MOTOR DRIVE UNIT

TYPE CMA9
Operation Instructions HM 0.460.003

Shanghai Huaming Power Equipment Co., Ltd


HM0.460.003

Thank you for choosing our motor drive unit !

Prior to operate the motor drive unit you purchased, please be sure to read carefully
operating instructions delivered with shipments.

Thanks!
Contents

1. General………………………………………………………………………………………………1
2. Technical data ……………………………………………………………………………………2
3. Design ………………………………………………………………………………………………3
4. Operational principle ……………………………………………………………………………5
5. Assembly……………………………………………………………………………………………12
6. Check and adjustment…………………………………………………………………………13
7 . Tr o u b l e s h o o t i n g ……………………………………………………………………………1 4
8. HMC-3 Indicator………………………………………………………………………………………16
9. Optional accessories…………………………………………………………………………………17
10. Appendix 1 Composition of mechanical control system…………………………………………18
11. Appendix 2 Diagram of position display connection………………………………………………19
12. Appendix 3 Overall dimensional diagram of CMA9……………………………………………20
13. Appendix 4 Circuit diagram of position indicator HMC-3C………………………………………21
14. Appendix 5 Electrical principle diagram of CMA9………………………………………………22
15. Appendix 6 Explanation of X1 and X3 terminals………………………………………………23
16. Appendix 7 Explanation of CX terminals…………………………………………………………24
HM0.460.003

1. General
The motor drive CMA9 (fig.1, 2) serves for driving
the tap changer type CV to selected operating position. Inspection
It also can be used for some off-load tap changers. window
The motor drive housing contains all mechanical and
electrical parts necessary for operating the tap changer
from one operating position to an adjacent one, the motor
drive action is initiated by a single control signal and
accomplished without any possible interruption.
Hand crank
Overrunning the end positions is prevented by doufle
electrical equipment limits. Further safety and monitoring
equipment for adapting the motor drive to any service
requirements and to existing plants can be provided with
supplementary equipment.
Fig.1

Note: The installation of motor drive, electrical During the period of installation of motor drive,
connection and operation must be carried out by the electrical connection and operation, improper
trained personnel according to the operating operation may have influence on the operation of
instructions. To replace or change the motor drive is motor drive, on-load tap changer and transformation.
forbidden without permission of our company.

Fig.2

1
2. TECHNICAL DATA
Note: The listed technical data only applies to standard design, which may exist some differences with actual device,
we reserve the right to make modification.

Item Data

Rated power (W) 370

Rated voltage (V) AC 3 phase 380V

Power
supply Rated current (A) 1.1

Frequency (Hz) 50

Rotary speed (r/min) 1400

Rated torque on drive shaft (Nm) 40

Revolution of drive shaft per switching operation 2

Revolution of hand crank per switching operation 30

Running time per switching operation 4.4

Max. number of operating positions 27

Voltage of control and heater (V) Single phase AC 220V

Energized power of control circuit (VA) 52

Power consumption of heater (W) 30

Insulation level (50Hz, 1 min.) 2kV

Weight (kg) 70

Level of protection IP54

Mechanical life of motor drive unit (operations) 800,000

2.1 Working condition of motor drive unit:


1) The height above sea level shall not exceed 2000 meters.
2) The ambient temperature shall be - 25 ~ 40 ℃.
3) The oblique of vertical installation shall not exceed 2%.
4) There shouldn’t exist dirt and explosive or corrosive gas on site.

2
HM0.460.003

3. DESIGN
3.1 Structure The bottom of the tank consists of plates for mounting
Note: The structure and equipment described in cable entries.
this section only applies to standard design, we reserve
the right to make modification. 3.1.2 Gearing (see fig.3)
The gearing consists of the transmission gear and the
3.1.1 Housing (See figure 1) control gear. The transmission gear is provided with a
The housing consists of two parts, the tank and the box. The control gear is fixed to one side of the
cover, both manufactured from corrosion-proof light- transmission gear. It comprises a cam wheel for
metal casting. The housing gets a prime and a finish coat mechanically operating the cam switches, the tap change
(color green). The cover can easily be swung open. The indication wheel and the mechanical position indicator.
swing-open direction is to the left side. The tap change indication wheel as well as the cam wheel
The surfaces between cover and tank are protected turn one rotation per switching operation. The green zone
by a ledge and sealed by sectional rubber. indicates the rest position of the cam switches. The initial
The apertures for drive shaft, inspection glass and position for a tap change operation is indicated by the red
hand crank are sealed in a way that the housing is well- center mark in the green field.
protected against jets of water.
For airing the housing, there are two abyrinth apertures 3.1.3 Hand crank
in the both sides of the tank. The hand crank provided with a plastic handle is

Drive gear: Control gear:


1 Driving motor 102 Control shaft
2 Driving worm z=1, m=1.5 103 Coupling
3 Worm wheel z=56 m=1 104 Cam control
4 Spiral gear z=56 m=1 105 Step-by-step control switch
5 Spiral gear z=56 m=1 106 Gear z=25 m=1
6 Latch shaft 107 Step progress position
7 Safety switch for manual indication wheel
operation 108 Cog wheel z=132 m=1
8 Hand crank 109 Intermediate gear z=22 m=1
9 Drive shaft 110 Limit protection gear wheel
10 Spiral gear z=52. m=1 111 Limit position wheel
11 Spiral gear z=26. m=1 112 Position indication wheel
115 Operation counter
116 Limit stop block
117 Electrical limit switch
118 Control circuit limit switch
119 Main circuit limit switch
120 Position indication wheel
(static contact lever)
121 Position indication wheel
(action contact lever)
122 Coupling
123 Follower block
126 Gear z=56, m=1
Fig. 3 Motor unit

3
attached outside the housing by a wing nut clamp.

