You are on page 1of 6

Electricidad Pérez • C/ Mayor nº 21 • n28051 Madrid

Electricidad Pérez
C/ Mayor nº 21
n28051 Madrid

Tel.: +34 123 456-0


Fax: +34 123 456-100
Correo electrónico: info@electricidad-perez.es
Internet: www.electricidad-perez.es

Project: Nigeria Case Church Location: Nigeria / New Nyanya


Project number: ---
Grid voltage: 230V (230V / 400V)

System overview

1176 x .SMA SMA Demo Poly 425W (PV array 1)


Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof, Peak power: 499.80 kWp

8 x SMA STP 50-40/41 (CORE1) 1 x SMA STP 15-50

Battery system

MC-Box-12.3-20 3 x Lithium (350 kWh)

3 x SMA Sunny Island 8.0H

PV design data

Total number of PV modules: 1176 Spec. energy yield*: 1581 kWh/kWp


Peak power: 499.80 kWp Line losses (in % of PV energy): ---
Number of PV inverters: 9 Unbalanced load: 0.00 VA
Nominal AC power of the PV inverters: 415.00 kW Annual energy consumption: 493 MWh
AC active power: 415.00 kW Self-consumption: 398 MWh
Active power ratio: 83 % Self-consumption quota: 50.4 %
Annual energy yield*: 790.43 MWh Self-sufficiency quota: 76.2 %
Additional yield with SMA ShadeFix: 0 kWh Total nominal capacity: 350.00 kWh
Energy usability factor: 99.7 % Annual nominal energy throughputs of 275
the battery:
Performance ratio*: 85.9 %
CO₂ reduction after 20 years: 5,308 t

Signature

*Important: The yield values displayed are estimates. They are determined mathematically. SMA Solar Technology AG accepts no
responsibility for the real yield value which can deviate from the yield values displayed here. Reasons for deviations are various external
conditions, such as soiling of the PV modules or fluctuations in the efficiency of the PV modules.

1/6 Version: 5.30.2.R / 9/1/2022


Inverter designs
Project: Nigeria Case Church Location: Nigeria / New Nyanya
Project number: Ambient temperature:
Annual extreme low temperature: 15 °C
Average high Temperature: 31 °C
Subproject Subproject 1 Annual extreme high temperature: 40 °C

8 x SMA STP 50-40/41 (CORE1) (PV system section 1)

Peak power: 482.80 kWp


Total number of PV modules: 1136
Number of PV inverters: 8
Max. DC power (cos φ = 1): 51.00 kW
Max. AC active power (cos φ = 1): 50.00 kW
Grid voltage: 230V (230V / 400V)
Nominal power ratio: 85 %
Dimensioning factor: 120.7 % SMA STP 50-40/41 (CORE1)
Displacement power factor cos φ: 1
Full load hours: 1908.5 h

PV design data

Input A: PV array 1
42 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input B: PV array 1
40 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input C: PV array 1
20 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input D: PV array 1
20 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input E: PV array 1
20 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input A: Input B: Input C:


Number of strings: 2 2 1
PV modules: 21 20 20
Peak power (input): 17.85 kWp 17.00 kWp 8.50 kWp

Inverter min. DC voltage (Grid voltage 230 V): 150 V 150 V 150 V
PV typical voltage: 731 V 696 V 696 V
Min. PV voltage: 692 V 659 V 659 V

Max. DC voltage (Inverter): 1000 V 1000 V 1000 V


Max. PV voltage 986 V 939 V 939 V

Inverter max. operating input current per MPPT: 20 A 20 A 20 A


Max. MPP current of PV array: 22.3 A 22.3 A 11.1 A
Inverter max. input short-circuit current per MPPT: 30 A 30 A 30 A
PV max. circuit current 23.3 A 23.3 A 11.7 A

2/6 Version: 5.30.2.R / 9/1/2022


Input D: Input E: Input F:
Number of strings: 1 1
PV modules: 20 20
Peak power (input): 8.50 kWp 8.50 kWp ---

Inverter min. DC voltage (Grid voltage 230 V): 150 V 150 V 150 V
PV typical voltage: 696 V 696 V ---
Min. PV voltage: 659 V 659 V ---

Max. DC voltage (Inverter): 1000 V 1000 V 1000 V


Max. PV voltage 939 V 939 V ---

Inverter max. operating input current per MPPT: 20 A 20 A 20 A


Max. MPP current of PV array: 11.1 A 11.1 A ---
Inverter max. input short-circuit current per MPPT: 30 A 30 A 30 A
PV max. circuit current 11.7 A 11.7 A ---

PV/Inverter compatible

You get this inverter including SMA ShadeFix. SMA ShadeFix is a patented inverter software that automatically optimizes the yield of PV
systems in any situation. Even under shading conditions.

