PV Array Test Report Array1
Intial Periodic
INSTALLATION ADDRESS REFERENCE
PT Mulia Cemerlang Abadi MCA 125KW-Ref2A
Jl. Industri KM 12 Kp. Cirewed, Desa Sukadamai,
Sukadamai, Tangerang, Banten 15710, Indonesia DATE
09/01/2017
DESCRIPTION OF WORK UNDER TEST ENGINEER/INSPECTOR
To carry out offline testing of PV arrays & Strings prior to Energisation Amran Mohamad
TEST INSTRUMENTS
Seaward PV 150
STRINGS 1 2 3 4 5 6
Array 1 Module Wattage 260 W 260 W 260 W 260 W 260 W 260 W
Inverter 1 Quantity 20 20 20 20 20 20
Array parameters(as Voc (stc) 38.53 38.53 38.53 38.53 38.53 38.53
specif ied)
Isc (stc) 8.72 8.72 8.72 8.72 8.72 8.72
String over-current Type: Litell Fuse 0SPF015.T 0SPF015.T 0SPF015.T 0SPF015.T 0SPF015.T 0SPF015.T
protective device
Rating (A) 15 15 15 15 15 15
DC Rating (V) 1000 1000 1000 1000 1000 1000
Capacity (kA) 20KA 20KA 20KA 20KA 20KA 20KA
Wiring Type: PV1-F 1*4mm2 PV1-F 1*4mm2 PV1-F 1*4mm2 PV1-F 1*4mm2 PV1-F 1*4mm2 PV1-F 1*4mm2
DC Cables (mm2) 4 4 4 4 4
Earth (mm2) 16 16 16 16 16 16
String test Voc (V) 660 659 656 655 653 642
Isc (A) 1.32 1.28 1.22 1.16 1.12 0.81
Irradiance 300 300 300 300 300 300
Polarity Check OK OK OK OK OK OK
Array insulation Test voltage (V) 500 500 500 500 500 500
resistance
Pos - Earth (MΩ) 115 170 158 142 110 133
Neg - Earth (MΩ) 115 170 158 142 110 133
Earth continuity (where f itted) 0.5 Ohms 0.5 Ohms 0.5 Ohms 0.5 Ohms 0.5 Ohms 0.5 Ohms
Switchgear f unctioning correctly Yes Yes Yes Yes Yes Yes
Inverter make / model: Chint Power CPS CSA30KTL CPS CSA30KTL CPS CSA30KTL CPS CSA30KTL CPS CSA30KTL CPS CSA30KTL
Inverter serial number 10122771646002 10122771646002 10122771646002 10122771646002 10122771646002 10122771646002
Inverter f unctioning correctly Yes Yes Yes Yes Yes Yes
Loss of mains test: Anti-islanding OK OK OK OK OK OK
Comments:
Pv installations have been checked & tested and found to comply with the IEC/SNI standards and project specifications. PV Inter-
connections were made within the site Panel 8 enclosure and in-line with PLN guidelines.