3.1.4 Counter
The electrial counter records the switching operations
performed. For reading the counter it is not necessary to
open the housing.

3.2 Electrical equipment


Note: The code of every element have been marked
on device with adhesive label.

Standard equipment:
S5 Push-button for tripping the motor
H1 Lamp signalling the tripping of the motor protective switch Q1
protective switch Q1 with lamp holder. Contacts: 1 NO + 1 NC
KI/K2 Motor contactor for control direction of with lamp socket (for lamp H1)
motor“Raise”(towards position n), K1 S16/S17 Limit switch for position n/position 1,
close. switch on/off control circuit
“Lower”(towards position 1), K2 close. Contact: 1 NC
Contacts: 4 NO + 2 NO + 2 NC S6/S7 Limit switch for position n/position 1,
K3 Brake contactor switch on/off main control circuit
Contacts: 4 NO + 4 NC Contacts: 3 NC
K20 Intermediate contact S8 Safety switch for manual operation
Auxiliary relay for step-by-step operation. Contacts: 3 NC
Contact: 4 NO + 4 NC. S12/S14 Cam switches for control direction towards
M1 Driving motor position 1 /towards position n
Squirrel cage rotor Contact: 1 NO + 1 NC with common
Ratings see section 2 switch-over point.
Q1 Motor protective switch with thermic and S13 Cam switch for step-by-step operation
magnetic tripping X1/X3 Terminal block for external connection.
Contacts: 1 NO + 1 NC auxiliary contacts. S38 “Remote”/ “local”selector
R1 Heater X10 Socket (220V.AC.10A)
Resistance 1.5 k Ω K21 Time relay, prevent the continual operation.
S1/S2 Push-button for control rotary direction of CX Terminal socket for HMC-3
motor. COUN Counter
Contacts: 1 NO + 1 NC

4
HM0.460.003

4.Electrical
Operational Principle
4.1 Circuits
The electrical operation principle of motor drive is
associated with the designed circuit of this motor drive
(see diagram 5). It includes motor circuit (main circuit),
control circuit, protective circuit and indication circuit etc.

4.1.1 Motor circuit


The motor terminals U, V, W are connected to the
terminal X1/1, 2, 3 of power source L1, L2 and L3 via
motor contactor K3, K1/K2, limit switch S6/S7, manual
protective switch S8 and motor protective switch Q1.

4.1.2 Control circuit


The control circuit is connected to L1, N via terminals
6,7, with the motor protective switch S8, interconnected
so that the control voltage is interrupted when Q1 or S8
is energized.
4.1.1 Motor circuit 4.1.3 Circuit for indicating the
The tripping circuit of motor
tripping of safety switch Q1
protective switch Q1 is interlinked
with the control circuit.
The motor protective switch Q1
is provided with a tripping coil which
can be energized via pushbutton S5
(on the motor drive unit and in the
control room) and via the safety
circuit. The safety circuit consists of
switching elements of the cam
switches S12, S13, S14 and of
auxiliary contacts of motor contactors
K1/K2 and K3.

4.1.3 Circuit for indication of the motor


protective switch Q1 tripping
This circuit is connected to L1 and N
via the terminals X1/18,17. The signaling
lamp H1 is installed in the emergency-off
push button S5 in the motor drive unit.
The auxiliary contact Q1 (43,44) is
connected to X1/27,28, which is the
captive contact when Q1 is closed. 4.1.2 Control circuit

5
4.1.4 Indication circuit of motor operation
The phase voltage of motor M1 is connected to
terminals X1/19, 20. Operation indication lamp H3 (inside
control chamber). As the captive signal of motor
operation, the contact signal integrated by K1 (23,24) K2
(23,24) is connected to X1/25,26.

4.1.5 Indication circuit of remote position


Digital remote position signal transmitter adopts
digital slide contact set, the static contact is connected to
the terminal on socket via decimal code, the action is
operated by means of first open and later close from one
position to next position. And integrated with display to
display the position parameter (see attached diagram 2).

4.1.6 Heater circuit


The heater circuit is connected to L1, N via the
terminals X1/4 and 5.
The heater resistor R1 is connected permanently with
power source.

4.1.4 Motor operation 4.1.6 Heater circuit


4.2 Operation(See appendix diagram 5)
indication circuit

4.2.1 Control
The motor drive control follows the step-by-step
principle, i.e after the initiation the switching operation
is automatically and irrevocably accomplished
independent of whether the push-buttons S1……S4 have
been operated during the running time of the motor drive.
(emergency stop is an exception). Another switching
operation is only possible when the control system is again
in the rest position. The rest position of the cam switches
controlling the running period is indicated by red center
mark of the tap change indication wheel.
Prerequisite:Motor protective switch Q1must be
closed; the voltage of L1, L2 and L3: AC 380V, 3 phase,
50Hz; Voltage of L1 and N: AC 220V 50 Hz, the
sequence of phase shall be correct, remote/local control
switch S38 should be in position.
Operation: control of transforming towards
position n.

