Technical Specification

Position 710KW 6KV


Description AC Induction Machine
Type AMI 400L2A BANS
Machine Category Process Performance
Quantity of identical units 3

Standards IEC
Potentially Hazardous Atmosphere Ex nA (IEC 60079-15)
Max. Ambient Temperature 40 degC
Max. Altitude 1,075 m a.s.l.

Supply Type Fixed speed


Load TL/Tn @ n/nn; J(WR2) TL = 0 p.u., 0.08 p.u., 0.4 p.u. @ n = 0%, 50%, 100%; J = 6 kgm2
Output 710 kW
Speed 2,971.8 rpm
Supply 6,000 V / 3 ph / 50 Hz
Temperature Rise Class B-class
Duty Type S1

Mounting / Protection / Cooling IM 1001 / IP 55 / IC 611


Insulation Class F, vacuum pressure impregnated
Direction of Rotation Clockwise
Bearings Standard ball bearings
Bearing Insulation Bearings not insulated
Terminal Box Standard air insulated IEC main terminal box
Quality Assurance ISO 9001 and ISO 14001
Color Standard blue Munsell 8B 4.5/3,25

Documentation
- (E)Ex nA standard type certificate
- Auxiliary terminal box drawing
- Connection diagram (main and auxiliary)
- Dimension drawing of machine
- Main terminal box drawing
- Manual for Induction Motors and Generators (delivered with motor)
- Performance data & Current and torque in function of speed
- Test report

Tests and Certificates


- Routine test according to ABB standard procedure

Painting and corrosion protection


- Surface treatment C3 - Standard industrial environment

Accessories
- Additional standard IEC(haz.atmosphere)
- Non-sparking motor Ex nA
- Temperature class T3 design
- Standard vibration acc. to IEC 60034-14 Grade A
- Air-to-air cooler with aluminium tubes
- Bearing insulation for antifriction bearings, none
- Standard air insulated IEC main terminal box
- Cable entry with drilled plate without cable glands
- RTD's (Pt-100) in stator windings, 6 pcs, 3-wire, unshielded, safe and hazardous areas
- RTD's (Pt-100) in antifriction bearings, 2 pcs / bearing, 3-wire, shielded, hazardous areas
- RTD's (Pt-100) in warm and cold cooling air, 3-wire, shielded, hazardous areas
- Low temperature space heater for stator winding, 1 ph, safe and hazardous areas
- Temperature transmitters for Pt-100s in stator winding (3 pcs), hazardous areas
- Temperature transmitters for Pt-100s in bearings (1 pc / bearing), hazardous areas
- Temperature transmitters for Pt-100s in cooling air, hazardous areas
- Surge voltage arresters for Pt-100s in stator winding (3 pcs), hazardous areas
- Location of ATB for instrumentation: Acc. To MDD
- Terminal box for accessories 1, ATB_A1Y_M0202_X0000_N
- Terminal box for space heater, ATB_H1Y_M0201_X0000_N
- Fabricated aluminium rotor
- Documentation in English language
- Only final version of documents in defined language
- Safety instructions and warning labels in English
- Rating and Lubrication plates in English
- 20% additional terminals in ATB for AMA & HXR Price the same as AMI
- 4-20mA vibration transmitter-type SLD 823 C/G SPM company's product, accelerometer that can
output 4-20mA signal directly, datasheet attached in cussamo attachement, barrier is not included

Notes, comments and deviations:


Driven equipment: 010 Pump
Motor type code AMI 400L2A BANS
Motor type Squirrel cage Motor
Type of Ex-protection Ex nA II T3 (IEC 60079-15)
Mounting designation IM 1001
Protected by enclosure IP 55
Method of cooling IC 611
Insulation Class F
Standards IEC
Ambient temperature, max. 40 °C
Altitude, max. 1075 m.a.s.l.
Duty type S1
Temp. rise Class B (RES)
Connection of stator winding Star
Rated output 710 kW
Voltage 6000 V ±5 %
Frequency 50 Hz
Speed 2972 rpm
Current 83 A
Relat. starting current 4.9
Relat. starting torque 0.5
Relat. maximum torque 2.1
No load current 22 A
Rated torque 2281 Nm
Load characteristics Load % Current A Efficiency % Power Factor
100 83 94.9 0.87
75 63 95.0 0.85
50 46 94.4 0.79
Direction of rotation Clockwise
Sound pressure level: (sinus supply, no load) 85 dB(A), tol. + 3 dB(A), 1 m
Weight of rotor 550 kg
Total weight of Motor 3000 kg
Inertia rotor / load Approx. 7 kgm² / 6 kgm²
Bearings Standard ball bearings
Maximum stalling time 13.2 s (warm)
Starting time 2.7 s (U=100%)
4.5 s (U=80 %)
Number of consec. starts 3 / 2 (cold/warm)
Maximum number of starts 1000 / year
All Motor data is subject to tolerances in accordance with IEC.
Efficiency based on typical additional load losses acc. measurements.
Motor type code: AMI 400L2A BANS
Rated output 710 kW Power Factor 0.87
Voltage 6000 V ±5 % Rated torque 2281 Nm
Frequency 50 Hz Relat. starting current 4.9
Speed 2972 rpm Relat. starting torque 0.5
Current 83 A Relat. maximum torque 2.1

Torque and Current as a Function of Speed

5 2.5

4 2

3 1.5

I/In T/Tn

2 1

1 0.5

0 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1

n/ns

I, U=100% I, U=80% Load Torque


T, U=100% T, U=80%