You are on page 1of 3

SAND2013-1394C

Photovoltaic Ground Fault Simulations Using SPICE

Jack Flicker and Jay Johnson


Sandia National Laboratories, Albuquerque, NM 87185, USA

fault conditions [3]. A common method of circuit simulation


Abstract — In order to better understand the impact of is the use of the Simulation Program with Integrated Circuit
changing the fuse ratings on ground fault protection devices Emphasis (SPICE). SPICE, originally developed at the
(GFPDs) of photovoltaic (PV) arrays with regard to detection University of California, Berkeley Electronics Research
window and nuisance tripping, a range of fault scenarios,
including array size, leakage current, fault position, and fault
Laboratory in 1973 [4], is a general-purpose, open source,
impedance were analyzed using a simulated program with analog circuit simulator used to predict circuit behavior. In
integrated circuit emphasis (SPICE). The simulations show that, this work, the program MacSPICE, a derivative of SPICE3f4,
by decreasing GFPD ratings, there is an improvement in the is used to analyze the behavior of PV systems in various array
number of faults that can be detected without increasing the configurations and ground-fault conditions [5].
number of nuisance trips and, therefore, the GFPD ratings The SPICE model of the PV array (Figure 1) is
mandated by UL1741 should be decreased in the future. accomplished through the construction of a single module
Index Terms — SPICE, ground fault, PV, GFPD, GFDI using a one-diode model. This module consists of an ideal
current source at the module short-circuit current (Isc) in
I. INTRODUCTION
parallel with a diode and shunt resistance (Rsh) and in series
with a series resistance (Rs). In order to increase the Voc of the
The mechanical, electrical, or chemical degradation of PV
module above the voltage drop of a regular diode (~0.6 V), the
systems can lead to a number of fault scenarios, including ideality constant of the diode is increased [6].
series faults, ground faults, intra-string faults, and string-to-
string faults. The behavior of the array and the fault
current/voltage can vary widely dependent on the type,
location, and impedance of the fault path, making accurate
detection without false-positives (nuisance tripping)
challenging. In order to mitigate ground fault effects, a
GFPD—often called the Ground Fault Detector/Interrupter
(GFDI)—is used. These devices typically consist of a simple
10x38 mm “midget” style fuse. Figure 1: (left) One diode model for single PV module. (right) IV
While there are a number of PV configurations and curve of single PV module
topologies in the United States, the most common is the
grounded, isolated system. Unfortunately this design is For the purposes of this work, the one-diode model is
known to have problems with undetectable ground faults in constructed to approximate a nearly perfect photovoltaic
some cases [1, 2] where the GFPD is not capable of de- module. The current source is set to supply 2.5 A at short
energizing the fault, resulting in multiple fires. Industry circuit, the diode has an ideality factor of N=80, the shunt
leaders have suggested lowering the GFPD (i.e., fuse) ratings resistance is set 11020  and the series resistance is set to 10
would improve the chances of detecting high impedance, low m. This module gives an IV curve with Isc of 2.5 A, Voc of
current ground faults. However, many system designers and 56 V, and Pmp of 118 W. The max power point has a current
operators are hesitant due to the belief that this will increase of 2.4 A and a voltage of 49.2 V.
nuisance-tripping events. In this work we conduct SPICE The PV array model is comprised of a number of strings
simulations in order to optimize the GFPD fuse rating (and wired in parallel. Each string is composed of 7 modules in
thus increasing the fault detection window) without series (Figure 2). Each module is connected to a bypass diode
exacerbating nuisance tripping. (Isat=4.710-12 A, N=1). When multiple modules are placed in
series to form a string, the frames of all the modules are
II. PV MODEL connected to earth via equipment grounding conductors [7].
This results in leakage current from the module to ground. In
PV modules are non-linear circuits. Their behavior is this work, to model leakage current, the positive terminal of
difficult to describe analytically without transcendental each module in a string has a leakage resistor connected to
equations. However, the use of computer circuit simulations ground.
can describe the behavior of a PV system for a wide variety of
While there is current leakage from a number of places in this abstract only details related to GFPD sizing will be
the array, the primary source of leakage in a PV array is in the discussed.
modules. Module leakage current is defined as the current
between the module, biased at some high voltage, and the III. RESULTS AND DISCUSSION
grounded frame. Leakage current measurements for
crystalline Silicon modules are described by IEC 61215 A set of simulations was carried out for a 25  fault at the
(section 10.15.3) [8] and UL1703 (section 21.5) [9]. In order positive terminals of modules 1 through 7, denoted as 1+
to simulate the leakage current of a real array, the positive through 7+ (Figure 3). The GFPD current is sub-linear with
terminal of each module in a string has a leakage resistor respect to array size and has a near linear relationship with
(Rleak) connected to ground. Rleak is taken to be a value of 5 array size for small array sizes and a nearly independent
M, giving a 100 A leakage current for a module biased at relationship for large array sizes. This is due to the inverter
500 V (UL maximum leakage current for a 1.5 m 2 module is Rmp decrease as array size increase. As strings are added in
11.1 A at 500 V). parallel, the PV current is increased without a corresponding
increase in output voltage. Since R mp has an inverse
dependence on system current, Rmp decreases rapidly for
smaller array sizes while remaining fairly constant for large
array sizes.