4.2.1.1 Start
Press push-button S1, 13-14 of S1 will be closed (21-
4.2.1.1 Start-up

6
HM0.460.003

22 cut-off), meanwhile the current will connect K1 coil


from X1/6 via Q (13,14),
S8(S,V),S38(1,2),S2(21,22),
S1(13,14),K20(52,51),S16(C,NC),S6(S,V), K2(32,31);
the contactor K1 will be closed, which will make contact
K1(5,6) close, K20 coil will be energized via K20(72,
71), thus the instant action has been completed.
When K1 is closed, the contact K1 (13,14) will be
closed, which make K3 coil via K1, K3 close, the motor
M1 will operate.

4.2.1.2 Step-by-step control:


After motor start working, step position indication
wheel will overrun the green field, the cam switch S14
(C, NO) will close, the contactor K1 (A1, A2) can be
energized by S14 ( C, NO). When motor step position
indication wheel revolve another small section, cam
switch S13 will start, the closing of S13 (NO1, NO2) make
the intermediate relay K20 coil close after being
energized, K20 (52,51), K20 (72,71) open, K20 (14,13),
K20 (34,33) close, and K20 is energized via S13 (NO1,
NO2) and K3 (13,14), K20 (34,33), but K1 can keep being
energized only via
4.2.1.2 Step-by-step control
cam contact switch
S14(C, NO), S13
(NO1, NO2) will be
opened before the
motor drive stop, and
K20 still keep being
energized via K3 (13,
14), K20(34,33).

4.2.1.3 Stop
When the
operation of step 1 has
been completed, the
cam switch S14(C,
NO1) open, K1
release, the contact 13,
14 of K1 opens, K3
release and the main
circuit opens, motor
brake contact 21-22,
31-32,41-42,51-52,
self-actuating energy
Figure 4.2.1.3 Stop
consumption braking,

7
motor M1 stop running. At the same time, K3 is released, contact R-U, T-W, thus the motor will stop running, and
the contact 13 and 14 of K3 open, which make K20 de- the motor contactor K1 or K2 circuit will be opened via
energized. contact S-V.
If pushbutton S1 or S2 has been pressed, K20 will be
self-locked via it’s contact13-14 or 23-24 to prevent K1 4.2.3.2 Protection of manual operation
or K2 from being excited via 51-52 or 61-62 of K20, if Insert hand crank on shaft, the manual protection
the pushbutton S1 or S2 has not been pressed, K20 will switch S8 actuate to cut off motor power supply and
be released. control power supply. After manual operation, the hand
The control of transforming to position 1: press crank is withdrawn from shaft, manual protection switch
pushbutton S2 →contactor K2 is powered and closed → S8 is closed again.
braking contactor K3 is powered and closed → the motor Note: To prevent motor drive unit from being initiated
will run reverse → The direction-memory cam switch automatically, after manual operation, the motor drive
S12 start up → the following control is the same as that
of the transforming towards to position n. At the switch
action sequence from one tap changer to next tap changer
(0-30 block on step progress indication wheel), the
operation situation of each control is shown in figure 4.
At the switch action sequence from one tap changer
to next tap changer (0-30 block on step progress indication
wheel), the operation status of each control element.
The sequence of closing: S1(S2), K1(K2)K3, S14
(S12)S13,K20
The sequence of opening: S1 Figure 4
(S2), S13, S14 (S12), K1 (K2), K3,
K20.

4.2.2 Skip action performance of


middle position
For the switch with middle skip
point, the motor drive unit will
perform continuous operation by
means of the close/open of S37.

4.2.3 Performance of safety


protection

4.2.3.1 Protection of limit position


When the motor drive reach limit
position, the permanently-closed
contact C-CN of limit switch S16 (at
position N) or S17 (at position 1) will
open, thus contactor K1 or k2 can’t be
energized any more. When the
terminals position is overrun, the limit
switch S6 or S7 will open main circuit
Figure 4.2.3.1 Limit position protection

8
HM0.460.003

unit must be swung into the red line of step progress


position indication wheel, outside the red line shall be
the rest position of cam switch driven by motor drive
unit.

4.2.3.3 Phase sequence protection


To ensure the motor drive unit to revolve according
to the preset direction, there are certain requirement for
the phase sequence of motor 3 phase power supply, if the
phase sequence of terminals L1, L2 and L3 is not correct,
the phase sequence protection circuit will make safety
switch Q1 trip, see figure 4; when the phase sequence is
wrong, press down S1 pushbutton, K1 will close, K1 (41,
42) will open, and the motor will revolve
counterclockwise, the motor drive will operate towards
the reverse direction to make S12(C, NO2)close, make
Q1 release coil energized via K2(41,42), S13(NC1, NC2),
safety switch will trip, cut off main circuit and control
circuit, the motor will stop running, in this case, the phase
sequence shall be adjusted accordingly(any two phase can
be interchanged), operation can’t be executed until manual
operation reach the red line in the center of step-by-step
4.2.3.2 Manual operation protection
position indication wheel green field and close the safety

