VI-SOP-O&M-02

VI-IMSP-O&M-01-F02

RELAY TEST REPORT


JBS Enterprises Pvt. Ltd. Test Report for 33/132KV Terralight Solar Energy Sitamau SS Pvt Ltd.
(TSESSSPL)
First floor,Bella Vista,Oswal Park,Pokharan
Road no.2,Thane west ,Thane,Maharashtra RELAY TEST REPORT
Fax: +91 22 2543 7835 web:www.jbsepl.com
email: jbs@vsnl.com Date: 28/03/2023
CLIENT: Virescent Renewal Energy

TEST REPORT FORTRAFFO.DIFFPROTECTION RELAY (P643)

1. Test Equipment’s:
NO. Device Name Device Type
1 Test kit make PONOVO
2 Type PW460
3 Version 2.5
4 Serial No IN127101202

2. GENERAL DATA AND RELAY INFORMATION:

Sub. Name 33/132KV SITAMAUGSS Rated CT Current 150A/450A


Panel Name 132KV TRANSFORMER -1 Current Range 1A
Relay Make SCHNEIDER ELECTRIC Normal Volts 63.5V
Relay Type P643 Aux Volts 110V DC
Relay Serial No. 39509791 Frequency 50HZ
Relay Designation TRAFO DIFF. RELAY Date 28/03/2023

3. General Check:

Item Description Result

1 Physical inspection of the Relay  Yes  N/A OK

2 Inspect for physical damage / defects.  Yes  N/A OK

TESTED BY: WITNESSED BY: Client Rep.:


Mr. NAVEEN KUMAR JBS ENTERPRISES PVT. LTD. TERRALIGHT SOLAR ENERGY SITAMAU SS PVT. LTD.
(TSESSSPL)
Prepared BY:
Mr. PRATEEK
VI-SOP-O&M-02
VI-IMSP-O&M-01-F02

4. Measurement Test:

PARAMETERS WINDING-1 WINDING-2

Winding configuration HV side LV side


Power 25 MVA
PT Ratio(kV) 132 33
Rated current(Amp) 109.34 437.38
Full load current Ifl(mA) 0.729 0.972
Differential CT Ratio 150/1A 450/1A

5. Current Measurement Test:

INJECTED
MEASURED VALUES (In terms of Primary
CURRENT(Amp)
Values)
R Y B

HV SIDE CT 1A 1A 1A RN: 151.50A YN: 150.38 A BN: 150.85 A

LV SIDE CT 1A 1A 1A RN: 450.81A YN: 449.34A BN: 448.24A


PT 110V 132KV

6.DIFFERENTIAL PICK UP TEST & TIMING TEST:

Differential Pick Up Timing in ms


Phase
HV side Pick Up LV side Pick Up HV side LV side

L1 0.218 0.292 36 39

L2 0.218 0.292 36 39

L3 0.218 0.292 36 38
L1,L2,L3 0.147 0.197 40 51

TESTED BY: WITNESSED BY: Client Rep.:


Mr. NAVEEN KUMAR JBS ENTERPRISES PVT. LTD. TERRALIGHT SOLAR ENERGY SITAMAU SS PVT. LTD.
(TSESSSPL)
Prepared BY:
Mr. PRATEEK
VI-SOP-O&M-02
VI-IMSP-O&M-01-F02

7.STABILITY CHECKS: WITH HV AND LV WINDING :

Injected current ( A )
S.NO STATUS Time (Sec)
HV SIDE LV SIDE
0.145∟0° 0.194 ∟180°
1. 0.145∟-120° 0.194∟60° Stable No –Trip
0.145∟+120° 0.194∟300°
0.145∟0° 0.194∟0° T
2. 0.145∟-120° 0.194∟60° Unstable rip
0.145∟+120° 0.194∟300°

