You are on page 1of 2

TEST REPORT OF DRIVE DUTY TRANSFORMER DATE : 18/11/2006

01. Designation : 216FA05TF10


Location : R.M.S.S
02. Name plate details :
Serial No : 7731/1 Type : ONAN
Make : VOLTAMP Vector Group : Dy11d0
Rated Primary Voltage : 6600 V Rated Secondary Voltage : 2305 V/2305 V
Rated Primary Current : 314.92 Rated Secondary Current : 450.86/450.86

Rating : 3600 KVA Percentage Impedance : 7.304% / 7.274%


03. Insulation Resistance Test ( in giga ohms ) :
Temp. : 32C

Megger Used Circuit Reference IR ( 15 Secs ) IR ( 60 Secs )

1000V Primary to Earth > 10 G OHMS > 10 G OHMS

1000V Primary to Secondary 01 > 10 G OHMS > 10 G OHMS

1000V Primary to Secondary 02 > 10 G OHMS > 10 G OHMS

500V Secondary 01 to Earth > 10 G OHMS > 10 G OHMS

500V Secondary 02 to Earth > 10 G OHMS > 10 G OHMS

04. Magnetising Current Measurment : ( At normal tap )

Applied Primary Voltage(V) Magnetising Current(mA)

RY YB BR R Y B

415 415 415 20 20 20

05. Magnetic Balance Test : ( At normal tap )

Measured Secondary Voltage(V)


Applied Secondary Voltage(V)
LV-1(Star) LV-2 (Delta)

RY YB BR ry yb br ry yb br

R Ph. Open 231.7 415 184 131 121.1 10.3 81.5 145 65
Y Ph. Open 90.1 325.5 415 48 149.7 101.9 32 114.2 145.2
B Ph. Open 415 338.6 78.6 152.6 53.4 99.4 145.4 119 27.7

06. Ratio Test :

Measured LT Side (V)


Applied HT Side (v)
Obtained
Tap position LV-1(Star) LV-2 (Delta)
Ratio
Rated Ratio

RY YB BR ry yb br ry yb br

03 415 415 415 145.3 145.3 145.4 145.3 145.3 145.2 0.35 0.35
07. Vector Group Test : ( Terminals R & r Shorted ) ( At normal tap )
Applied Voltage(V) Measured Voltage(V) LV - 1 (Star)
RY YB BR r1y1 y1b1 b1r1 Rb1 Ry1 Bb1 By1 LV-2 (Delta)
415 415 415 148.7 145.5 148.6 149.5 149.7 300.3 441
Yb2 By2 Bb2 Yy2
r1 R
367.9 367.5 273.2 273.3
Vector Group Dyn11 Conditions : n n y1 R, r2
b1
y
(1)RY = Rn+Yn : N/A
( 2) Ry1 = Rb1 : 149.5 ~ 149.7
( 3 ) Bb1 < By1 : 300.3 < 441 b2 y2
B Y
Vector Group Dy11d0 Conditions :
(1) Bb2 = Yy2 273.2 ~ 273.3 Vector Group Dyn11 B Y
Vector Group Dy11d0
8. Remarks : Transformer is in very good condition

9. Details of Equipments Used :

Sl. No. Description Make Range


01 1 kV Megger MEGGER 0 - 10 GIGA OHMS
0 - 600 VOLTS,
2 Digital Clamp on Meter FLUKE
0 -200A