Professional Documents
Culture Documents
I. INTRODUCTION
The power flow through a corridor is estimated by the
following equation (series resistances and shunt admittances
are neglected):
Δα Detect- 6)
ion Series Transformer
EA. EB
PAB sin Fig. 1. Connection diagram of a PST designed as two separate transformers
XAB (Indirect type)
(1)
With advancement in the technology of OLTC
manufacturing, both functions are now possible to be
in which PAB is the power flowing from A to B, E A is the
combined in a single transformer with delta/hexagonal
voltage phasor at sending end A, E B is the voltage phasor connection, schematically shown in Fig. 2.
at receiving end B, XAB is the series reactance between A and
B and δ is the angle difference between E A and E B .
From (1) it is clear that power flow is dependant
significantly to the angle difference between sending and
receiving end voltages. If the angle between two ends can be
regulated, the power flow can be controlled. Phase Shifting
Transformers (PST), sometimes called as Phase Angle
Regulating (PAR) transformers, are placed in series with
important lines of a power corridor or combined with power
transformers between two voltage levels, to regulate the
Authors are with ALSTOM Grid, P.O.Box. 48957, Dubai, UAE, (e-mail :
Fig. 2. PST with delta/hexagonal winding connection
slobodan.mladenovic@alstom.com and ali.azadvar@ieee.org )
2
A connection diagram of this PST which is classified as The latest solutions for differential protection of PST’s are
“Direct” type is shown in Fig. 3. based on transmitting the tap position of OLTC mechanism
to the numerical differential element [2], [3], [4], [6]. Correct
information regarding the phase shift α, corresponding to the
transmitted tap position, should already be set to the relay
from PST nameplate.
Tap position can be transmitted from OLTC mechanism to
differential element by using analog transducer providing
stepwise milliamp signals proportional to each tap position,
or via binary coded decimal (BCD) signal which allocates a
digital code to each tap position. Reliable and error free
information from a mechanical device and transmitting it to a
Fig. 3. Connection diagram of a PST designed as one transformer
dedicated protective instrument, however, would not be
(Direct type) sufficiently ensured. For instance, in case of utilizing BCD
signal, the state of all bits will not be changed at exactly the
The phase shift across a standard transformer is zero or an same time, thus making error in calculation of phase shift
increment of 30 degrees at each phase, which is the result of compensation. Failure of the mechanism itself and
a fixed combination of currents from the other phases. unavailability of data during transition between steps are
Because of this phase shift, the currents going to differential other problems in applying this solution [2].
protection of the transformer are required to be compensated, This paper introduces a method to compensate the phase
so that in balance conditions, as well as any unbalanced shift angle of PST on the input currents of differential
disturbances outside the transformer, all the current phasors elements without any requirement to transmit tap position.
sum to zero.
In a PST as the phase shifting is the main task, it is
continuously varying by the position of tap changer II. PHASE SHIFTING OF SYMMETRICAL COMPONENTS IN A PST
mechanism to create the amount of phase shift required to Angle shifting in phase currents and voltages across a PST
regulate the power flow to the set point. Here, the magnitude is applied by injecting to each phase, a controllable value
of the currents from the other two phases that are combined from voltage of other phases. In this paper the source side, S
with the phase current is not fixed. In other words, phase shift is taken as reference side (phase angle zero), and the load
“α” across PST is the function of tap position “n” which is side, L is assumed as shifting side (phase angle α). The
continuously varied. Phasor diagram of the PST in Fig. 3 is following equations can be written for all three phases in
presented in Fig. 4 emphasizing the fact that α and thus ΔU most general forms:
are functions of tap position n.
