Professional Documents
Culture Documents
SIMRAN GOEL
Aim:
I) To draw the Magnetization characteristics and load characteristics of current
transformer
II) To calculate the ratio error and phase angle for the given CT.
Apparatus Required:
Theory:
The CTs and PTs used in protective relaying have two important roles to play namely:
Electrically isolate the protective relays from the high-voltage power system for ,
the purpose of safety of the operating personnel.
Step down the current and voltage to standard values of 1 A, 5 A, 110 V so that
the design of relays can be standardized irrespective of the actual primary voltage
and current.
Measurement CT and Protective CT
CTs are also used for measurement purposes. However, the desired response
from measurement CTs under short-circuit conditions (when the primary current is high)
is Quite different. A protection CT is required to faithfully transform the primary current
Throughout its entire range from normal load current to short-circuit current. A
measurement CT, on the other hand, is designed to saturate at currents more than
around 1.2 times the full-load current, and thus save the measuring instruments from
possible damage.
By suitable design, the operating point of the measurement CT is kept near the knee
of the excitation characteristic. The knee point is defined as that point on the excitation
characteristic at which 10% increase in excitation voltage results in a 50% increase in the
excitation current (Fig.1)
.
Loading Rheostat
(0- 10)A
A
CT
(O-10) A
P1 S1
V
230 V
Single AC V (O-30)V
(0 – 300) V MI P2 S2 MI
1 Variac
Load Characteristics
For IP vs IS
Loading Rheostat
(0- 10)A
A
CT
(O-10) A
P1 S1
V
230 V (0 – 300) V MI
Single AC A (O- 1)A
P2 S2 MI
1 Variac
Observation Table:
Magnetization characteristics
IP (A) VS (V )
1.01 9
2.04 12
2.44 13
3.45 15
4.43 16
6.29 17
Load Characteristics:
IP(A) Is(A)
1.03 0.25
2.06 0.5
2.46 0.6
3.48 0.85
4.48 1.1
6.36 1.55
MODEL GRAPH
SATURATION
Secondary voltage, Vs in
KNEE REGION
KNEE POINT
REGION
LINEAR
ANKLE POINT
V
IP in A
Fig. Magnetization characteristics
Is (Amps)
IP ( Amps)
Fig. Load characteristic
Conclusion:
Aim:
To study the earth leakage protection scheme used for single phase and three
phase loads.
Apparatus:
S.No Description Range Type Quantity
1. Core Balance Transformer (0- 100)mm - 1
2. Ammeter (0-500)mA AC 1
3. Ammeter (0 - 10)A AC 1
4. 1 Auto Transformer (0- 230)V AC 1
5. Loading Rheostat (0 – 10)A 3 1
Iph = In + IP
Iron core
Flux
P
Ph Ph Earthed
N Chassis
N N
C
N Fig 1
Under normal operating conditions, the current through the phase wire is exactly
the same as that through the neutral wire .Thus there is no magneto motive force (mmf)
acting on the toroidal core. The flux linked with the pickup coil is therefore zero, and thus
no voltage is induced in the pickup coil and the ammeter remains energized.
Earth Leakage Protection for Three – Phase Loads
The earth leakage protection scheme used for three phase loads is shown in Fig.2.
The three phase leads are threaded through a CT core on which a pickup coil is provided
as in the case single phase earth leakage protection.
Ia + Ib +Ic =ILEAK
Iron core flux
(0-10) A
R R
Y Earthed
Y Chassis
B B
(0-600) v
N
N
3 Ф load
A
3 Ф supply
Fig 2
During the normal balanced operating condition, the phasor sum of the three phase
currents is zero. Therefore is no net mmf acting on the core and the OC relay remains un
energized. However, during the earth Leakage situation shown in Fig, the net mmf acting
in the core is (Ileak) ampere – turns. This causes a flux to be produced. A voltage is induced
in the pickup winding causing the OC relay connected across it to operate.
Earth leakage protection circuit breakers (ELCB) implement this relay circuit for
the protection of three phase transformers and other equipment’s from earth faults.
