Professional Documents
Culture Documents
Quality Assurance
Alternators are manufactured using production procedures having a quality assurance level to BS EN ISO 9001.
Page 1 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
Electrical Data
Page 2 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
Mechanical data
Cooling Air 0.176 m³/sec (50Hz) 0.211 m³/sec (60Hz)
All alternator rotors are dynamically balanced to better than
Shaft and Keys
BS6861: Part 1 Grade 2.5 for minimum vibration in operation.
Page 3 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
Page 4 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
50Hz
60Hz
Transient Voltage Dip Scaling Factor Transient Voltage Rise Scaling Factor
PF Factor
< 0.5 1.00 For voltage rise multiply voltage dip by 1.25
0.5 0.97
0.6 0.93
0.7 0.90
0.8 0.85
0.9 0.83
1.0 0.80
Page 5 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
Three-phase Short Circuit Decrement Curve
50Hz
60Hz
Page 6 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
400V/50Hz
480V/60Hz
Page 7 A055R776_RevA_14.07.2016
S1L2-R1 Winding 311 / 711
Class - Temp Rise Standby - 163/27°C Standby - 150/40°C Cont. H - 125/40°C Cont. F - 105/40°C
Series Star (V) 380 400 415 440 380 400 415 440 380 400 415 440 380 400 415 440
50 Parallel Star (V) 190 200 208 220 190 200 208 220 190 200 208 220 190 200 208 220
Hz
Series Delta (V) 220 230 240 254 220 230 240 254 220 230 240 254 220 230 240 254
kVA N/A 55.0 55.0 N/A N/A 53.3 53.3 N/A N/A 50.0 50.0 N/A N/A 45.5 45.5 N/A
kW N/A 44.0 44.0 N/A N/A 42.6 42.6 N/A N/A 40.0 40.0 N/A N/A 36.4 36.4 N/A
Efficiency (%) N/A 88.3 88.4 N/A N/A 88.5 88.7 N/A N/A 89.0 89.1 N/A N/A 89.5 89.6 N/A
kW Input N/A 49.9 49.8 N/A N/A 48.2 48.1 N/A N/A 45.0 44.9 N/A N/A 40.7 40.6 N/A
Series Star (V) 416 440 460 480 416 440 460 480 416 440 460 480 416 440 460 480
60 Parallel Star (V) 208 220 230 240 208 220 230 240 208 220 230 240 208 220 230 240
Hz
Delta (V) 240 254 266 277 240 254 266 277 240 254 266 277 240 254 266 277
kVA 58.1 61.0 N/A 66.0 56.5 59.3 N/A 64.0 52.8 55.4 N/A 60.0 48.0 50.5 N/A 54.6
kW 46.5 48.8 N/A 52.8 45.2 47.4 N/A 51.2 42.2 44.3 N/A 48.0 38.4 40.4 N/A 43.7
Efficiency (%) 89.8 89.8 N/A 89.6 90.0 89.9 N/A 89.8 90.3 90.3 N/A 90.2 90.7 90.7 N/A 90.6
kW Input 51.8 54.4 N/A 58.9 50.2 52.7 N/A 57.0 46.8 49.1 N/A 53.2 42.3 44.5 N/A 48.2
De-Rates
All values tabulated above are subject to the following reductions:
- 3% for every 500 meters by which the operating altitude exceeds 1000 meters above mean sea level
- 3% for every 5°C by which the operational ambient temperature exceeds 40°C
- For any other operating conditions impacting the cooling circuit please refer to applications
Note: Requirement for operating in an ambient exceeding 60°C and altitude exceeding 4000 meters must be
referred to applications.
Note: Continuous development of our products means that the information contained in our data sheets can change
without notice, and specifications should always be confirmed with Cummins Generator Technologies prior to
purchase.
Page 8 A055R776_RevA_14.07.2016
Follow us @stamfordavk