CT Primary 600.00
CT Secondary 1.00
PT Primary 132000.00 V CT/PT Ratio
PT Secondary 110.00 V
Grounding Magnitude Kg= ((Z0-Z1)/3Z1)
Factor
Angle
0.50
0.83
ZONE Settings
ZONE-1 SETTING(80% ofLine Imp*CTR/PTR ratio) 14.01
ZONE-2 SETTING(100% ofLine Imp+50% of Shortest
24.61
Line Impedence*CTR/PTR ratio)
ZONE-3 SETTING 120% of (Line Imp+ longest Line
45.00
Impedence)*CTR/PTR ratio)
% of Accu ZONE-4 SETTING(25% of Line Imp) 3.50
0.31 #DIV/0!
IS2 is
TMS/(M-1)2
-0.05
0.00
Apply full load current and find the stability between two windings
Single phase pickup HV side and LV side of each phase-Zero sequence filter to be Disabled
Three Phase pickup of HV side and LV side-Zero sequence filter Disabled
Three Phase pickup of HV side and LV side-Zero sequence filter Enabled
Find the Min Diff Pickup
K1 Slope(Apply Full load Current and Ramp one current)or(Give above(IS1/K1)CT% at both HV,LV
K2 Slope
ISHS1 Trip - 10PU Means,give more than 10 times of FLC at HV side or LV side
ISHS2 Trip - 15PU Means,give more than 15 times of FLC at HV side or LV side
2nd harmonic Test-Phsically connect LV CT (R,Y,B,N)Over on to HV CT.Apply IN-PHASE 2 CT's at FLC.Apply HV-50HZ&LV-10
Same 2nd harmonic Procedure for 5th harmonic Procedure…
1-PU Means (1* FLC)
Other Method to find SLOPE
K1= to be less than IS2 Current.
K1 = (Id/Ib)
K2= to be above than IS2 Current.
K2 = ((Id-K1 IS2)/(Ib-IS2))
4
's at FLC.Apply HV-50HZ&LV-100HZ..Gradually Decrease 100HZ CT Current.When Current Reach Less than Setted Percentage w.r.to FL
Voltage(kV) 220 KV
Current(A) 600 A
Relay Operating Time(IEC SI) (0.14*TMS)/((I flt/I nom)^0.02-1) Angle 0 Deg
Pow/Min
Power for 60 Min
ating Angle(Over Current Protection)
OPER REV
46
-134
-74
-254
166
-16
erating Angle(Earth fault Protection)
OPER REV
136
-46
16
-166
256
74
Neutral Current
9
NUTRAL CT= SQRT of (a2+b2+c2-ab-bc-ca) 3
YMMETRICAL COMPOENTS
POWER
MVA MW Mvar
228.62 228.62 0.00
0.00 1.00 0.00
3.8104
228.624
GENERATOR DIFFERENTIAL PROTECTION
GEN DIFF: RELAY SETTING DIFF GRAP
DIFF MODE Biased Differential
Is1(A) 0.40 0.40
K1(%) 0.00 0.00
Relay Parameter
Is2(A) 6.00 6.00
K2(%) 70.00 0.70
To find K1 Slope - Apply below IS2 current at both side
I Diff(A) 0.27 0.27
I Bias(A) IB= {(I1+I2)/2}
From Relay
Bias Gen Side(A) 1.00
1.14
Bias NGR Side(A) 1.27
K1Slope is = (Id-IS1/Ib) -11.45% Id-IS1 -0.13
To find K2 Slope - Apply above IS2 current at both side
I Diff(A) 1.20 1.20
I Bias(A) IB= {(I1+I2)/2}
From Relay
Bias Gen Side(A) 1.40
2.00
Bias NGR Side(A) 2.60
K2={(Id-IS1-(K1IS2))/(IB-IS2)} K1IS2 0.00 0.80
(IB-IS2) -4.00 -4.00
K2 Slope is = -20.00% -0.20
DIFF GRAPH
1.00
2.00
3.00
4.00
5.00
6.00
7.00
8.00
9.00
10.00
11.00
12.00
13.00
14.00
15.00
16.00
17.00
18.00
19.00
20.00
21.00
22.00
23.00
Generator differential protection (87G) {P343/4}
overcurrent (50/51) (67)
negative phase sequence (NPS) overcurrent
Restricted earth fault (low impedance)
earth fault (50N/51N)
Neutral displacement/residual overvoltage (59N)
Sensitive directional earth fault (67N)
100% stator earth fault {P343/4}
Voltage dependent overcurrent (51V)
Under impedance (21)
Under voltage (27)
Over voltage (59)
Negative phase sequence (NPS) overvoltage
Under frequency (81U)
Over frequency (81O)
Reverse power/low forward power/over power (32R/32L/32O)
Negative phase sequence (NPS) overpower
Field failure (40)
Negative phase sequence thermal (46)
Volts/Hz (24)
Pole slipping (78) {P343/4}
Thermal overload (49)
CB fail and backtrip breaker fail