Circuit Diagram:
P. A
(0 – 10A)
Loading Rheostat
230 V (0- 10)A
V
Single AC
(0 – 300 V) S1 S2
1 Variac
A
Core Balanced Transformer
(0 – 500mA)
1 0 1 0
2
0 2 10
Three phase load
Balanced condition Unbalanced Condition
( Normal operation) (During earth fault)
Ip (A) Is (mA) Ip (A) Is (mA)
2.4 0 2.4 20
3.5 0 3.5 60
Conclusion:
We have successfully studied the earth leakage protection scheme used for single phase and three
phase loads.
When the line and neutral core is passed inside the core balance transformer, the current through the winding is 0.
when only the line wire is passed through it, current in third winding increases as we increase load. This is due to
imbalance created inside the core balance transformer, flux and current induced.
MICRO-CONTROLLER BASED OVER/UNDER VOLTAGE RELAY
IDMT/DMT RELAY
AIM
i. To study the Micro Controller based over voltage relay.
ii. To study the Micro Controller based Under Voltage relay.
EQUIPMENT REQUIRED
1) VPL – 05 Module
2) 1 φ Auto transformer
3) Connecting wires
Formulae Used:
𝐾
𝑡 = 𝑇𝑀𝑆 [ ]+𝐶
𝑉 𝛼
[𝑉 ] − 1
𝑆
𝐾
𝑡 = 𝑇𝑀𝑆 [ ]+𝐶
𝑉𝑆 𝛼
[𝑉 ] − 1
𝜶 = 𝟎. 𝟎𝟐, 𝑲 = 𝟎. 𝟏𝟒, 𝑪 = 𝟎
Theory
The static relay circuits have no moving parts, there are two contacts provided
in static relay they are relay contact and NC (normally closed) contact. The relay
contact which is opened normally gets closed and NC contact gets opened
automatically during fault. The Micro controller based static relay is programmed to
make the relay to operate in IDMT as well as in DMT mode.
1. It is No Moving Parts
2. It is reliable
3. External power supply has to be needed for static relay.
The block diagram shows the hardware of microcontroller based over current
relay in which current transformer rating of 10V / 10A is placed at the input of
microcontroller. The output of CT secondary, current and voltage is adjusted by
means of trimpot to have 5 Amps is given to the microcontroller. The Programming is
done in Microcontroller in such a way, when the fault current value is above the set
value the relay contact is closed/opened (depends on connections) and trips the
circuit. The LED display shows the fault current value and the LCD is to show the set
time, set current, fault current and the tripping time.
The microcontroller output is of 5V / 0V. Relay circuit operates at the voltage of
24V, hence, a transistor is placed in between the relay circuit and the microcontroller
to improve the voltage input to relay circuit. As and when the fault current flows in the
CT, it gets actuated and relay contact is closed and NC is open to trip the circuit .
It is consists of
1. LCD display
2. Input terminal
3. Buttons
4. Static Relay.
Input terminal
Function of Buttons
5. Press the button - 1 (select a over voltage operation) the following message will be displayed.
OVER VOLTAGE
After few seconds
SET VOLT = V
Set the voltage by using buttons, 1,2,3,4
Example
* 5 times press the button - 1 set 5 value and press the button - 3.
7. Trip the relay, when input voltage is exceed set voltage. Now source is remove from the
faulty section the display is displayed.
1 OVER VOLTAGE
2 UNDER VOLTAGE
5. Press the button -2 (select a under voltage operation) the following message will be
displayed.
UNDER VOLTAGE
SET VOLT = V
* 8 times press the button - 1 set 5 value and press the button - 3.
7. Trip the relay, when input voltage is below the set voltage. Now source is remove from the
faulty section the display is displayed.
Tabulation:
IDMT
DMT
Time Multipler
Fault Actual Relay
S.No Set Voltage (Vs) Setting - TMS
Voltage (VF) Tripping Time
(Volts) (Volts) (Sec) (Sec)
Over Voltage
1 100 170 0.1 5s
2 100 109 0.1 5s
3 100 145 0.1 5s
4
5
6
Under Voltage
1. 100 90 0.1 5s
2. 100 60 0.1 5s
3. 100 30 0.1 5s
4.
5.
6.
Result:
Conclusion:
For DMT relays, the time of operation/ tripping time is the same even with the
changes in the fault voltages in either conditions that is under/over voltage.
For IDMT relays, we see that the change in voltages in overvoltage condition
results in a faster tripping time compared to that of in undervoltage condition.
Also, the actual and calculated tripping time seem to be appearing similar.