Figure 2: Schematic for a two-string array of modules that have a


leakage current, Rleak. The red lines denotes the current path through
the GFPD for a fault to ground. Figure 3: GFPD current vs. array size for 25  fault at various
module positions. The GFPD current is clearly sub-linear with
In each simulation, the PV array is constructed with respect to array size. For large array sizes, the load resistance (Rmp)
multiple modules connected to a central inverter. A grounded, is small enough compared to the fault resistance to divert a
isolated, central inverter is modeled because this topology is significant amount of current from the GFPD through the load.
susceptible to faults that are undetected by the ground fault
fuse. A resistor is taken as a basic approximation of the real For small arrays, the value of R mp is large compared to the
input impedance of an inverter and is set at the resistance fault resistance, so that the current path through the
required to generate maximum PV power, R mp, of the inverter/load is much more resistive than the current path
unfaulted array. through the fault/GFPD. As more strings are added, most of
Although physical inverters are a complex system the added current flows through the fault path.
containing transistors, capacitors, and switching controls [10], For large array sizes, the value of Rmp has decreased so that
only the real component of the inverter impedance is modeled the resistance of the inverter current path is smaller than the
here since, if voltage ripple and max power tracking [11] are resistance of fault/GFPD path. As more strings are added,
ignored, the PV system can be approximate by a steady state nearly all of the added current flows through the inverter and
DC system with a constant resistance. This means that the the GFPD current is nearly constant with regards to array size.
imaginary components of the inverter impedance have no UL1741 [12] defines the maximum GFPD detection setting
effect on the steady state solution before and after the fault as a function of array size. The standard lists a maximum
occurrence. During changes in state of the array, transients rating of 1 A for array sizes 0-25 kW, 2 A for 25- 50 kW, 3 A
due to energy storage elements are not long lasting enough to for 50-100 kW, 4 A for 100-250 kW, and 5 A for arrays
trip GFPDs. greater than 250 kW. The simulation data shown in Figure 3
The SPICE simulations carried out in this work have shows GFPD currents for certain fault conditions which would
focused on various aspects of GFPD sizing related to the PV not meet the maximum GFPD detection settings.
array, including array size, module leakage, GFPD resistance, For example, for arrays in the 100-250 kW range, the GFPD
and fault location. However, due to space considerations in rating is allowed to be upwards of 4 A. SPICE simulations of
ground faults have shown that, in this case, the fault current
for a ground fault at the positive terminal of either of the first ACKNOWLEDGEMENTS
two modules (1+ or 2+) is below this threshold of protection.
Most disturbing is the 1+ fault cause, which provides less This work was funded by the DOE Office of Energy
than 1 A of GFPD current for all array sizes. This GFPD Efficiency and Renewable Energy. Sandia National
threshold is undetectable by the UL1741 standard for GFPD Laboratories is a multi-program laboratory managed and
rating for any array size. operated by Sandia Corporation, a wholly owned subsidiary of
Figure 4 shows a close-up view of the 1+ fault shown in Lockheed Martin Corporation, for the U.S. Department of
Figure 3. The GFPD current of a 1+ fault (red trace) shows a Energy's National Nuclear Security Administration under
very small dependence on array size for large arrays. The contract DE-AC04-94AL85000.
