You are on page 1of 8

INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER

WT-3A

WT-3A
Generator Automatic Voltage Regulator
Operation Manual
1. INTRODUCTION
The WT-3A Voltage Regulator is base on Pulse-Width Modulation (PWM) to controls the DC exciter field
power of conventional, 50 or 60 Hz brushless generators. The AVR circuitry includes under-speed and sensing loss
protection features. Excitation power is derived directly from the generator terminals or the others(PMG, Harmonic, Full
Harmonic, Auxiliary Winding and so on).

2. ENVIRONMENTAL
2.1. Operating temperature:–20 to 60℃(–4 to 140℉)
2.2. Storage temperature:–20 to 85℃(–4 to 185℉)
2.3. ALTITUDE: Less than 1000 meter
2.4. RELATIVE HUMIDITY: <90%

3. TECHNOLOGY SPECIFICATION
Sensing Input
Paralleling
Transformer isolated, with respect to neutral, 400
Vac or 220 Vac line-to-line nominal, 50/60Hz Internal burden and adjustment for 0 to 10%
Terminal V0 - V220 for 220 Vac droop at 1 Aac, 0 PF, (from external CT)
Terminal V0 – V380 for 400 Vac Votage Buildup
Power Input 6Vac, 30 Hz
Voltage: 180to 250 Vac External Volts Adjustment
Frequency: 40 to 500 Hz At least ±10% with 1k ohm 2 watt trimmer
Burden: 1 kVA.
Thermal Drift
Voltage Adjust Range
0.05% per ℃ change in AVR ambient
180 - 250 Vac, 350 - 480 Vac
Field Resistance Analog Voltage Input
0 to 10% generator voltage per 1Vdc turn the TRIM
9Ωminimum
trimmer
Voltage Regulation Current Compensation
< ±0.5% (with 4% engine governing) In : 1A Input
Output Voltage Maximum 4% @ P.F. = 0.8
Maximum 90 Vdc @ 220 Vac Dimensions
Output Current 165 mm L ×135 mm W × 45 mm H
Maximum continuous: 8 A @ 220 Vac Weight
10 second forcing: 15 A @ 220 Vac
700±10g

4. MECHANICAL SPCIFICATION
DRAWING

1
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A

Figure 1 Outline Drawing

AVR can be mounted directly on the engine, genset, switchgear or control panel that conforms to the
mounting specification.
All voltage readings are to be taken with an average-reading voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AVR.

5. WIRING
connect a 1k ohm 2 watt potentiometer to terminals
1. V0 - V220 – V380: Sensing Input terminals.
VR1 and VR1 as shown. If not, connect a jumper
When the generator output voltage for 220 Vac, between terminals VR1 and VR1.
connect the sensing input to the terminals V0 and
V220. When the generator output voltage for 400 Vac, 6. A1 - A2: Analog Voltage Input.
connect the sensing input to the terminals V0 – V380. The terminals can accept ± 5Vdc.
The sensing should be connected "line-to-line" from All wiring please refer to Figure 2 Figure3 and
generator output. Figure 4.
2. E+ . E-: Excitation Output. 7. DIP SWITCH: Function Selection Switch.
Connect the brushless exciter field to terminals E+ SW1 Reaction Time Range: ON: for under 550 kW
and E-. Be sure to observe polarity. SW2 Voltage Compensation : ON: for over 550 kW
3. X1 - W1 - X2 - W2: Power Input terminals. SW3 Rated Frequency 50/60Hz Selection :
When using single phase power input, please ON: 60 Hz, OFF: 50 Hz
connect to terminals X1 and X2 or W1 and W2. For
3-phase power input, please connect to X1. X2. W2
Voltage Build Up
terminals. The power input can be PMG, Harmonic,
Full Harmonic and Auxiliary Winding and so on. When first starting of voltage regulator and
generator, the residual voltage of generator might
4. S1 - S2: Current compensation input. be not enough for the voltage building up, and the
Current Transformer(CT) secondary current = 1A. P1、P4 terminal residual voltage is lower than 6V. So
5. VR1 - VR2: External Voltage Adjustment. it should be perform the following steps:
If an external voltage adjust control is being used, 1. Stop the engine, and use the 24Vdc connected

