Alternator Data Sheet

Frame Size: SOL2-M1

Characteristics 1-bearing weight


Weights: Stator assembly: 108 lb 49.0 kg
Rotor assembly: 96 lb 43.4 kg
Complete assembly: 267 lb 121.1 kg
Maximum speed: 2250 rpm
Excitation current: Full load: 3.6 Amps
No load: 0.86 Amps
Insulation system: Class H throughout
1 ∅ Ratings 60 Hz (winding no)
(Based on specific temperature rise at 40° C
ambient temperature)
0.8 power factor 1.0 power factor

120/240 120/240
(06/706) (06/706)
163° C rise ratings @ 27° C kW 17.0 22.9
kVA 21.2 22.9
150° C rise ratings kW 16.4 22.2
kVA 20.5 22.2
125° C rise ratings kW 15.4 20.8
kVA 19.3 20.8
105° C rise ratings kW 13.9 18.8
kVA 17.4 18.8
(per unit ± 10%)
1 ∅ Reactances 0.8 power factor 1.0 power factor
(Based on full load at 125° C rise 120/240 120/240
rating) (06/706) (06/706)
Synchronous 0.896 0.966

Transient 0.099 0.107

Subtransient 0.098 0.106

Negative sequence 0.206 0.222

Zero sequence 0.072 0.078

1 ∅ Motor starting 120/240


(06/706)
(90% sustained voltage)
Maximum kVA 45

Time constants 120/240


(sec) (06/706)

Transient 0.024
Subtransient 0.001
Open circuit 0.561
DC 0.012
Windings (@22° C) 120/240
(06/706)

Stator resistance (Ohms per phase) 0.097


Rotor resistance (Ohms) 0.747
Number of leads 4

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Characteristics 1-bearing weight


Weights: Stator assembly: 108 lb 49.0 kg
Rotor assembly: 96 lb 43.4 kg
Complete assembly: 267 lb 121.1 kg
Maximum speed: 2250 rpm
Excitation current: Full load: 3.6 Amps
No load: 0.86 Amps
Insulation system: Class H throughout
3 ∅ Ratings (0.8 power factor) 50 Hz (winding no) 60 Hz (winding no)
(Based on specific temperature rise at 40° C 190/380 200/400 208/415 208/416 220/440 240/480
ambient temperature) (311/711) (311/711) (311/711) (311/711) (311/711) (311/711)

163° C rise ratings @ 27° C kW 20.2 22.0 22.0 23.2 24.6 26.4
kVA 25.2 27.5 27.5 29.0 30.8 33.0
150° C rise ratings kW 19.5 21.4 21.4 22.6 23.9 25.6
kVA 24.4 26.7 26.7 28.2 29.9 32.0
125° C rise ratings kW 18.3 20.0 20.0 21.1 22.4 24.0
kVA 22.9 25.0 25.0 26.4 28.0 30.0
105° C rise ratings kW 16.6 18.2 18.2 19.2 20.4 21.8
kVA 20.8 22.8 22.8 24.0 25.5 27.3
(per unit ± 10%) 190/380 200/400 208/415 208/416 220/440 240/480
3 ∅ Reactances
(311/711) (311/711) (311/711) (311/711) (311/711) (311/711)
(Based on full load at 125° C rise rating)
Synchronous 2.318 2.284 2.122 2.676 2.537 2.284
Transient 0.154 0.152 0.141 0.178 0.169 0.152
Subtransient 0.129 0.127 0.118 0.149 0.141 0.127
Negative sequence 0.236 0.233 0.216 0.272 0.258 0.233
Zero sequence 0.050 0.050 0.046 0.058 0.055 0.050
(90% sustained voltage)
Maximum kVA 30.5 37 40 31.5 38 49.5

Time constants 190-415 208-480


(sec) (311/711) (311/711)

Transient 0.021 0.021


Subtransient 0.002 0.002
Open circuit 0.552 0.552
DC 0.006 0.006
Windings (@22° C) 190-415 208-480
(311/711) (311/711)

Stator resistance (Ohms per phase) 0.290 0.290


Rotor resistance (Ohms) 0.747 0.747
Number of leads 12 12

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)
Alternator Data Sheet
Frame Size: SOL2-M1

Cummins Inc. Data and specification subject to change without notice ADS-612
(07/18)