4.2.3.3 Phase sequence


protection 4.2.3.4 Automatic restart protection after

9
switch. S9 in control chamber, safety switch Q1 will trip
Additionally, when tap changer initiated, if the motor immediately, as these two pushbutton is parallel
is started by direction memory cam contact S14/S12 (Not connection.
pass via operating position automatically) not by After the safety switch has tripped, it can’t operate
pushbutton, safety switch Q1 will trip via S14(C, NO2), until the door of motor drive unit has been opened
K1 (41,42), S13 (NC1, NC2) or S12(C, NO2), S13 (NC1, and the safety switch Q1 has been closed.
NC2).
4.2.3.6 Continuous operation protection
4.2.3.4 Automatic restart protection after control Time relay K21 is set at set-point, if the motor drive
voltage under temporary de-voltage unit make a continuous tap changing without control
If control voltage restore after being disappeared signal, the energized time of K21 exceed the set-point,
within the operation time of motor drive unit, the motor contact 15,18 will be conducted and protection switch
drive unit will restart automatically according to the Q1 will trip.
controlled direction. Once restarting, the tap changer
action will be performed by the closed direction memory 4.2.3.7 External circuitry connection
cam switch S14 or S12. In this case, safety circuit is not There are special terminals X1 in motor drive unit
energized, as cam switch S13 (NC1,NC2) has been box, as a terminals for power leading wire and remote
opened. control and signal indication, it can perform all remote
control of raising, lowering, emergency releasing and
4.2.3.5 Emergency cut-off power supply protection remote indication for operation status signals. The external
(emergency stop) circuitry is shown by dotted line in circuit diagram, users
See figure 4, press down motor drive emergency
release pushbutton S5 or emergency release pushbutton

4.2.3.5 Emergency stop 4.2.3.6 Continuous operation protection

10
HM0.460.003

4.2.3.8 Step signal captive terminal

can install and connect them according to the circuit diagram.

4.2.3.8 Step signal captive terminals (also called double


signal)
Add a group slide contact set on remote position
transmitter, the static contact is relative to the position of
static contact of position indication circuit, and connected to
terminal block X3 according to the sequence from 1 to N;
The action contacts start by means of first open and later
close from one position to next one. Two groups contacts set
keep mechanical sync relative, independent of each other on
electrical, thus the signal contact supplied on terminals X3 is
4.2.3.7 Connection of external circuitry a set captive and closed operation position.

11
5. ASSEMBLY
motor drive action. This red center mark is used as a
5.1 Mounting the motor drive unit to the reference when adjusting.
transformer tank (see appendix, dimension One tap change operation corresponds to one rotation
drawing). corresponds to one rotation of the indication wheel. The
The motor drive unit is mounted by means of 4 studs tap change indication wheel is divided into 30 sections
fixed at the sides of transformer tank. The corresponding with one section corresponding to one rotation of the
bore holes are at the external side of the housing of the crank.
motor drive. Take care that the motor drive unit is mounted The number of sections counted from the beginning
vertical and that its drive shaft is in correct alignment of the tap change operation until the red center mark of
with the shaft of the bevel gear. the indication wheel faces the mark on the inspection
If the transformer causes extremely heavy mechanical
vibrations, the use of vibration dampening connectors is
recommended.

5.2 Coupling of tap changer and motor drive. Switching position of tap changer
It is absolutely necessary that the tap change operation
is accomplished before the motor drive stops. This is
ensured by setting the time of the selector or diverter
Switching position of tap changer
switch action at a distinct interval before the end of the

Example: (See figure 5)


a) On-load tap changer now is in operation position 10. Turn crank Switching position of tap changer
towards position 11until the selection switch sound a click, keep
cranking it and count the number of section of red line. (Revolutions
of hand crank)
b) Result: 4 sections
Compare a with b Uncouple clutch
12-4=8 sections is more than 3.75 sections
It must be readjusted.
Corrected number of sections (12-4)÷ 2=4 sections, choose 3.75
sections.
c) Turn crank towards 11 until red center mark appears.
d) Uncouple a coupled joint clamp under vertical drive shaft.
e) Turn on in the same direction (towards 12) by 3.75 sections.
f) Couple again. Install clutch
g) Turn on in the same direction (as with e) until selector switch
action occurs. Count number of TIW sections until red center mark
appears.
Result: 8.25 sections.
h) Check in the opposite direction.
Switching position
Result: 7.25 TIW sections. of tap changer
8.25-7.25=1 less than 3.75 sections
Coupling tap changer-motor drive is sufficiently symmetrical in
both directions.
Switching position of tap changer
Fig.5

12
HM0.460.003

window should be equal in both rotation senses. Minor -If there is a difference between the numbers of sections
asymmetry is admissible. Symmetrical coupling is counted on both directions, the motor drive must be
achieved as follows: readjusted in relation to the tap changer by half this
-Adjustment only with manual operation. difference of numbers.
-Tap changer and motor drive have to be in the adjustment Notes:
position. The square shaft tube of the vertical drive shaft can
- Couple tap changer and motor drive. only be coupled to the coupling brackets after a rotation
-Turn crank in one direction until selector or diverter angle of 90°Ê or multiples . This angle corresponds to
switch action occurs. Count the remaining TIW sections 3.75 TIW squares. Readjusting, therefore, becomes
until the red center mark of the tap change indication necessary only if the difference necessary only if the
wheel is visible in the middle of the inspection window. difference between clockwise and anti-clockwise
-Repeat this procedure in the opposite direction. cranking is in excess of 3.75 TIW sections.