2
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A
in series to appropriate power resistance (24
ohms/24W), connected to the F+, F- terminals
for the magnetizing of generator;
2. After 2 seconds start the voltage building-up;
3. If it doesn’t work after step 1 & 2, check the DC
power
6. ADJUSTMENTS
All trimmer build in back of the AVR board, except frequency is between 55 and 57 Hz (for 60 Hz
the TRIM trimmer. The trimmers Include DROOP applications). For 50 Hz applications, the frequency
DIP UFRO STAB and VOLT. roll-off is factory preset to between 45 and 47.5 Hz.
Please refer to Figure 5 To reset the frequency roll-off, proceed as follows:.
1. VOLT: Voltage Adjustment. a. Adjust the prime mover RPM to the desired
frequency compensation (corner frequency
The generator output voltage can be altered by
adjustment of the VOLT trimmer on the AVR board, roll-off) point.
or bythe external trimmer (1k ohm 1W) if fitted. b. Adjust the back panel UFRO trimmer until the
a. The terminals RV1 and RV2 must be linked if no output voltage starts to drop off.
hand trimmer. c. Bring the prime mover up to rated speed. The
b. Before start the generator, please turn the VOLT output voltage should return to normal
trimmer on the AVR board fully clockwise Turn the 4. DROOP: Droop Adjustment.
external trimmer to midway position. Generator intended for parallel are fitted with a
c. Turn the stability trimmer on the AVR board to quadrature droop CT with provides a power factor
midway position. dependent signal for the AVR. The CT is connected
d. Connect a voltmeter to generator output voltage to S1 and S2 on the AVR. The Droop adjustment is
terminals. normally present in the works to give 5% voltage
e. Start generator set and run on no load at nominal droop at full load zero power factor. Anticlockwise
frequency 50 ~ 53Hz or 60~63Hz. increases the amount of CT signal injected into the
f. If the red Led is illuminated, refer to the under AVR and increases the droop with lagging power
frequency roll off adjustment. factor. With the control fully clockwise there is no
droop.
g. Carefully turn volt trimmer anticlockwise until
rated voltage is reached. 5. DIP: To set the frequency related voltage DIP.
2. STAB: Stability Adjustment. When the generator frequency under the knee, the
voltage of the generator drop 0 - 5 Vac per 1 Hz turn
If a replacement AVR has been fitted or re-setting of the DIP trimmer. Turn the DIP trimmer fully
the stability control is required, turn the stability clockwise voltege drop minimum, anticlockwise
trimmer slowly unticlockwise until the output voltage voltege drop maximum.
is steady, on or off load.
6. TRIM: Analog Voltage Input Adjustment.
3. UFRO: Frequency Roll-Off Adjustment.
Turn the TRIM trimmer fully clockwise has no effect,
The WT-3A under frequency adjust is factory preset anticlockwise it has maximum effect.
to cause an average 1 volt drop in the generator's
line input voltage to the regulator when the

OPERATIONAL TEST
To operationally test any WT-3A, refer to Figure 5 and perform the following steps.
a. Connect the voltage regulator as shown in Figure 6 and apply 230 Vac 50Hz.
b. Adjust the rear panel VOLT trimmer fully clockwise (CCW).
RESULT: Observe that the lamp does not light.
c. Adjust the rear panel VOLT trimmer fully counter-clockwise (CW).
RESULT: Observe that the lamp is now lit.
d. Adjust the rear panel VOLT trimmer until the lamp just goes out.
Regulator operation is satisfactory if the above results are obtained. Stability, however, must be tested with
the generator and regulator operating.

3
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A

Figure 2 Typical Interconnection, self Excitation for 400Vac operation

4
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A

Figure 3 Typical Interconnection, single-phase or 3-phase PMG Excitation

5
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A

Figure 4 Typical Interconnection, self Excitation for 220Vac operation

6
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A

Figure 5 The Drawing For Trimmer

7
INSTRUCTIONS FOR AUTOMATIC EXCITATION CONTROLLER
WT-3A

Figure 6. Operational Test

You might also like