UL1=US1* x∠α(n) IL1= p. IS1+ q. IS2+ r. IS3 (2-
1)
IL2= r. IS1+ p. IS2+ q. IS3 (2-
2)
x=1 Symmetrical PST IL3= q. IS1+ r. IS2+ p. IS3 (2-
x≠1 Asymmetrical PST
3)
(4) I ns j . Ins
L1 = x. e S1 (8-
I I 3)
I I p q r I
INS = Aˉ ¹ . r p q .A. I
q r p (8) implies that if the positive sequence current component at
S side is shifted by angle α across PST, then its negative
sequence component will be shifted by angle – α. In other
where
words, for any given values of p, q and r determining by a
1 1 1 specific tap position n:
A= 1 a² a - The zero sequence component at L side is in phase with the
1 a a² same component at S side
zs ps ns
- The positive sequence component at L side is the shifted
a = e j120 and a² =e j 240 . Also I , I and I are positive sequence component at S side by angle α
magnitude of zero, positive and negative sequence - The negative sequence component at L side is the shifted
components respectively for IL1 and IS1, and Aˉ ¹ is the negative sequence component at S side by angle – α
inverse of A. α is the phase angle shift across PST of balanced load current
Substituting A and Aˉ ¹ in (4) and doing some or no load voltage, stipulated on the nameplate, for position
mathematical calculations, the following relation is derived: n of the OLTC.
(5) This means if the position n is transmitted to the relay, and
I if the look up table containing the angle α corresponding to
I
I I p+q+r 0
Time
0 every value of n are already set in the relay, then in case of a
Synch. I
INS = 0 p+a²q+ar 0 disturbance causing an unbalance condition, the relay can
I
0 0 apply appropriate phase shift to sequence components as
p+aq+a²r stated above and extract compensated three phase currents,
ready for measurement by a conventional restraint
In equation form, (5) may be written as follows: differential element. This solution is now being applied for
zs zs
I L1 = (p+q+r) . I S1 (6- differential protection of PST’s. [2]-[6] and [11]-[18]
1)
ps ps
I L1 = (p+a²q+ar) . I S1 (6- III. DIFFERENTIAL PROTECTION FOR PST
2)
ns
Differential element is normally applied as main protection
I ns
L1 = (p+aq+a²r) . I S1 of power transformers including autotransformers and PST’s.
(6-3) As power transformer contains magnetic linkage, protecting
it by a differential element is encountered with many
As p, q and r are real numbers, (6-1) indicates that zero challenges compared with a simple electrical node such as a
sequence components, in case it could be transferred, does busbar. Some of the most important challenges are as follow:
not experience any phase shift across PST, so that “zero - phase shift due to combination with other phases
sequence transfer factor” is a real number y. Suppose that - magnitude mismatch due to transformation ratio
“positive sequence transfer factor” in (6-2) is x with angle α, - zero sequence transmission
that is - inrush currents (energizing, recovery, sympathetic)
- overexitation
p+a²q+ar = X = x. e j (7- There are well developed solutions for each of these
1) problems regarding normal power transformers. These
solutions are valid in case of PST as well; however,
it is then simply verified that “negative sequence transfer compensation of the variable phase shift is still developing.
factor” in (6-3) would be: This paper focuses on a simple method to mimic the variable
phase shift across PST on current transformers output, before
p+aq+a²r = X * = x. e j (7- applying to a conventional restraint differential element.
2)
Substituting (7) into (6) yields:
is not only function of n but also depending to the current sequence currents at both sides is obtained by subtracting the
magnitude of other phases at the same time. At balance measured angle α from phasor angle of positive sequence
condition, (2-1) can be written as indicated below: current at L side. Similarly, to align negative sequence
currents, the angle α should be added to measured phasor
IL1= (p+a²q+ar) . IS1 (9) angle of negative sequence component at L side. The zero
sequence current would not experience any angle shift, if it
Substituting from (7), this equation can be rewrite as has to be transmitted. The mirrored phase currents at L side
follows: are now calculated from these new sequence components,
IL1= x. e j . I S1 (10-1) and together with the phase currents at S side are connected
to a conventional restraint differential element for further
Similarly, for other two phases the following relations may processing.
be obtained from (2-2) and (2-3): Fig. 5 depicts a simplified block diagram of the new phase
shifting compensator.