6. Operational test and adjustment


performed one switching operation and the red line and
6.1 Preparations digital line will be aligned with reference line when
The transformer has been put on utilization site, prior stopped.
to operate the tap changer, the motor drive unit shall be During the actual use, the red line on step progress
experienced following test: position indication wheel can’t be aligned with the
. Prior to operate, please be sure to familiar with manual reference line, there may exist some deviation between
instruction and method of use. the lines, if they are still within the green field, it won’t
. Prior to use, check whether the signal of the adjusted affect the operation, when the reference line is out of the
position of tap changer, motor drive and the position of green field, it can be adjusted, and the method of
remote control display (accessories) is identical. adjustment are as follows: when motor drive is adjusted
. Prior to connect via the power supply, check whether up to (down) one step, the red line will appear deviation,
the wire of all electrical element is loosen, the grounding one piece on (or under) cam wheel shall be loosen, adjust
blot of motor casing should be grounded safely. the size of angle, which has been adjusted before ex
. Prior to operate electrically, check whether the hand factory, user needn’t make any further adjustment.
crank is flexible, the switching position and stop position
of tap changer is correct. 6.2.2 Checking limit position
. Under the low temperature and dampened condition, The full range tap change until one end position, it is
the heater resistor R can’t be used until it has been impossible to keep electrical operation in the same
powered and heated for some hours. If the switch is direction, but it’s possible in the opposite direction, for
transported to on site and stored over two weeks, R circuit the test of another end position, the same procedure is
shall be connected to power supply to avoid being rusted also applied.
for condensed dew. When the end position is reached, the wheel
connection between control and main circuit is achieved
6.2 Electrical operation test by means of the limit stop block on the limit protection
Note: The requirement of operating power supply and gear wheel bumping lever, wheel connecting S16 (or S17)
phase sequence (See appendix 2) should be observed! and S6 (or S7) successively.
Thus a. Adjust S16 (position n) or S17 (position 1).
6.2.1 Checking the step-by-step operation b. Adjust limit stop blocked piece.
Press down pushbutton S1 or S2 to make motor drive To make S16 or S17 start running before completing
run at clockwise (counter-clockwise), and driving motor tap changing, and S6 or S7 can start running only
is automatically switched off when the tap changer has exceeding the end position, which has been adjusted

13
before export factory, user needn’t to make any further move it forward to make it start action earlier.
adjustment. When pull out the hand crank handle, we should hear
the sound of S8 restoration, and electrical operation is
6.2.3 Manual operation protection test correct, if S8 can’t be restored, we can adjust the clip
When inserting hand crank handle, we should hear a ring, if S8 itself can’t be restored, it must be replaced.
sound occurred from protective switch S8, and the
operation is impossible by pressing any pushbutton from 6.2.4 Checking the emergency cut-off power supply
S1 to S5, if S8 don’t have action, adjustment is necessary, See 4.2.3.5

7. Trouble shooting
7.1 Short circuit of power wire d. Limit switch S6 (raising) or S7 (lowering) has not
a. External operating power supply itself is faulty. been restored or invalid, making S-V contact
b. Power supply connection is wrong, connection disconnected.
should be made according to the arrangement terminal e. The permanently-closed auxiliary contact 61-62 of
block in diagram 4. contactor K2 (raising) or S7 (lowering) is disconnected
c. The parallel connection on terminal block is wrong, invalid.
most of them are because the original connection drop f. The coil of contact K1 (raising) or K2 (lowering) is
off and false connected when user make external broken.
connection, the parallel should be made correctly g. Some terminal lead of control circuit is loosen or
according to terminal block in diagram 4. disconnected.

7.2 The contactor can’t be closed even the 7.3 Contact closed when pressing down S19 or
pushbutton S1 or S2 has been pressed down S2, but the motor can’t revolve (see 4.1.1)
(See 4.2.1.1) Remote/local switch position is wrong. a. External power supply is not conform to the
requirement (see 2)
7.2.1 Both direction can’t be closed b. Some contact of travel switch S6, S7, S8 or K1,
a. The parallel connection wire on terminal block X1 K2, K3 can’t be closed normally
is loosen or drop off, which make control power supply c. Some connection wire lead of main circuit is loosen
unconnected. or disconnected.
b. Air break switch Q1 has not been closed. d. Main motor is broken.
c. Manual protective switch S8 has not been restored
or disconnected invalidation (See 6.2.3) 7.4 Pause in the process of operation
d. Some connect joint is loosen or drop off. a. External power supply is blackout.
e. Remote/local switch position is wrong. b. The position cam switch S14 (uprising) or S12
(lowering) is too large or it’s permanently-opened can’t
7.2.2 Single direction is not closed be closed normally.
a. Pushbutton hasn’t been restored, two pushbutton c. The action sequence of cam switch S12, S13, S14
S1 and S2 is interlocked, the invalid action of pushbutton is wrong, (see 4.2.1.2)
in one direction is always due to non-restored of another d. When motor drive is at limit position, the limit stop
direction pushbutton. block is tend to forward, thus making S6 or S7 is
b. Pushbutton itself is invalid disconnected when the step 1 tap changing has not been
c. Limit switch S16 (uprising) or S7 (lowering) has completed (see 6.2.2)
not been restored or disconnected. e. The false connection between motor drive and

14
HM0.460.003

switch (the step position is not the same) cause mechanical until there exist delay in release (if coil remain magnet,
limit position when switch limit position is reached. there will be bur on auxiliary contact). Characteristic:
operation in both directions, the red line all beyond the
7.5 The trip of safety switch Q1 range when stopped.

