The EA20S is a Special Generator Voltage Regulator that uses UltraFast CoPack IGBTs Power Devises
in its power stage . This design gives us the flexibility for using PMGs with varied frequencies outputs
from diverse alternator manufactures. In addition, A1 and A2 terminals for use in remote bias and
other terminals adding the ability to use 1 and 5 Amp CTs
.

1. Specifications
Sensing Input External Volts Adjustment
Terminal 0 to 110V = 95 ~ 135V ±10% @ 1KΩ
Terminal 0 to 220V = 180 ~ 250V
Terminal 0 to 380V = 360 ~ 515V Power Input X1、
、X2 Z1、 、Z2
Frequency 50/60 Hz, Jumper selectable 45 ~ 600HZ

Harmonic Voltage Thermal Drift


Voltage 25 ~ 300VAC 0.05% per ? change in AVR ambient

Voltage Regulation Analog Voltage Input A1 & A2


< ±0.5% (with 4% engine governing) 10% generator voltage per 1VDC

Voltage Build-up Current Compensation


Harmonic Residual Volt. > 5 VAC N : 5 A or N : 1A Input
Maximum 4% @ P.F. = 0.8
Output Voltage
Maximum 150VDC @ 220VAC Dimensions
150mm L * 135mm W * 55.3mm H
Output Current
Maximum Continuous 16A Weight
Intermittent 20 A for 10 sec 600g ± 2%

154.0

130.0

120 220 380/480 GND


Z1 X 2 Z2 F+ F- E1
E2

X1
203.0

180.0

A1 A2 VR VR S1 S2 S3

UFRO STAB LAM D R OO P VO LT T R IM


UF ON

Mechanical Specifications
AV R can be moun ted directly on the engine, genset, switchgear or control pan el that conforms to the
moun ting specification.
All voltage readings are to be taken with an average-read ing voltmeter Meggers and high-potential test
equipment must not be used. Use of such equipment could damage the AV R.
Installation is straightforward, remove the old regulator and plug new one in its place, the small plug is not used
and not installed (it is for data acquisition only). The regulator comes prewired for use in 220-volt sensing circuits if
you need 380 or 480-volt sensing change the E2 wire to another position.
Adjust your voltage and stability pots. Stability is best adjusted with a analog voltmeter connected to the output of
the generator and changing the load of the generator and adjusting the STAB pot for minimum needle movement.

2. WIRING
3. ADJUSTMENTS
1. Sensing Input terminals (single phase)
0 to 110V TRIM :Analog Voltage Input Adjustment A1, A2
0 to 220V VOLT :Voltage Adjustment.
0 to 380/480V
DROOP :Droop Adjustment.
2. F+ F- : Field Output Terminals
DIP :To set the frequency related voltage dip
3. X1, X2, Z2 PMG power input terminals. STAB :Stability Adjustment.
from 45 to 600Hz. See Drawings UFRO :UFRO Knee Point set.

4. S1, S2 & S3 Terminals. Current Compensation D IP SWITCH :Function Selection Switch.


inputs. S1 to S2 use 5A CTs -
S2 to S3 use 1A CTs. 1. Voltage Compensation : ON => for over 500
0 KW
2. Reaction Time Range: ON = > for 90 ~ 500 KW
5 . VR - VR Terminals used to external voltage
Adjustmnet using a 1K Ohm POT. Keep shorted 3. Rated Frequency 50/60Hz Selection :
.
if not used. ON = 60Hz

6. A1 & A2 Terminals accept remote DC voltage OFF = 50Hz


to adjust generator output voltage. The TRIM
controls controls its sensibility