IL2= x. e j . I S2 (10-2)
IL3= x. e j . I S3 (10-3) 2)
Input Phase Shift 5)
Trans& A/D I / In Compensation IS
Analog converte I - Io
This means as long as the system is balanced, any tap Filter r
Seq.
position n applies a unique phase shift α on all three phases Filter Pos.
+
3)
α transient
Filter&
-
equally. But in case of an unbalance fault, obviously neither 1)
Memory
Differential
Time 6)
all phases experience an equal phase-shift, nor have the angle Synch.
Δα
Detect-Seri
Element
ion es
shifts such a simple relation with tap position n. The phase A/D Tran
convert
shift α corresponding to the tap position n indicated on the Input
2)
Pos.
er sfor
-α
Input4)mer
nameplate of a PST is always defined at balance condition. Trans&
Analog
A/D
converte
I / In
I - Io
Seq.
Filter Neg.
Trans&
α
Analog
Phase
Current
IL
Extract-
The relation between sequence currents as shown in (8) Filter r Filter
ion
1) Unlike phase currents, any sequence current at side L 1) Sampling time synchronization
2) Amplitude normalizing & zero sequence cancellation (if required)
depends only on the same sequence at side S. This means that 3) Angle Difference Measuring
the angle shift of each sequence current is only function of 4) Phase Angle Shifting clockwise (-α) and counter clockwise (α)
5) The dashed part is replaced by “vector group compensation” in traditional diff. protection
tap position n. 6) Detection of internal fault incidence
2) For a given tap position n, the angle difference between Fig. 5. Simplified block diagram for phase shift compensation
positive sequence at sides S and L is always α, whether or not
the system is balanced.
To describe this more in detail, suppose that the system at a In this method, the input currents from both sides to
moment t is in balance condition and OLTC is in tap position differential protection are aligned in a way to compensate the
n. Further, suppose that at this moment the phase shift across phase shifting across main transformer, whether this shifting
the PST is α. This angle obviously is the same as the angle is variable, like a PST, or fixed, same as standard power
difference between positive sequence components of the two transformers. In fact, as indicated in Fig.5, replacing this
sides, as it is clear by comparing (8-2) with (10-1). If at the solution by “vector group compensator” in conventional
moment t an unbalanced through fault happens, the angle α differential relays, it may be utilized for any kind of power
between positive sequence currents at L side and S side transformers and PST’s without any need for setting and
remains intact, as the tap position n has remained unchanged, adjusting the relay for vector group of the main transformer.
while the angle difference between IL and IS in any of the
phases is no longer α. This means simply that by measuring
the angle difference between positive sequence components
of the two sides continuously, the relay can compensate for
shifting of the sequence current components at L side for any
system conditions based on equations (8). Compensation for
phase currents is obtainable accordingly, without any
requirement to import OLTC tap position.
B. Developing a new solution
The new solution for differential protection of PST requires
extracting continuously the sequence components of current
at L side as well as the positive sequence current at S side. It
is based on measuring the angle difference α between
positive sequence currents at L and S sides. In this method,
phase shift compensation is rendered by alignment of
sequence components. Assume that S side is reference when
measuring the angle difference. Then alignment of positive
5
angle shift across PST or any other standard transformer by [18] Hedding, R.A.; “ Some old and new thoughts on phase angle regulator
protection”; Protective Relay Engineers, 2010, 63 rd Annual Conference
measuring the angle difference between positive sequence for, pp1-13.
currents of both sides. It does not require transmitting actual [19] Sevov, L.; Wester, C.; “Phase Angle Regulating Transformer Protection
tap position of PST to the relay. The solution was simulated Using Digital Relays”; Development in Power System Protection, 2004,
mathematically and tested successfully for stability in case of 8th IEE International Conference on, Volume 1, pp 376-379.
all types of external faults, while sufficient sensitivity was
achieved for internal disturbances.
V. REFERENCES