7.5.1 Tripping upon connecting power supply 7.7 Interlocking of motor drive unit
a. False connected to permanently-closed inside a. The position of cam switch S13 is too wide, its
control chamber of external remote stop pushbutton S9, permanently-opened contact never close during a cycle
which should be connected to permanently-opened of transforming operation, thus cause the intermediate
contact. relay K20 don’t close all the time.
b. Inside 4 and 5 terminal of pushbutton plug-ins has b. The cam switch S13 is out of effect and its
been broken. permanently-open contact can’t be closed normally.
c. Air break switch Q 1 itself is malfunction, to replace c. Contactor K1 (rising) or K2 (lowering) discharge
Q1. until there exists delay in release.
When next tap changer transforming to S14 (C, NO1)
7.5.2 Tripping during operation or S12 (C, NO1), It still don’t release when close again.
a. The phase sequence of three phase is wrong, the
phase protection cause tripping (see 4.2.3.3) 7.8 The motor can run, but step progress
b. Short circuit between safety switch and some power indication wheel can’t work
supply circuit. The fan block screw on step progress indication wheel
shaft is broken.
7.5.3 Revolve one step, tripping when stopped
a. The contact releasing of cam switch S12 or S14 is
7.9 Limit protection is invalid ( See 6.2.2)
not sync.
b. The restore force of cam wheel spring is too large,
7.10 Once power on, the pushbutton hasn’t be
which causing cam wheel knock reverse at cam switch
when restoring, and S12 or S14 instant conducted, thus pressed, but the motor drive unit will go up
making Q1 trip (see last par. of 4.2.3.3) (go down) one step automatically, and the
c. The continuous action, time relay action make intermediate relay K20 don’t release when
safety switch trip. stopped.
a. 1,2 terminal (up) or 3,4 (down) of pushbutton plug-
7.6 When stopped, the red line will appear deviation ins has been broken via.
(see 6.2.1) b. The external remote control pushbutton S3 (up) or
S4 (down) is improperly connected to permanently-close
7.6.1 Deviation of one direction contact, it should be connected to permanently-open
The cam wheel block is loosen and displaced, readjust contact.
cam wheel (see 6.2.1)
7.11 No indication on indicator
7.6.2 Deviation in both directions
a. Loosen because step progress position indication 7.11.1 No indication in overall indicator
wheel has not been tighten. Characteristic: position of a. 220V power supply has not been provided.
red line is at random, un-definite. b. The switch key of indicator has not been switched on.
b. The poor contact of auxiliary contact (motor short c. The cable from motor drive unit to control chamber
brake contact) of contactor K3 or contactor K3 discharge has not been connected or the plug-ins on both end hasn’t

15
been tighten. 7.12 The step of indication doesn’t correspond
d. When user add cable, the position indication share to that of site position indication wheel
terminal has been connected.
e. The plug of plug-ins is not suitable for the 7.12.1 Specific step is not corresponding.
arrangement of socket tube. a. The cable lead wire is improperly connected.
f. The indicator is broken. b. The lead wire of contact set contact is falsely
welded.
7.11.2 No indication for specific step
a. Poor contact of slide contact set 7.12.2 All steps are indicated
b. The lead wire of contact set contact is false-welded Loosen and displaced between the shaft of contact
or broken. arm and coupler.
c. Some cable lead wire connection is missing

8. HMC-3 Position Indicator For On Load Tap Changer

8.1 Introduction of performance c. Max. indication steps: 39 steps


HMC-3 type on-load tap changer step indicator can d.Operating temperature: -10~ 40℃
be used for the remote indicator provided that it is e. Hole dimension: width × height × depth
combined with remote position indication circuit (4.1.5) =150 × 75 × 166(mm3)
of motor drive unit. It also has the function of “raise” f. Weight: about 0.85kg
“stop” “lower” for tap changer, with remote indicator
lamp. 8.3 How to connect
HMC-3 indicator adopts integrated circuit control, a. Connect one end of cable of display to socket under
LED digital tube indication, which boasts high stability the bottom of motor drive unit box. The other end should
and reliability; its plastic housing is lightweight, small be connected to the socket at the back side of display.
volume, safe and easy to use. Attention: screw tightly to obtain good contact.
b. Connect operation command terminals
8.2 Technical data c. Connect operating voltage terminals to AC 220V.
a. Operating voltage : ~220V/AC d. Press the button of power supply, it can be put into
b. Operating frequency: 50 Hz/60Hz operation.

Terminal of indicator HMC-3 Motor Drive unit CMA7/CMA9 Remarks


1 8 Raise
2 12 Stop
3 9 Lower
4 11 Common
5 23
Remote control indication
6 24

Cable terminal connect to the back indicator.

16
HM0.460.003

9. Optional accessories
can display signal voltage, upper limit voltage (drop
Performance introduction of HMK-2 type on- voltage), lower limit voltage (rise voltage); Step indication
load voltage-regulating tap changer automatic can display the tap position of tap changer; The setting of
controller voltage can be set to the users’ desired range; The
HMK-2A type on-load voltage-regulating tap changer adjustment range of relay should be 20~180S. HMK-2A
automatic controller can be used for the manual or is also supplied with the function of locking “over-
automatic control of transformer on-load voltage- voltage” and “insufficient-voltage”, thus, if there exist
regulating. If the actual voltage of HMK-2A (wire PT any trouble in power network, HMK-2A will lock
second test voltage) compare with the set voltage, once automatically, and the capacity of controller getting rid
the voltage deviate from preset range, it will produce a of trouble is greatly enhanced. HMK-2A also has the
“1-N”or “N-1” control signal, thus making on-load tap function of alarm of over-voltage or insufficient voltage.
changer move from one tap change position to next one. HMK-2A has the function of over-current blocking and
HMK-2A has unique three voltage indication, which resistance-compensating.