entirety of this slope is due to module leakage current (blue
trace). It is apparent that the UL1741 standards would not
detect such a fault for any array size. In order to fully protect REFERENCES
a PV system from a 25  fault, it would be required to have a
0.25 A fuse for 1- and 2-string arrays (IGFPD=0.30 and 0.45 A). [1] B. Brooks. (2012, Mar) Bakersfield Report SolarPro. 62-
Larger array sizes could utilize a 0.5 A fuse if there were 70.
extremely high module leakage currents, e.g., 1 mA (~120 [2] A. Rosenthal, G. Ball, B. Brooks, and J. C. Wiles, "The
SolarABCs Ground-Fault Research Project - Examination
times larger than the IEC 61215 requirement). However, a
of Inverter Ground-Fault Detection Blind Spot and
0.25 A fuse would almost certainly not experience nuisance Recommendations for Mitigation," In Press.
tripping from leakage current alone (shown by the 100 A [3] Y. Zhao, B. Lehman, J. de Palma, J. Mosesian, and R.
blue trace) even for large array sizes. Lyons, "Challenges to overcurrent protection devices under
line-line faults in solar photovoltaic arrays," Audio,
Transactions of the IRE Professional Group on, pp. 20-27,
Sep 01 2011.
[4] L. W. Nagel and D. O. Pederson, "SPICE (Simulation
Program with Integrated Circuit Emphasis)." vol. ERL-
M382, ed: University of California, Berkeley, 1973, p. 62.
[5] L. Castaner and S. Silvestre, Modelling Photovoltaic
Systems using PSPICE. Chichester, West Sussex, England:
John Wiley and Sons Ltd, 2002.
[6] A. Devasia and S. K. Kurinec, "Teaching solar cell I-V
characteristics using SPICE," American Journal of Physics,
vol. 79 (12), p. 1232, 2011.
[7] J. C. Wiles, "Photovoltaic System Grounding," ed, 2012,
pp. 1-29.
[8] International Electrotechnical Commission, "Crystalline
Silicon Terrestrial Photovoltaic (PV) Modules-Design
Qualification and Type Approval," 2nd ed. Geneva, p. 102.
Figure 4: Close-up view of the 2+ and 1+ fault positions. The 1+
[9] Underwriters Laboratories, "Flat-Plate Photovoltaic
fault position has a sub-linear dependence on array size with a smal
Modules and Panels," 3rd ed. Northbrook, IL, 2008, pp. 1-
slope at large array sizes (due entirely to module leakage current).
82.
For any array size, a 1 A fuse (the lowest fuse rating mandated by
[10] J. Worden and M. Zuercher-Martinson. (2009, May) How
UL1741) would be insufficient to catch such a fault.
Inverters Work. SolarPro. 68-85. Available:
IV. CONCLUSION http://xiazai.inktronics.com.cn/Uploadfile/DownFile/
10-08-13/100813131907_hjkg.pdf
[11] J. Flicker, R. Kaplar, M. Marinella, and J. Granata, "PV
Undetected fault conditions in PV arrays present dangers to Inverter Performance and Reliability: What is the Role of
normal PV operations because they have been the cause of the Bus Capacitor?," Photovoltaic Specialists Conference
fires in the past. This is especially problematic for roof- (PVSC), Austin, TX, 2012, p. 6.
mounted systems. It is vital to mitigate fire hazards by [12] Underwriters' Laboratory, "Inverters, Converters,
increasing the fault detection window and decreasing the Controllers, and Interconnection System Equipment for
changes of an undetected fault condition. However, care must Use with Distributed Energy Resources," UL 1741 ed.
be taken to increase detection without a significant increase in Northbrook, IL, 2001.
nuisance tripping due to transients or module leakage.
In this work, SPICE simulations of ground fault conditions
of arrays of various sizes have shown that even modestly
resistive ground faults can be undetected if the UL1741
maximum allowable GFPD ratings are used. The results
strongly suggest that GFPD ratings can be lowered below 1 A,
even for large array sizes, without inducing nuisance tripping
due to module leakage.

You might also like