F 8.2.

4-03
Date 21.02.2011

ASTOR TRANSFORMER
TEST
Serial No:
Brand
11-3677
TRANSTEK

REPORT Vector Group Dyn11


CUSTOMER TYPE Normal Project 10-02800
POWER 400 KVA 3 PHASE FREQUENCY 50 Hz Cooling Sys ONAN

Tab. HV (V) LV(V) HV(A) LV(A) D.C. RESISTANCE 19

1 14000 H.V. (Ω) L.V.(mΩ)


2 14500 1U1V= 6,60 2U2V= 3,77
3 15000 400/231 15,396 577,367 1V1W= 6,61 2V2W= 3,75
4 15500 1W1U= 6,71 2W2U= 3,80
5 16000 RORT= 6,640 Rort= 3,77

NOMINAL TURNS-RATIO TESTING % ERROR(± 0.5)


TAB.
TURN RATIO 1U1V 1V1W 1W1U 1U1V 1V1W 1W1U

1 60,62 60,74 60,71 60,71 0,195 0,146 0,146


2 62,79 62,91 62,87 62,87 0,196 0,132 0,132
3 64,95 65,09 64,99 64,98 0,213 0,059 0,043
4 67,12 67,26 67,17 67,17 0,213 0,079 0,079
5 69,28 69,43 69,34 69,29 0,214 0,084 0,012

ISOLATION RESISTANCE(Giga ohm) 20 °C ISOLATION TESTING


TIME (s) 15 30 45 60 30 60 TEST NAME KV Hz. S.
H.V.-TANK (5 KV) _ 17 _ 23 17,0 23,0 Applied Voltage H.V. 38 50 60
H.V.-L.V(5 KV) _ 20 _ 31 20,0 31,0 Applied Voltage l..V. 3 50 60
L.V.-TANK (3 KV) _ 10 _ 15 10,0 15,0 Enduced Overvoltage 0,8 120 60

MEASUREMENT OF IMPEDANCE AND LOAD LOSS MEASUREMENT OF NO-LOAD AND CURRENT

NOMINAL VOLTAGE Wattmeter Multiplier Currents (A) Wattmeter


15000 W. 1 1 1709 W. 1 2U 4,82 1 200
Cur. (A) 15,396 V.T. 1 2 1561 V.T. 1 2V 4,68 2 391
Uk (V) 569,828 C.T. 1 3 1379 C.T. 1 2W 4,01 3 201

CALCULATION NO LOAD NO LOAD LOAD SHORT CIRCUIT Regulation Efficiency


VALUES LOSS CURRENT ( % ) LOSS VOLTAGE at 4/4 Full Load at 4/4 Full Load

(W) (% ) (W) +%10 CosΦ=1 CosΦ=1


GUARANTIED 930 1,5 6000 4 (%) (%)
VALUES 792 0,78 5513 3,87 1,44 98,45

OIL USED WEIGHT OF OIL (kg) WEIGHT OF ACTIVE PART (kg) TOTAL WEIGHT(kg)
SHELL DIALA BX 280 815 1365

CUSTUMER TEST MANAGER