3/6 Version: 5.30.2.R / 9/1/2022


Inverter designs
Project: Nigeria Case Church Location: Nigeria / New Nyanya
Project number: Ambient temperature:
Annual extreme low temperature: 15 °C
Average high Temperature: 31 °C
Subproject Subproject 1 Annual extreme high temperature: 40 °C

1 x SMA STP 15-50 (PV system section 2)

Peak power: 17.00 kWp


Total number of PV modules: 40
Number of PV inverters: 1
Max. DC power (cos φ = 1): 15.31 kW
Max. AC active power (cos φ = 1): 15.00 kW
Grid voltage: 230V (230V / 400V)
Nominal power ratio: 90 %
Dimensioning factor: 113.3 % SMA STP 15-50
Displacement power factor cos φ: 1
Full load hours: 1801.1 h

PV design data

Input A: PV array 1
16 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input B: PV array 1
16 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input C: PV array 1
8 x .SMA SMA Demo Poly 425W, Azimuth angle: 0 °, Tilt angle: 11 °, Mounting type: Roof

Input A: Input B: Input C:


Number of strings: 1 1 1
PV modules: 16 16 8
Peak power (input): 6.80 kWp 6.80 kWp 3.40 kWp

Inverter min. DC voltage (Grid voltage 230 V): 150 V 150 V 150 V
PV typical voltage: 557 V 557 V 278 V
Min. PV voltage: 527 V 527 V 264 V

Max. DC voltage (Inverter): 1000 V 1000 V 1000 V


Max. PV voltage 751 V 751 V 376 V

Inverter max. operating input current per MPPT: 24 A 24 A 24 A


Max. MPP current of PV array: 11.1 A 11.1 A 11.1 A
Inverter max. input short-circuit current per MPPT: 35 A 35 A 35 A
PV max. circuit current 11.7 A 11.7 A 11.7 A

PV/Inverter compatible

You get this inverter including SMA ShadeFix. SMA ShadeFix is a patented inverter software that automatically optimizes the yield of PV
systems in any situation. Even under shading conditions.

4/6 Version: 5.30.2.R / 9/1/2022


Information
Project: Nigeria Case Church Location: Nigeria / New Nyanya
Project number:

Nigeria Case Church

Subproject 1

8 x SMA STP 50-40/41 (CORE1) (PV system section 1)


You get this inverter including SMA ShadeFix. SMA ShadeFix is a patented inverter software that automatically optimizes the
yield of PV systems in any situation. Even under shading conditions.

1 x SMA STP 15-50 (PV system section 2)


You get this inverter including SMA ShadeFix. SMA ShadeFix is a patented inverter software that automatically optimizes the
yield of PV systems in any situation. Even under shading conditions.

Increased self-consumption

SMA MC-Box-12.3-20
Maximum permissible PV power of the Multicluster Box exceeded.

5/6 Version: 5.30.2.R / 9/1/2022


Monthly values
Project: Nigeria Case Church Location: Nigeria / New Nyanya
Project number:

Diagram

Table

Month Energy yield [kWh] Self-consumption [kWh] Grid feed-in [kWh] Purchased electricity
[kWh]

1 73992 (9.4 %) 34450 39542 9703

2 67970 (8.6 %) 31827 36143 7864

3 73534 (9.3 %) 34704 38830 8378

4 67412 (8.5 %) 33867 33545 9040

5 66445 (8.4 %) 33792 32652 10012

6 59290 (7.5 %) 32977 26313 8900

7 52258 (6.6 %) 29552 22706 13960

8 52130 (6.6 %) 32575 19555 11224

9 57568 (7.3 %) 32194 25373 10489

10 70185 (8.9 %) 34301 35884 9640

11 75900 (9.6 %) 33077 42823 8901

12 73747 (9.3 %) 34770 38978 9272

6/6 Version: 5.30.2.R / 9/1/2022

You might also like