17
Appendix 1 Composition of mechanical control system

18
HM0.460.003

Appendix 2 Connection diagram of position indication

one place decimal


Position indicator
Common
line

19
Appendix 3 Overall dimension diagram of CMA 9 motor drive unit

Grounding bolt M12

Hinge bolt

Wall of transformer tank


Insert

319 Cover
opened by 90°
Fixation of cabinet

864 cover opened by 180°

Aperture in cabinet for cable entry

20
Appendix 4 Circuit diagram of position indicator HMC-3C
HM0.460.003

21
1 2 3 4 5 6 7 8 9 10 11

22
380V/3PH/50Hz 220V/50Hz 220V/50Hz 220V/50Hz
L1
L2
L3 A
N
A X1 1 2 3 S3
X1-6 X1-16 X1-4 X3 N+1 1 N
13 S9
1 3 5 Q1
14 S4
Q1 /1.F8
/1.F8 X20-1 X1-24 X1-23 S41
I> I> I> X1-11 X1-12
X1-8 X1-9
1 3 7
2 4 6
S S38 18
R S8 2 4 8 K21 B
T 14
B /1.G7 V /1.G7 15 CX 15 1
S8
/1.G7 U W 21 21
S2 S1
22 22 X20-4 S40
21 1
13
R T R T 13 13 13
S6 S7 S1 K3 S2 14 S5 Q1 R1
14 14 22 CX 16 17 18 19
/1.G6 U W /1.G6 U W X20-2 /1.F7 14
X20-3 /1.F8
2
72 52 62 C X20-5 K1
C 14 34 24 S12 1 /1.F4 53 54
C 3 1 3 1 S14 K20 X10
NO1/1.F5 /1.F6 53 K2 54 C
K1 K2 /1.G8 71 51 13 33 23 61 /1.G8 NO1
4 2 4 2 X1-14 2 /1.F8 31 Q1 32
/1.F4 /1.F6
6 S16 C S13 NO1 6 S17 C 13 13 S14 C S12 C
K1 K2 K1
/1.F4 /1.G6 NC /1.G8 K2 NO2
5 NO2 /1.F6 5 /1.G6 NC /1.F4 14/1.F6 14 /1.G8 NO2 /1.G8
4 6 2 22 32 42 52 X1-25 X1-26

K3 X20-7
3 5 1 21 31 41 51 S S 42 42 K1
/1.F7 /1.F4 23 24
S6 S7 K1 K2 H1
D V /1.F6 K2 D
/1.G6 /1.G6 V /1.F4 41 /1.F6 41 23 24
X20-6
32 32 NC1
43 S13
W1 V1 U1 X1-19 K2 K20 K1
/1.F6 31 /1.F4 31 /1.G8 NC2
A1 /1.F5 44 X1-27 X1-28

M1 M H3 K21 A1 A1 A1 A1 C1
3
~ A2 /1.G7 K1 K20 K2 K3 Q1 Q1
/1.F4 /1.F6 X1-17 X1-18 /1.F8 43 44
V2 X1-20 X1-5 A2 /1.F5 A2 A2 /1.F7 A2 /1.F8 C2

E N H2
E
Contact closed X1-7
N
S12 N X1-13 Q1
K20 H1 SIGNALLING LAMP "Q1 OFF" K3 BRAKE CONTACTOR
S13
K1 K2 K3 H2 SIGNALLING LAMP "Q1 OFF" (CONTROL ROOM) K21 TIME RELAY
A1 A2 A1 A2 A1 A2 A1 A2 H3 TAP CHANGE IN PROGRESS LAMP (CONTROL ROOM) R1 HEATER
/1.E4 /1.E5 /1.E6 /1.E7 Q1 MOTOR PROTECTIVE SWITCH X10 SOCKET
<I

S14 /1.A1 1 2
/1.C2 1 2 /1.C4 13 14 /1.C3 1 2 /1.D2 1 2 S1, S2 PUSH BUTTON FOR K1,K2 M1 MOTOR
3
<I

3 4 /1.C5 23 24 /1.C2 3 4 /1.D1 3 4 /1.A2 4 S3, S4 PUSH BUTTON FOR K1,K2 (CONTROL ROOM)
/1.C1 X1, X3 TERMINAL BARS
<I

5 6 /1.C5 33 34 /1.D6 5 6 /1.D2 5 6 /1.A2 5 6 S5 EMERGENCY PUSH BUTTON "OFF" FOR "Q1"
/1.D4 /1.B3
/1.D7 13 14 /1.D5 43 44 /1.D7 13 14 /1.C5 13 14 13 14 S6, S7 LIMIT SWITCH (MOTOR)
F WHEEL OF INDICATION /1.D11 23 /1.C4 51 /1.D11 23 /1.D2 21 /1.C9 22 S8 SAFETY SWITCH F
24 52 24 22 21
GREEN ZONE /1.E6 31 32 /1.C6 61 62 /1.E4 31 32 /1.D2 31 32 /1.D11 43 44 S9 PUSH BUTTON "Q1 OFF" (CONTROL ROOM)
/1.D8 41 42 /1.C4 71 72 /1.D8 41 42 /1.D3 41 42 /1.D11 S12, S14 CAM SWITCHES FOR CONTROL DIRECTION
RED CENTER MARK 31 32
/1.C11 53 54 81 82 /1.C11 53 54 /1.D3 51 52 S13 CAM SWITCHES FOR STEP-BY-STEP OPERATION
1 /1.E8 C1 C2 S38 "REMOTE"/"LOCAL" SELECTOR
S37 S40, S41 N/O CONTACT RANGE(POSITION INDICATION)
S6 S7 S8 X20 INTERMEDIATE CONNECTER
2 X3 S12 S13 S14

K21-18
X1

K21-A2
/1.C1 /1.C2 U R /1.B1 U R K1, K2 MOTOR CONTACTOR
NC1
/1.D4 /1.D6 V S /1.B3 V S NO1 K20 STEP BY STEP RELAY
T /1.C6 /1.C5 /1.C3 C S16,S17 LIMIT SWITCH (CONTROL)
W T W

R1-1

Q1-1
Q1-3
Q1-5
R1-2
S41
S41
S41

S37-1

Q1-13
S38-3
X20-5
K2-6
Q1-21
X20-6
Q1-22
K3-51 K21-A1
M1-V2
S38-7
S38-8

X20-4 K20-72

K1-A2
K20-14
K20-24
K20-44
K1-23
K1-24
Q1-43
Q1-44

S13-NO1 K3-13
/1.C2 /1.C3 /1.B2 /1.D8 NC2 CX TERMINAL SOCKET FOR HMC-3
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 1 2 N /1.C8 /1.C8 NO2

N+1 S41
L1 L2 L3 L1 N L1 N L1 N K21 G
S16 S17 A2 A1
G /1.C4 /1.C6 NC /1.E3
C 16
Power Supply Signal output 15 CMA9 Circuit Diagram
Remote control signal (input) NO /1.B8 18
380V/3PH/60Hz

1 2 3 4 5 6 7 8 9 10 11

Appendix 5 CMA9 electrical principle diagram


HM0.460.003

Appendix 6 Explanation of terminal X1 and X3

Explanation of X1 terminal:
X1Terminal No. Explanation

Power supply input, voltage of L1, L2 and L3: 380V/50Hz


1,2,3,5
Voltage of L1 and N: 220V/50Hz

8 For remote control “raise” command input

9 For remote control “lower” command input

10,11 Shared by remote control command.

12 For remote control “stop” command input

18 For emergency trip signal output (output 220V/50Hz power signal)

19,20 For motor operation signal output (output 220V/50Hz power signal)

23,24 “Remote control/local” change over switch, for “remote control” status signal output (output captive signal)

25,26 For motor operation signal output (output captive signal)

27,28 For safety switch “close” status signal output (output captive signal)

Explanation of X3 terminal:
The signal provided by X3 is a set of one to one correspondence step captive signal, among of them, X3-N+1 is step share
terminal, X3-1to X3-N corresponds to step 1 to N of tap changer.

23
Appendix 7 Explanations of CX terminals

CX output decimal position signal, CX is generally connected to HMC-3 display.

CX Socket No. Explanations

CX-1 Tap changer position signal digit “1”

CX-2 Tap changer position signal digit “2”

CX-3 Tap changer position signal digit “3”

CX-4 Tap changer position signal digit “4”

CX-5 Tap changer position signal digit “5”

CX-6 Tap changer position signal digit “6”

CX-7 Tap changer position signal digit “7”

CX-8 Tap changer position signal digit “8”

CX-9 Tap changer position signal digit “9”

CX-10 Tap changer position signal digit “0”

CX-11 Tap changer position decimal digit “0”

CX-12 Tap changer position decimal digit “1”

CX-13 Tap changer position decimal digit “2”

CX-14 Tap changer position decimal digit“3”

CX-15 Tap changer position signal digit “com”

CX-16 Tap changer position signal digit common terminal

CX-17 “raise” indication

CX-18 “lower” indication

CX-19 “Stop” indication

24
HM0.460.003

NOTICE TO USE AND ORDER

Customer and end-user should record the operation and inspection of the tap changer. In case of special
condition, please contact with us and give us your report for data collecting purposes that we can give you
possibly further recommendations for your next inspection.
After the OLTC sold out from the factory within 18 months, in case of any damage or malfunction of the
OLTC due to the manufacturing quality encountered by the customer or end-user under the regulations of
storage and application, we can give you inspection and repair work without charges.

Generally the provided cable lead for the indicator is 30M. Please specify your special requirement
when you give your order.

Our factory is sincerely providing best quality products, good service and preferential prices for our
customers.

WARMLY WELCOME YOU TO GIVE US COMMENT AND SUGGESTION FOR OUR


PRODUCTS. THANK YOU FOR YOUR SUPPORT AND COORDINATION.
WE WOULD LIKE TO PROVIDE OUR CUSTOMER WITH HIGH QUALITY PRODUCT,
EXCELLENT SERVICE AND PREFERENTIAL PRICE.
Shanghai Huaming Power Equipment Co., Ltd
Address:No. 977 Tongpu Road, Shanghai , China
Post code:200333
Tel. 86-21-52708966, Fax. 86-21-52703385
http://www.huaming.com
Email:public@huaming.com
Printing 2004.10