3-5

Date: 08/01/14 Customer: Bitte Interessent eingeben!


Project No.: AvK Reference: 1-203-0000032-1
Object data:
Site: Prime Mover:
Application: Stationary Power Plant Manufacturer:
Generator data:
Generator: DSG 86 K1/4 L Poles: 4 Standards: IEC 60034
Rated power: 1000 kVA 800 kWe 835 kWm
Power factor: 0.80
Power at pf 1,0 806 kVA 806 kWe 835 kWm
Rated voltage: 0.69 kV
Speed: 1500 1/min
Frequency: 50 Hz Voltage range / frequency range:
Rated current: 836.7 A Zone A according IEC 60034-1 (dU = +/-5%, df = +/-
2%)
Winding pitch:
Insulation class: Stator: Class H Rotor: Class H Temperature rise: B
Ambient temperature: 40 ° C Environment: Standard environment
Site altitude: 1000 m
Enclosure: IP44 Filter: n.a.
Cooling: IC616 - Air-to-air heat exchanger-fan motor in outer circuit
Coolant: Ambient Air Temperature 40 ° C Temperature Air inlet 55 ° C
Coolant: generator:
Cooling air vol.: 2.9 m³/s Cooling water quantity: n/a
Moment of inertia (I): 60 kgm² Weight: 5250 Kg Losses (environment): 35 KW
Losses (cooling): n/a
Connections and regulators:
Wires: 4 terminals, starpoint connected in terminal box
Operation mode: Parallel with the grid and island mode
Regulators:
Voltage regulator: DECS 100
Electrical data: (acc. IEC)
Efficiencies: 110% 100% 75% 50% 25%
Power factor 0.8 95,57 95,79 95,17 93,97 0
Power factor 0.9 95,94 96,14 95,44 94,17 0
Power factor 1.0 96,3 96,48 95,71 94,37 0

Reactances and time constants


unsaturated saturated unsaturated saturated

xd 1.26 1.13 p.u. xq 0.62 0.61 p.u. Td0' 3.05 s Td0'' 0.02598 s
xd' 0.142 0.142 p.u. xq' 0.62 0.61 p.u. Td' 0.35 s Tq0' 0.3 s
xd'' 0.090 0.082 p.u. xq'' 0.090 0.090 p.u. Td'' 0.015 s Tq0'' 0.20667 s
x2 0.095 0.086 p.u. x0 0.028 0.025 p.u. Ta 0.05 s Tq' 0.3 s
x1s n.a. 0.049 p.u. Tq'' 0.03 s
Short circuit ratio saturated: 0.88 Zn 0.476 Ohm

Short circuit data:


Initial short circuit current (3-phase): Ik'' 10204 A
Max. peak current (3-phase): IS 25975 A
Sustained short circuit current: Ik 2510 A Minimum 3 x rated current for
max.10 s
Initial short circuit torque: Mk2 100.9 kNm
Mk3 60.5 kNm
Max. faulty synchron moment: Mf 216.9 kNm
Rated kVA torque: MSN 6.37 kNm
Rated torque MN 5.10 kNm
Shaft torque MSh 5.32 kNm
Load application:
max. load application: 1056 kVA(corresponds to 105,63 % from 1000 kVA) Power: 1000 kVA
for Power factor 0.4 Power factor: 0.8
15% transient voltage drop transient voltage drop: -12.4 %