8.SLOPE TEST:Is1=0.200
K1=30.0%
Is2=1.500
K2=80.0%

INJECTED CURRENT IN MEASURED VALUES


S.NO SECONDARY IN P U STATUS REMARKS
HV SIDE LV SIDE Id Ir
400mA 750mA 0.258 0.844
1. 400mA 750mA 0.258 0.844
400mA 750mA 0.25 0.844 UNSTABLE
1A 805mA 0.354 1.175 IN SLOPE1 TRIP
2. 1A 805mA 0.350 1.175
1A 805mA 0.350 1.175
800mA 1.580A 0.679 2.082
3. 800mA 1.580A 0.679 2.082
800mA 1.580A 0.679 2.082 UNSTABLE
5A 2.710A 1.682 3.334 IN SLOPE 2 TRIP
5A 2.710A 1.682 3.334
4. 5A 2.710A 1.682 3.334
Slop 1:- (ID2-ID1)/IR2-IR1) x100
= (0.354-0.258)/1.175-0.844)x100
= 0.294x100
= 29.4%
Slop 2:- (ID2-ID1)/IR2-IR1) x100
= (1.682-0.679)/(3.334-2.082)x100
= 0.80x100
= 80%

TESTED BY: WITNESSED BY: Client Rep.:


Mr. NAVEEN KUMAR JBS ENTERPRISES PVT. LTD. TERRALIGHT SOLAR ENERGY SITAMAU SS PVT. LTD.
(TSESSSPL)
Prepared BY:
Mr. PRATEEK
VI-SOP-O&M-02
VI-IMSP-O&M-01-F02

9. VOLT/HERTZ PROTECTION:

Ref Operated Voltage Set V /Hz Operating Set time Optd. Time
V/Hz (Sec)
R-Phase 146.05 at 50Hz 2.310 2.310 10.00 10.08
Y-Phase 146.05 at 50Hz 2.310 2.310 10.00 10.07
B-Phase 146.05 at 50Hz 2.310 2.310 10.00 10.09

Ref Operated Voltage Set V /Hz Operating V/Hz Set time Optd. Time (Sec)

R-Phase 152.4 at 50Hz 2.410 2.410 10.00 10.08


Y-Phase 152.4 at 50Hz 2.410 2.410 10.00 10.04
B-Phase 152.4 at 50Hz 2.410 2.410 10.00 10.09

Ref Operated Set V /Hz Operating Set time Optd.Time


Voltage V/Hz (Sec)
R-Phase 165.1 at 50Hz 2.640 2.640 3.00 3.08
Y-Phase 165.1 at 50Hz 2.640 2.640 3.00 3.03
B-Phase 165.1 at 50Hz 2.640 2.640 3.00 3.04

10. HARMONICS BLOCK :

INJECTED INJECTED
S.NO STAGES CURRENT CURRENT AT N STATUS
AT 50Hz TIMES OF 50 Hz
1. 2nd HARMONICS HV Side 1A AT 50HZ 0.211 AT 100HZ BLOCKING
2 5th HARMONICS HV Side 1A AT 50HZ 0.191 AT 100HZ TRIP
3. 2nd HARMONICS LV Side 1A AT 50HZ 0.350 AT 100HZ BLOCKING
4. 5th HARMONICS LV Side 1A AT 50HZ 0.340 AT 100HZ TRIP

11. REF PROTECTION RELAY:-

TESTED BY: WITNESSED BY: Client Rep.:


Mr. NAVEEN KUMAR JBS ENTERPRISES PVT. LTD. TERRALIGHT SOLAR ENERGY SITAMAU SS PVT. LTD.
(TSESSSPL)
Prepared BY:
Mr. PRATEEK
VI-SOP-O&M-02
VI-IMSP-O&M-01-F02

Ref Set Current Time Delay Operating Time(sec)


HV-N CT 0.150 0.0 0.061

LV-N CT 0.150 0.0 0.062

12. FUNCTION CHECKS:

MEASUREMENT CHECKS TESTED & FOUND OK

PROTECTION FUNCTION CHECKS TESTED & FOUND OK

CONTACT OUTPUT RELAY CHECKS TESTED & FOUND OK

LED CHECK TESTED & FOUND OK

13. TEST RESULT :

RESULT PASS - RELAY FOUND HEALTHY ON ALL ASPECTS.

REMARKS NO

TESTED BY: WITNESSED BY: Client Rep.:


Mr. NAVEEN KUMAR JBS ENTERPRISES PVT. LTD. TERRALIGHT SOLAR ENERGY SITAMAU SS PVT. LTD.
(TSESSSPL)
Prepared BY:
Mr. PRATEEK