DIFFERENTIAL PICKUP

CT Ratio 600 1 2000

Injection 0 95.00%
Pickup CT Error System 92.00%
Idiff> Set 0.8 Local Remote Error
3% 3% 2%

PU = Set + Permissible local CT error XI/IN1 + Permissible Remote CT error XI/IN1


PU 0.8421 0.8696
(in Test Mode) (with Local and Remote)

Injection 1.7 88.00%


Biasing - relay to relay CT Error System
Idiff> Set 0.3 Local Remote Error
3% 10% 2%

PU = Set + Permissible local CT error XI/IN1 + Permissible Remote CT error XI/IN1


PU 2.4659
missible Remote CT error XI/IN1 + System Error

missible Remote CT error XI/IN1 + System Error


DIGSI Address Side A Relay Side B Relay
205 1600 A 1600 A
206 1 A 1 A
251 1.5 1.5
253 3 % 3 %
254 10 % 10 %
1104 1000 A 1000 A
1210 0.3 A 0.3 A
1213 0.3 A 0.3 A

Actual Current flow in Sec 2 A 2 A

Actual Current flow in Pri 3200 3200

Display values

Restraint 115.2 % 115.2 %

Differential 0 % 0 %
DISTANCE CALCULATION
(Fill the yellow cells only to get results)

km 13.7
Z0=(R+JX) 0.41 +j 0.0600 Ohms/km Primary 0.15 Angle 8.33
Z1=(R+JX) 0.0795 +j 0.1020 Ohms/km Primary 0.91 Line Angle 52.07

Z0 5.617 +j 0.822 Total Ohms Primary


Z1 1.089 +j 1.397 Total Ohms Primary RE/RL 1.39
XE/XL -0.14
Function 1110 X' (secondary) 0.20
CTR 600 / 1
VTR 33000 / 110 Zones Length Short line Long line R PH-PH
CTR/VTR 2.00 N1 Z1 80% 1.743
Z1B 100% 50% 3.267
Max Load Z2 100% 50% 3.267
394 A
Current Z3 100% 100% 4.357
R load Sec. 39.1689662 Z4 R 20% 0.436
Angle load 31 Z5 200% 4.357
(for Siemens R value may be taken either 2 or 3 times of X)
For Siemens For Siemens
2 times of X 3 times of X
X R PH-E R R
2.236 8.987 4.472 6.70752
4.192 16.851 8.384 12.5766
4.192 16.851 8.384 12.5766
5.590 22.468 11.179 16.7688
0.559 2.247 1.118 1.67688
5.590 22.468 11.179 16.7688
FAULT LOCATOR
(Fill the yellow cells only to get results)

TOTAL LINE LENGTH 8.3 KM


REACTANCE PER Km 0.1159 OHM
TOTAL REACTANCE at 90deg 0.962 OHM
Line Angle 85 deg
TOTAL REACTANCE at line angle 0.966 OHM
For Angle at 90 deg
Applied Calculated distance
Fault type
Reactance (Km) %
R–N 0.096 0.83 10
Y–N 0.577 4.98 60
B–N 0.962 8.3 100
R–Y 0.192 1.66 20
Y–B 0.481 4.15 50
B–R 0.770 6.64 80
R-Y-B 1.443 12.45 150

At Line Angle deg


Applied
Calculated distance
Fault type Reactance
(Km) %
R–N 0.097 0.83 10
Y–N 0.579 4.98 60
B–N 0.966 8.3 100
R–Y 0.193 1.66 20
Y–B 0.483 4.15 50
B–R 0.773 6.64 80
R-Y-B 1.448 12.45 150
THIS FILE FOR VECTOR GROUP YYN0 ONLY
Data
Primary KV 132 Current Primary 87.48 A
Secondary KV 33 current Secondary 349.92 A
MVA 20
Vector Group 0
Vector Group = 0
CT Ratio
Primary 800 1
Secondary 2400 1

Idiff> Set 0.2

HV Side
Ph-E Idiff Set x Primary Current x 1.5
PU =
Primary CT
0.038 1.148
PU - Ph-E
0.026 0.804

