Professional Documents
Culture Documents
Standards IEC
Potentially Hazardous Atmosphere Ex nA (IEC 60079-15)
Max. Ambient Temperature 40 degC
Max. Altitude 1,075 m a.s.l.
Documentation
- (E)Ex nA standard type certificate
- Auxiliary terminal box drawing
- Connection diagram (main and auxiliary)
- Dimension drawing of machine
- Main terminal box drawing
- Manual for Induction Motors and Generators (delivered with motor)
- Performance data & Current and torque in function of speed
- Test report
Accessories
- Additional standard IEC(haz.atmosphere)
- Non-sparking motor Ex nA
- Temperature class T3 design
- Standard vibration acc. to IEC 60034-14 Grade A
- Air-to-air cooler with aluminium tubes
- Bearing insulation for antifriction bearings, none
- Standard air insulated IEC main terminal box
- Cable entry with drilled plate without cable glands
- RTD's (Pt-100) in stator windings, 6 pcs, 3-wire, unshielded, safe and hazardous areas
- RTD's (Pt-100) in antifriction bearings, 2 pcs / bearing, 3-wire, shielded, hazardous areas
- RTD's (Pt-100) in warm and cold cooling air, 3-wire, shielded, hazardous areas
- Low temperature space heater for stator winding, 1 ph, safe and hazardous areas
- Temperature transmitters for Pt-100s in stator winding (3 pcs), hazardous areas
- Temperature transmitters for Pt-100s in bearings (1 pc / bearing), hazardous areas
- Temperature transmitters for Pt-100s in cooling air, hazardous areas
- Surge voltage arresters for Pt-100s in stator winding (3 pcs), hazardous areas
- Location of ATB for instrumentation: Acc. To MDD
- Terminal box for accessories 1, ATB_A1Y_M0202_X0000_N
- Terminal box for space heater, ATB_H1Y_M0201_X0000_N
- Fabricated aluminium rotor
- Documentation in English language
- Only final version of documents in defined language
- Safety instructions and warning labels in English
- Rating and Lubrication plates in English
- 20% additional terminals in ATB for AMA & HXR Price the same as AMI
- 4-20mA vibration transmitter-type SLD 823 C/G SPM company's product, accelerometer that can
output 4-20mA signal directly, datasheet attached in cussamo attachement, barrier is not included
5 2.5
4 2
3 1.5
I/In T/Tn
2 1
1 0.5
0 0
0 0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8 0.9 1
n/ns