1. Specifications
Sensing Input External Volts Adjustment
Terminal 0 to 110V = 95 ~ 135V ±10% @ 1KΩ
Terminal 0 to 220V = 180 ~ 250V
Terminal 0 to 380V = 360 ~ 515V Power Input X1、
、X2 Z1、 、Z2
Frequency 50/60 Hz, Jumper selectable 45 ~ 600HZ
150mm 55.3mm
130mm
22mm
X 1 Z1 X 2 Z2 F+ F- 0 V 1 10 22 0 38 0/480
A1 A2 VR VR S1 S2 S3
135mm
117mm
1 -D iffe re nt
2 -In teg ra l
3 -O N ,60H z
UFRO STAB LAM D R OO P VO LT T R IM
UF ON
Mechanical Specifications
AV R can be moun ted directly on the engine, genset, switchgear or control pan el that conforms to the
moun ting specification.
All voltage readings are to be taken with an average-read ing voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AV R.
2 EA 08 A
2. WIRING
3. ADJUSTMENTS
1. Sensing Input terminals (single phase)
0 to 110V TRIM : Analog Voltage Input Adjustment A1, A2
0 to 220V VOLT : Voltage Adjustment.
0 to 380/480V
DROOP : Droop Adjustment.
2. F+ F- : Field Output Terminals
DIP : To set the frequency related voltage dip
3. X1-X2, Z1-Z2 power input terminals.
STAB : Stability Adjustment.
We can use all types of power input
arrangement. Harmonic, Auxiliary, UFRO : UFRO Knee Point set.
PMG (single/3 phase) & shunt,
from 45 to 600Hz. See Drawings DIP SWITCH : Function Selection Switch.
4. S1, S2 & S3 Terminals. Current Compensation 1. Voltage Compensation : ON => for over 550KW
inputs. S1 to S2 use 5A CTs - S2 to S3 use 1A Cts. 2. Reaction Time Range: ON = > for 90 ~ 550KW
5 . VR - VR Terminals used to external voltage 3. Rated Frequency 50/60Hz Selection :
Adjustmnet using a 1K Ohm POT. Keep shorted
.
if not used. ON = 60Hz
X1
X2
Z1
X2
X1
Z2
E+
E-
0V
110V
220V
380V
A1
A2
VR
VR
S1
S2
S3
EXT.VR 1k Ohm
X1
X2
Z1
X2
X1
Z2
E+
E-
0V
110V
220V
380V
A1
A2
VR
VR
S1
S2
S3
Harmoni wires
AUX . wires
X2
X1
Z1
X2
X1
Z2
E+
E-
0V
110V
220V
380V
A1
A2
VR
VR
S1
S2
E X T . V R 1k O hm
4 EA08A
480V 480V
Not Used