Professional Documents
Culture Documents
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
Spec Information
Generator Specification
Generator Efficiency
Frame: 3045 Type: SR5 No. of Bearings: 2
Per Unit Load kW Efficiency %
Winding Type: FORM WOUND Flywheel: 21.0
0.25 775.0 86.3
Connection: SERIES STAR Housing: 00
0.5 1550.0 91.8
Phases: 3 No. of Leads: 6
0.75 2325.0 94.0
Poles: 4 Wires per Lead: 2
1.0 3100.0 94.8
Sync Speed: 1800 Generator Pitch: 0.6667
Short Circuit Ratio: 0.55 Stator Resistance = 0.0282 Ohms Field Resistance = 1.1229 Ohms
Voltage Regulation Generator Excitation
Voltage level adjustment: +/- 5.0% No Load Full Load, (rated) pf
Voltage regulation, steady state: +/- 0.5% Series Parallel
Voltage regulation with 3% speed change: +/- 0.5% Excitation voltage: 12.29 Volts 50.31 Volts Volts
Waveform deviation line - line, no load: less than 3.0% Excitation current 1.28 Amps 4.31 Amps Amps
Telephone influence factor: less than 100
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 1/7
11/16/23, 8:52 AM Caterpillar Generator Data
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 2/7
11/16/23, 8:52 AM Caterpillar Generator Data
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
Percent
SKVA
Volt Dip
558 2.5
1,145 5.0
1,764 7.5
2,417 10.0
3,108 12.5
3,839 15.0
4,614 17.5
5,438 20.0
6,316 22.5
7,251 25.0
8,251 27.5
9,323 30.0
10,474 32.5
11,713 35.0
13,052 37.5
14,502 40.0
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 3/7
11/16/23, 8:52 AM Caterpillar Generator Data
Current Decrement Data
E Time
AMP
Cycle
0.0 3,824
1.0 3,438
2.0 3,158
3.0 2,952
4.0 2,795
5.0 2,671
7.5 2,444
10.0 2,275
12.5 2,133
15.0 2,006
20.0 1,781
25.0 1,587
30.0 1,417
35.0 1,269
40.0 1,207
45.0 1,228
Instantaneous 3 Phase Fault Current: 3824 Amps Instantaneous Line - Line Fault Current: 2864 Amps
Instantaneous Line - Neutral Fault Current: 4610 Amps
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
Field Line -
Current Line Volt
0.0 0
18.3 2,496
21.6 2,912
25.3 3,328
29.5 3,744
34.7 4,160
41.6 4,576
51.6 4,992
67.1 5,408
92.3 5,824
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 4/7
11/16/23, 8:52 AM Caterpillar Generator Data
Short Circuit Curve
Field Armature
Current Current
0.0 0
41.7 323
48.6 376
55.6 430
62.5 484
69.5 538
76.4 592
83.3 645
90.3 699
97.2 753
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
Field Line -
Current Line Volt
69.5 0
90.8 2,080
94.6 2,496
99.0 2,912
104.3 3,328
111.6 3,744
122.0 4,160
138.4 4,576
165.1 4,992
210.3 5,408
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 5/7
11/16/23, 8:52 AM Caterpillar Generator Data
Air Gap Curve
Field Line -
Current Line Volt
0.0 0
17.8 2,496
20.7 2,912
23.7 3,328
26.7 3,744
29.6 4,160
32.6 4,576
35.5 4,992
38.5 5,408
41.5 5,824
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 6/7
11/16/23, 8:52 AM Caterpillar Generator Data
Selected Model
Engine: C175-16 Generator Frame: 3045 Genset Rating (kW): 3100.0 Line Voltage: 4160
Fuel: Diesel Generator Arrangement: 2628276 Genset Rating (kVA): 3875.0 Phase Voltage: 2402
Frequency: 60 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 537.8
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 41205 /43207 /43227 /8455
General Information
DM7827 Caterpillar SR5-HV Generators (50 Hz, 60 Hz)
Data for 3000 frame Caterpillar SR5-HV generators built by Leroy Somer
USA.
GENERATOR EFFICIENCY
Generator efficiency is the percentage of engine flywheel (or other
prime mover) power that is converted into electrical output. The
generator efficiency shown is calculated by the summation of all
losses method, and is determined in accordance with the IEC Standard
60034. The efficiency considers only the generator. There is no
consideration of engine or parasitic losses here.
Refer to DM7830 for high voltage protective setting values and limits.
https://tmiwebclassic.cat.com/tmi/servlet/TMIDirector?Action=openwindow&log=genXmlData&type=RNGenDataRefNum&refno=&selection=&unitType… 7/7