: ESI/O&M/IMS/FR/62
TEST REPORT OF NUMERICAL RELAY Rev. No/ Date: 00/ 01-02-2021

Equipment Details:

CLIENT : 250MW Solariepro Urja Pvt. Ltd, Kadapa, Andhra Pradesh


Location : CCR5
Feeder Name : BUS PT 01
Equipment : RELAY
Make : C&S
Sl. No. : 58033670003
Type : IRU-PRO-U
PT Ratio : 33 kV/110 V
Aux. Supply : 230V AC

1. Service setting
SET SET
SI.NO PROTECTION CURVE TYPE TMS
CURRENT(A) TIME
1 U> 115%Un 0.03 DMT -
2 U>> 120%Un 0.03 DMT -

2. Measurement:

Injected Expected Measured Voltage(V) Actual Measured Voltage(A)


Voltage(V) R Y B R Y B

63.5 19.05 19.05 19.05 19.05 19.05 19.05

3. Secondary Injection Test

3.1 Overvoltage (U >) (Function: DMT)

Set Voltage(V) Set Time Pickup Injected Operating Time


Phase Ref
(Vs) (Sec) Voltage(V) Voltage(V) (Sec)
R-PHASE 73.02 0.03
73.02 0.03 73.199 74.0
Y-PHASE 0.038

B-PHASE 73.02 0.03


Doc. No.: ESI/O&M/IMS/FR/62
TEST REPORT OF NUMERICAL RELAY Rev. No/ Date: 00/ 01-02-2021

3.8 Overvoltage (U >>) (Function: DMT)

Set Voltage(V) Set Time Pickup Injected Operating Time


Phase Ref
(Vs) (Sec) Voltage(V) Voltage(V) (Sec)
R-PHASE 76.2 0.03
76.2 0.03 76.6 77.0
Y-PHASE 0.036

B-PHASE 76.2 0.03

4. Check List:

SI.NO DESCRIPTION OPERATION REMARK


1 Relay Trip and Start LED Function YES OK
Master Relay operation by relay current
2 YES OK
injection method
3 Protection relay output Contact Function OK OK
4 Service Setting adopted after testing done YES OK
5 Relay healthy status after testing done YES OK

5. RESULT:

The above testing values are quite satisfactorily and fit for put into the service.

Reference Tested By Witnessed By


Name Mr. Akash.R
Signature

Date of Testing 29/05/2023