.818 80.826 80.818 80.833


69.28
1.00 90 0 0 0 0 114.312 114.312
69.28
1.00 180 -1 -0.99 -114.312 -114.309 0 0
69.28
1.00 270 0 0 0 0 -114.312 -114.312
69.28
1.00 315 0.707 0.70 80.818 80.835 -80.818 -80.831
69.28

7. Accuracy Test

Date :
TESTING ENGINEER SEC- CSD - Engineer

Signature: ___________________ Signature: ________________


Name : Name :
Site Acceptance Test Report Date :

Contractor’s Name: Customer: NGSA

Name Of Substation: SEC Contract No.:


ENERGY METER Page 4 of 5
Panel/Bay No:GT3 Equip. No.: Dwg. Ref.: Record No.:

Accuracy Test of Meter (Active Energy)


Result Result
IEC 62053-22
Test # Test Description Import Export
Limitations
(Error %) (Error %)
1 10% In, 100%Vn UPF ± 0.2 -0.0060 -0.0028
2 100% In, 100%Vn UPF ± 0.2 -0.0115 -0.0004
3 300% In, 100%Vn UPF ± 0.2 -0.0129 -0.0155
4 600% In, 100%Vn UPF ± 0.2 -0.0172 -0.0112
5 10% In, 100%Vn 0.5Lag ± 0.3 0.0165 0.0261
6 100% In, 100%Vn 0.5Lag ± 0.3 0.0030 0.0069
7 300% In, 100%Vn 0.5Lag ± 0.3 -0.0345 -0.0133
8 600% In, 100%Vn 0.5Lag ± 0.3 -0.0562 -0.0544
9 10% In, 100%Vn 0.8Lead ± 0.3 -0.0121 -0.0095
10 100% In, 100%Vn 0.8Lead ± 0.3 0.0013 -0.0087
11 300% In, 100%Vn 0.8Lead ± 0.3 0.0401 0.0028
12 600% In, 100%Vn 0.8Lead ± 0.3 0.0401 0.0375

Accuracy Test of Meter (Reactive Energy).


Result Result
IEC 62053-23
Test # Test Description Import Export
Limitations
(Error %) (Error %)
1 10% In, 100%Vn UPF ± 2% -0.0001 0.0056
2 100% In, 100%Vn UPF ± 2% -0.0115 0.0030
3 300% In, 100%Vn UPF ± 2% -0.0129 -0.0086
4 600% In, 100%Vn UPF ± 2% -0.0086 -0.0086
5 10% In, 100%Vn 0.5Lag ± 2% -0.0096 -0.0019
6 100% In, 100%Vn 0.5Lag ± 2% 0.0025 -0.0112
7 300% In, 100%Vn 0.5Lag ± 2% -0.0012 0.0401
8 600% In, 100%Vn 0.5Lag ± 2% -0.0349 -0.0349
9 10% In, 100%Vn 0.8Lead ± 2% 0.0132 0.0235
10 100% In, 100%Vn 0.8Lead ± 2% 0.0051 0.0137
11 300% In, 100%Vn 0.8Lead ± 2% -0.0131 -0.0391
12 600% In, 100%Vn 0.8Lead ± 2% -0.0105 -0.0105

Date :
TESTING ENGINEER SEC- CSD - Engineer

Signature: ___________________ Signature: ________________


Name : Name :
Site Acceptance Test Report Date :

Contractor’s Name: Customer: NGSA

Name Of Substation: SEC Contract No.:


ENERGY METER Page 5 of 5
Panel/Bay No:GT3 Equip. No.: Dwg. Ref.: Record No.:

8.Maximum Demand Test:

Phase
3 Ph Voltage 3 ph current MW meas. MVAR meas.
Angle
applied (V) injected (A)
set @ Exp Actual Exp Actual

69.28 1.00 60 57.156 57.16 98.99 99

Test Inst. Used :

EQ: OMICRON CMC 256+ Serial No.: RJ921T


Cal. Due: 10/05/2018

Date :
TESTING ENGINEER SEC- CSD - Engineer

Signature: ___________________ Signature: ________________


Name : Name :