You are on page 1of 8

Caterpillar Generator Data Page 1 of 8

GENERATOR DETAIL MARCH 14, 2013


For Help Desk Phone Numbers Click here

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Spec Information
Generator Specification
Generator Efficiency
Frame: 2770 Type: SR4BHV No. of Bearings: 2
Per Unit Load kW Efficiency %
Winding Type: FORM WOUND Flywheel: 21.0
0.25 500.0 91.6
Connection: SERIES STAR Housing: 00
0.5 1000.0 95.0
Phases: 3 No. of Leads: 6
0.75 1500.0 95.8
Poles: 4 Wires per Lead: 1
1.0 2000.0 96.0
Sync Speed: 1500 Generator Pitch: 0.667

Reactances Per Unit Ohms


SUBTRANSIENT - DIRECT AXIS X''d 0.1867 9.0385
SUBTRANSIENT - QUADRATURE AXIS X''q 0.2327 11.2618
TRANSIENT - SATURATED X'd 0.2457 11.8902
SYNCHRONOUS - DIRECT AXIS Xd 2.5455 123.2034
SYNCHRONOUS - QUADRATURE AXIS Xq 1.3152 63.6559
NEGATIVE SEQUENCE X2 0.2097 10.1501
ZERO SEQUENCE X0 0.0270 1.3050

Time Constants Seconds


OPEN CIRCUIT TRANSIENT - DIRECT AXIS T'd0 4.7990
SHORT CIRCUIT TRANSIENT - DIRECT AXIS T'd 0.6390
OPEN CIRCUIT SUBSTRANSIENT - DIRECT AXIS T''d0 0.0480
SHORT CIRCUIT SUBSTRANSIENT - DIRECT AXIS T''d 0.0370
OPEN CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T''q0 0.0240
SHORT CIRCUIT SUBSTRANSIENT - QUADRATURE AXIS T''q 0.0040
EXCITER TIME CONSTANT Te 0.2220
ARMATURE SHORT CIRCUIT Ta 0.0650

Short Circuit Ratio: 0.66 Stator Resistance = 0.5508 Ohms Field Resistance = 1.1819 Ohms
Voltage Regulation Generator Excitation
Voltage level adustment: +/- 5.0% No Load Full Load, (rated) pf
Voltage regulation, steady state: +/- 0.5% Series Parallel
Voltage regulation with 3% speed change: +/- 0.5% Excitation voltage: 14.01 Volts 50.28 Volts Volts
Waveform deviation line - line, no load: less than 2.0% Excitation current 3.8 Amps 11.22 Amps Amps
Telephone influence factor: less than 50
Caterpillar Generator Data Page 2 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Generator Mechanical Information


Center of Gravity
Dimension X -1189.0 mm -46.8 IN.
Dimension Y 0.0 mm 0.0 IN.
Dimension Z 0.0 mm 0.0 IN.
z "X" is measured from driven end of generator and parallel to rotor. Towards engine fan
is positive. See General Information for details
z "Y" is measured vertically from rotor center line. Up is positive.
z "Z" is measured to left and right of rotor center line. To the right is positive.
Generator WT = 6486 kg * Rotor WT = 2139 kg * Stator WT = 4347 kg
14,299 LB 4,716 LB 9,583 LB

Rotor Balance = 0.0508 mm deflection PTP


Overspeed Capacity = 125% of synchronous speed

Generator Torsional Data

J1 = Coupling J2 = Rotor J3 = Exciter


and Fan TOTAL J = J1 + J2 + J3 End
K1 = Shaft Stiffness between K2 = Shaft Stiffness between
J1 + J2 (Diameter 1) J2 + J3 (Diameter 2)
J1 K1 Min Shaft Dia 1 J2 K2 Min Shaft Dia 2 J3
817.0 LB IN. s2 227.0 MLB IN./rad 5.5 IN. 88.6 LB IN. s2 46.8 MLB IN./rad 5.0 IN. 2.5 LB IN. s2
92.313 N m s2 25.651 MN m/rad 140.0 mm 10.011 N m s2 5.2884 MN m/rad 127.0 mm 0.277 N m s2
Total J
908.1 LB IN. s2
102.601 N m s2
Caterpillar Generator Data Page 3 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Generator Cooling Requirements -


Temperature - Insulation Data
Cooling Requirements: Temperature Data: (Ambient 40 0C)
Heat Dissipated: 83.3 kW Stator Rise: 130.0 0C
Air Flow: 153.0 m3/min Rotor Rise: 130.0 0C
Insulation Class: H
Insulation Reg. as shipped: 100.0 MΩ minimum at 40 0C

Thermal Limits of Generator


Frequency: 50 Hz
Line to Line Voltage: 11000 Volts
B BR 80/40 1946.0 kVA
F BR -105/40 2281.0 kVA
H BR - 125/40 2500.0 kVA
F PR - 130/40 2500.0 kVA
Caterpillar Generator Data Page 4 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Starting Capability & Current Decrement


Motor Starting Capability (0.4 pf)
Percent
SKVA
Volt Dip
251 2.5
515 5.0
794 7.5
1,088 10.0
1,399 12.5
1,728 15.0
2,077 17.5
2,448 20.0
2,843 22.5
3,264 25.0
3,714 27.5
4,196 30.0
4,714 32.5
5,272 35.0
5,875 37.5
6,527 40.0

Current Decrement Data


E Time
AMP
Cycle
0.0 702
1.0 618
2.0 564
3.0 527
4.0 500
5.0 480
7.5 442
10.0 413
12.5 387
15.0 364
20.0 323
25.0 287
30.0 257
35.0 234
40.0 220
45.0 214

Instantaneous 3 Phase Fault Current: 702 Amps Instantaneous Line - Line Fault Current: 573 Amps
Instantaneous Line - Neutral Fault Current: 929 Amps
Caterpillar Generator Data Page 5 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Generator Output Characteristic Curves


Open Circuit Curve

Field Line -
Current Line Volt
0.0 0
15.5 6,600
19.0 7,700
23.0 8,800
27.8 9,900
33.7 11,000
41.1 12,100
50.7 13,200
63.2 14,300
79.9 15,400

Short Circuit Curve

Field Armature
Current Current
0.0 0
33.2 79
38.7 92
44.2 105
49.7 118
55.3 131
60.8 144
66.3 157
71.8 171
77.4 184
Caterpillar Generator Data Page 6 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Generator Output Characteristic Curves


Zero Power Factor Curve

Field Line -
Current Line Volt
55.3 0
78.1 5,500
83.2 6,600
89.4 7,700
97.3 8,800
107.5 9,900
120.9 11,000
138.8 12,100
162.8 13,200
195.4 14,300

Air Gap Curve

Field Line -
Current Line Volt
0.0 0
11.8 6,600
13.8 7,700
15.7 8,800
17.7 9,900
19.7 11,000
21.6 12,100
23.6 13,200
25.6 14,300
27.5 15,400
Caterpillar Generator Data Page 7 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

Reactive Capability Curve


Click to view Chart
Caterpillar Generator Data Page 8 of 8

Selected Model
Engine: 3516 Generator Frame: 2770 Genset Rating (kW): 2000.0 Line Voltage: 11000
Fuel: Diesel Generator Arrangement: 2524246 Genset Rating (kVA): 2500.0 Phase Voltage: 6351
Frequency: 50 Excitation Type: Permanent Magnet Pwr. Factor: 0.8 Rated Current: 131.2
Duty: STANDBY Connection: SERIES STAR Application: EPG Status: Current
Version: 40953 /40401 /38315 /4050

General Information
DM7826 Caterpillar SR4B-HV Generators (50 Hz, 60 Hz)
Data for 2600 and 2700 frames Caterpillar SR4B-HV generators built by
Leroy Somer – USA.

Refer to DM7821 for explanation of all generator data in Technical


Marketing Information (TMI) except generator efficiency for which the
explanation is given below.

GENERATOR EFFICIENCY
Generator efficiency is the percentage of engine flywheel (or other
prime mover) power that is converted into electrical output. The
generator efficiency shown is calculated by the summation of all
losses method, and is determined in accordance with the IEC Standard
60034. The efficiency considers only the generator. There is no
consideration of engine or parasitic losses here.