Professional Documents
Culture Documents
Location
Company: GTSM Country: MY
Station: LOTTE CHEMICAL TITAN Feeder: 22BF10
Phase: N-CT IEC-ID: 61869-2
CT Nameplate
Manufacturer: YOUNGHWA INDUSTRIAL ELETRICAL CO., LTD Tap: 1S1-1S2
Type: Core Number: 1S1-1S2
Serial Number: 403249 Optional 1:
Equipment
Test Device: CT-Analyzer Software Version: 5.00 (449) 2018-08-07
Serial Number: JC278D Hardware Version: 01/00/09/05/00/11
Test Settings:
Resistance
Secondary Winding:
R-meas: 806.4mΩ T-meas: 25.0°C
R-ref: 961.8mΩ T-ref: 75.0°C
Ratio:
NOTE: Measurements with '!' have reduced accuracy. Accuracy only guaranteed on non-gapped cores.
Excitation:
Knee Points:
Standard V I
IEC 61869-2 29.43V 16.12mA
Results:
Kr: 96% Lm: 6.5H
Ls: 360.7μH
Results with nominal burden: Results with operating burden:
Burden: 0.0 VA cos φ: 1.0 Burden: 0.0 VA cos φ: 1.0
FS: >20.07 FS: >20.07
FSi: 20.01 FSi: 20.01
Ts: 6.757s Ts: 6.757s
ε-i: >0.000% (@ FS = -2.0) ε-i: >0.000% (@ FS = -2.0)
Excitation Table: