Generator Automatic Voltage Regulator

Operation Manual

Self Excited Automatic Voltage Regulator


Using IGBT’s Insulated- Gate Bipolar Transistors

For use in Marathon* generators with PMG

* Use only for reference purpose only. This is not a Marathon Product

CALL US TODAY REQUEST A QUOTE SHOP ONLINE


1-888-POWER-58 parts@genpowerusa.com www.genpowerusa.com
1. Specifications External Volts Adjustment
Sensing Input Terminals ±10% @ 1KΩ
From 0 to 110v terminal (95 to 140 Volts) PMG Input 200v Max
From 0 to 220v terminal (170 to 260 Volts) 2 wire PMG
From 0 to 480v terminal (340 to 520 Volts)
Thermal Drift
Under/Frequency 50 or 60 Hz -
0.05% per Degree Cchange in AVR ambient
DIP Switch selectable
Voltage Regulation Analog Voltage Input
< ±0.5% using a 4% engine governor 10% generator voltage per 1VDC
Voltage Build-up
Current Compensation
Residual Volt. > 5 VAC
5 Amp CT (S2 to S1) 1 Amp CT (S2 to S3)
Output Voltage Maximum 4% @ P.F. = 0.8
Maximum 90VDC @220VAC
Output Current Dimensions
Continuous 8 A 150mm L * 135mm W * 55.3mm H
Max 12 A for 10 sec
Weight
600g ± 5%
PMG

PMG

220
110

480

F+ F- 0
A1 A2 VR VR S1 S2 S3

xx/1 CT

xx/5 CT

Generator Under Freguency LED indicator

UFRO STAB DIP DROOP VOLT TRIM


UF ON

1 2 3

ON 1-ON LARGER 500KW OFF LESS 500KW


2-ON 90-500KW OFF LARGER 500KW
1 2 3 3-ON 60HZ OFF 50HZ

Using a megger may cause damage to the semiconductors in this AVR.


______________________________________________________________________________________
2 EA 08A-2000

CALL US TODAY REQUEST A QUOTE SHOP ONLINE


1-888-POWER-58 parts@genpowerusa.com www.genpowerusa.com
2. WIRING 3. ADJUSTMENTS
1. 0V to 110V TRIM: Input sensitivity for terminal A1 & A2
0V to 220V VOLT: Generator output Volts adjust
0V to 480V Sensing Input terminals
DROOP: Droop adjustment
2. F+ & F- To Field
DIP: Load Acceptance Adjustment (LAN)
3. Connect the two PMG wires--The Capasitor is not needed
with this AVR STAB: Stability Adjustment
5 Amp CT use terminals S1 & S2 UFRO: Change knee point
4. S1-S2-S3:
1 Amp CT use terminals S1 & S3 DIP SWITCHES Set generator reaction time
5. VR-VR Remote voltage adjustment 1kΩ DIP Switch1
ON = Larger then 500 kw
OFF = Less then 500 kw
.
6. A1 & A2 Provided Connection to PF controller or other
devices, designed to work with signals up to +/- 5 Volts. DIP Switch 2
Inputs must be fully floating. TRIM Adjustable ON = From 90 to 500kw
OFF = Less then 90kw
.

DIP Switch 3 ON = 60Hz


OFF = 50Hz

PMG Exciter field C.T


Armature
xxx:1A or
Stator wires xxx:5A
R L1
200VAC max
50 to 500 Hz S L2
T L3

Capacitor is
not needed

PMG

UFRO PMG

STAB (F+) E+
(F-) E-

DIP 0V
110V
DROOP 220V
480V
VOLTS

TRIM
VR
VR
A1
A2

S1
S2
S3

EXT.VR 1k Ohm S2 to S1=5A CT


S2 to S3=1A CT

Use original spare (10A) fuse for replacement.


Product’s specification and appearance may be modified without prior notice.