LV Side
Ph-E Idiff Set x Secondary Current x 1.5 Ph-Ph
PU =
Primary CT
0.050 1.531
PU - Ph-E
0.035 1.072
Idiff>> Set 7

Hiset Pu
Idiff Set x Primary Current Ph-E PU = Idiff Set x Primary Current x 1.5
PU =
Primary CT Primary CT
0.019 0.765
PU - Ph-Ph
0.013 0.536

Idiff Set x Secondary Current


PU =
Primary CT
0.025 1.021
PU - Ph-Ph
0.018 0.714
Primary Current x 1.5
Data
Primary KV 220 Current Primary 367.42
Secondary KV 33 current Secondary 2449.44
MVA 140 Star Point of Side1 Isolated
Vector Group -150 Star Point of Side2 Earthed

CT Ratio
Primary 300 1
Secondary 2500 1

30661-Operat. Meas.Current IL1 side1(A) 24


30662-Operat. Meas.Current IL2 side1 (A) 0
30663-Operat. Meas.Current IL3 side1 (A) 0

30667-Operat. Meas.Current IL1 side2(A) 160


30668-Operat. Meas.Current IL2 side2 (A) 0
30669-Operat. Meas.Current IL3 side2 (A) 0
Matrix-A
-0.57735 0 0.57735
0.57735 -0.57735 0
0 0.57735 -0.57735

IDL1 #VALUE!
IDL2 #VALUE!
IDL3 #VALUE!
###
###
###
###
###
###
###
###
###
###
###
###
IF STAR POINT is Earthed
###
0 DEG
###

###
(-30 or 1 clock)
###

###
(-60 or 2 clock)
###

###
(-90 or 3 clock)
###

###
Matrix-B (-120 or 4 clock
0 -0.57735 0.57735 ###

0.333333 0.333333 -0.666667 ###


(-150 or 5 clock)
###

###
(-180 or 6 clock)
###

###
(30 or 11 clock)
###

###
(60 or 10 clock
METERING
(Fill the yellow cells only to get results)
Primary Details
Voltage KV 380 PE 219 kV
Current A 2000
Sec Details
Voltage V 110
Current A 1

Ang DEG 0 -30 -90 180


0 -0.500 -1.000 0.000

P (active power) MW 1316.32 1139.97 0.00 -1316.32

Q (reactive power) MVAR 0.00 658.16 1316.32 0.00

Power Factor PF 1.00 0.87 0.00 -1.00


45 135 225 315
0.707 0.707 -0.707 -0.707

930.78 -930.78 -930.78 930.78

-930.78 -930.78 930.78 930.78

0.71 -0.71 -0.71 0.71


THERMAL OVER LOAD TIMING CHECK
(Fill the yellow cells only to get results)

4202 K Factor 0.68 A


4203 Time Constant 50.1 m
4204 Thermal alarm stage 90 %
4205 Current Overload Alarm 0.65 A
Actual Flow of Sec current 3 A
4207A 49 Kt-Factor when motor stops 1
4208A 49 Emergency Time 100 Sec
4209A Current Pickup value of motro starting 5 I/InS

0.680
Thermal Trip 158.550 Sec
Near to Thermal Trip 142.695 Sec
(Fill the yellow cells only to get results) IEC CURVE K ALPHA
NI 0.14 0.02
VI 13.5 1
Current setting : 0.2 Is EI 80 2
LTI 120 1
Time Multiplier : 0.25 Tms

Curve : IEC CURVE

Normal Inv. Very Inv. Extremly Inv. Long Time Inv.


User defined Value (2 Times) 2 TIMES I/Is 2 2.51 3.38 6.67 30.00
User defined Value (5 Times) 5 TIMES I/Is 5 1.07 0.84 0.83 7.50
User defined Value (10 Times) 10 TIMES I/Is 10 0.74 0.38 0.20 3.33

User defined Value (Times) 20 I/Is 20 0.57 0.18 0.05 1.58

User defined Fault Current 3 A 15 0.63 0.24 0.09 2.14

PICKUP CURRENT ACCURACY

0.22
0.209

TIMING ACCURACY
GPS Antenna
110
50
310
16 IC 99.0264

132
50
10
10 2.3958
0.019965 0.049913 0.369913