Generator Automatic Voltage Regulator

Operation Manual

Self ExcitedAutomatic Voltage Regulator


For use in Brushless Full Harmonic or Harmonic andAuxiliaryWinding
The EA08A is a Special Generator Voltage Regulator that uses in its power stage UltraFast CoPack
IGBTs Power Devises. This design gives us the flexibility for using PMGs with varied frequencies outputs
from diverse alternator manufactures. Terminals are also included to power the AVR as a shunt regulator
or from harmonic and auxiliary windings. The IGBT makes it flexible enough to easily substituting haft
and full wave AVRs. In addition, A1 and A2 terminals for use in remote bias and other terminals adding
the ability to use 1 and 5 Amp CTs.

1. Specifications
Sensing Input External Volts Adjustment
Terminal 0 to 110V = 95 ~ 135V ±10% @ 1KΩ
Terminal 0 to 220V = 180 ~ 250V
Terminal 0 to 380V = 360 ~ 515V Power Input X1、
、X2 Z1、 、Z2
Frequency 50/60 Hz, Jumper selectable 45 ~ 600HZ

Harmonic Voltage Thermal Drift


Voltage 25 ~ 300VAC 0.05% per ? change in AVR ambient

Voltage Regulation Analog Voltage Input A1 & A2


< ±0.5% (with 4% engine governing) 10% generator voltage per 1VDC

Voltage Build-up Current Compensation


Harmonic Residual Volt. > 5 VAC N : 5 A or N : 1A Input
Maximum 4% @ P.F. = 0.8
Output Voltage
Maximum 150VDC @ 220VAC Dimensions
150mm L * 135mm W * 55.3mm H
Output Current
Maximum Continuous 8 A Weight
Intermittent 12 A for 10 sec 600g ± 2%

150mm 55.3mm
130mm
22mm

X 1 Z1 X 2 Z2 F+ F- 0 V 1 10 22 0 38 0/480
A1 A2 VR VR S1 S2 S3
135mm
117mm

1 -D iffe re nt
2 -In teg ra l
3 -O N ,60H z
UFRO STAB LAM D R OO P VO LT T R IM
UF ON

Figure 1 Outline Drawing

Mechanical Specifications
AV R can be moun ted directly on the engine, genset, switchgear or control pan el that conforms to the
moun ting specification.
All voltage readings are to be taken with an average-read ing voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AV R.

2 EA 08 A
2. WIRING
3. ADJUSTMENTS
1. Sensing Input terminals (single phase)
0 to 110V TRIM : Analog Voltage Input Adjustment A1, A2
0 to 220V VOLT : Voltage Adjustment.
0 to 380/480V
DROOP : Droop Adjustment.
2. F+ F- : Field Output Terminals
DIP : To set the frequency related voltage dip
3. X1-X2, Z1-Z2 power input terminals.
STAB : Stability Adjustment.
We can use all types of power input
arrangement. Harmonic, Auxiliary, UFRO : UFRO Knee Point set.
PMG (single/3 phase) & shunt,
from 45 to 600Hz. See Drawings DIP SWITCH : Function Selection Switch.
4. S1, S2 & S3 Terminals. Current Compensation 1. Voltage Compensation : ON => for over 550KW
inputs. S1 to S2 use 5A CTs - S2 to S3 use 1A Cts. 2. Reaction Time Range: ON = > for 90 ~ 550KW
5 . VR - VR Terminals used to external voltage 3. Rated Frequency 50/60Hz Selection :
Adjustmnet using a 1K Ohm POT. Keep shorted
.
if not used. ON = 60Hz

6. A1 & A2 Terminals accept remote DC voltage OFF = 50Hz


to adjust generator output voltage. The TRIM
controls controls its sensibility

PMG Exciter field


Armature
C.T
Stator wires N:1A
R
S
T
200VAC max 50~500HZ

X1
X2
Z1
X2
X1
Z2
E+
E-
0V
110V
220V
380V
A1
A2
VR
VR
S1
S2
S3

EXT.VR 1k Ohm

Figure 2 Single Phase / 3 Phase PMG Wiring


EA08A 3
E xciter field
Armature
C .T
S tator wires N:5 Aor1A
R
S
T

(Harmoni) AUX . wires

X1
X2
Z1
X2
X1
Z2
E+
E-
0V
110V
220V
380V
A1
A2
VR
VR
S1
S2
S3

EX T .V R 1k Ohm N:5A N:1A

F igure 3 3 P has e (Auxiliary W inding F ull Harmonic S elf E xc ited) W iring


E xc iter field
Armature
C .T
S tator wires N:1A
R
S
T

Harmoni wires

AUX . wires

X2
X1
Z1
X2
X1
Z2
E+
E-
0V
110V
220V
380V
A1
A2
VR
VR
S1
S2

E X T . V R 1k O hm

F igure 4 Auxiliary W inding & H armonic W iring

P leas e us e original s pare fus e (10A).


P roduct P erformance, s pecification and appea rance are s ubject to change (Improvement) without prior
notification.

4 EA08A
480V 480V
Not Used

Replace the Grameyer GRT7-TH4 With the McPherson EA-08A