You are on page 1of 7

www.ietdl.

org
Published in IET Generation, Transmission & Distribution
Received on 9th June 2011
Revised on 15th September 2011
doi: 10.1049/iet-gtd.2011.0439

ISSN 1751-8687

Algorithm for single phase-to-ground fault digital


distance relay
Lj.M. Popović
Faculty of Electrical Engineering, University of Belgrade, Bulevar Kralja Aleksandra 73, 11020 Belgrade, Serbia
E-mail: ljubivoje@beotel.net

Abstract: The value of the potential that appears at the fault location during a ground fault at a high-voltage overhead line
depends on many different factors and cannot be considered as an a priori known quantity. Owing to this, the influence of
this quantity on the current and voltage measured at one of the line terminals is also unknown so the fault distance cannot be
exactly calculated, and as a final consequence, the relay may operate undesirably. It could happen especially in the case of
the relatively short lines such as those in sub-transmission systems. The development of the proposed algorithm is based on
the complete transmission line model under ground-fault conditions that include ground-fault current component coming from
the remote end. The proposed algorithm has been tested using the simulated current data. Sample test results have also been
presented in this study.

1 Introduction technique [5] utilises conventional power line


communication line traps and high-voltage capacitors of
Protection distance relays (DIRs) detect faults at high-voltage capacitor voltage transformers (CVTs). The line traps
overhead lines and initiate tripping of appropriate circuit confine the fault-generated high-frequency transient signals
breakers to isolate the faulted zone from the rest of the to the protection zone, where they are then captured by the
power system reliably and as fast as possible. Fault high-frequency voltage detectors. However, this technique
detection and locations methods that have been proposed requires line traps at both ends of the protected line, which
and implemented so far can be broadly classified as those unavoidably increases the costs and limits the application of
using the power frequency phasors in the past fault duration this technique. The non-communication is achieved by the
[1 – 10], using differential equation of the line and detection of whether or not the system is in a balanced
estimating the line parameters [11 – 13] and using travelling operation, to identify the breaker operation at remote end of
waves including travelling wave protection systems [14 – the protection section, from which the fault position (inside
17]. The problem is successfully overcome if synchronised or outside of the protected section) can be determined [19].
measurements are available at each line terminal [18]. However, this technique also has limited application. It
Unfortunately, some lines are not equipped with the cannot be applied in cases of radial sub-transmission
protective devices at both terminals, and the existing system systems where the circuit breakers are installed only at the
upgrade may not be economically justified. beginning of the lines. Another approach for overcoming
Most of the distant relay algorithms are based on the the problem is based on a specific improvement of the
computation of the post-fault, fundamental frequency voltages conventional algorithm for calculating zone-2 setting [8].
and currents measured at one of the transmission line Also, an attempt to achieve this goal is described in [6].
terminals. However, these algorithms need some simplifying Recent papers [9, 10] suggest the usage of fault resistance
assumptions to permit fault distance calculations. For example, estimation in distance relaying.
the algorithm proposed in [1] completely disregarded potential The algorithm presented in this paper uses a priori
appearing at the fault place. Since potential at the fault place determined (calculated or measured) value of grounding
can be significant (several kV), the distant relay may see the impedance at the border between zone-1 and zone-2 and the
fault in another protective zone and causes a non-selective results of an a priori made ground-fault current analysis. It
tripping of the adjacent circuit section. enables the operation of distant relay without causing
In recent decades rapid developments in microelectronics coordination problems characteristic in the cases of
technology have enabled substantial progress with research relatively short radial sub-transmission systems. Also, the
in the area of power transmission line protection leading to proposed algorithm considers particular fault type, so-called
a new concept in the area of transmission lines protection. ‘line-to ground with broken conductor fault’, which is not
One of them is the so-called non-communication protection the case with algorithms given in [9, 10].
that implies unit protection of transmission lines without the This paper is a logical continuation of the investigation
need for communication links. The first such protection presented in publications [2 – 4, 20]. The proposed

226 IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226 –232
& The Institution of Engineering and Technology 2012 doi: 10.1049/iet-gtd.2011.0439
www.ietdl.org
algorithm calculates the distance to the fault location by using determined by the following relation
fundamental frequency voltage and current from one terminal
of the transmission line. The technique necessary for Ua
obtaining corresponding phasors for these magnitudes at the Za = (3)
ZIa − (z0 − z)I0
moment of the fault is described in detail in [7].
However, in practice, the grounding impedance at fault place
2 Basic problem description is not negligible and is a complex function of the distance to
the fault location [2, 3, 20, 21]. Owing to this, at the fault
Let us assume one transmission and one distribution network location, potential Vf appears with a value proportional to
with directly grounded neutrals and connected by the single the total fault current If for a certain value of the
circuit line. DIR detects the faults and initiates tripping of transmission line reduction factor and for a certain value of
the circuit breaker to isolate fault. the fault impedance, Zf [3]. Since the fault current from the
For single-line-ground fault occurring anywhere along the remote end of line Ib contributes to the creation of this
line, the electrical circuits established during the fault may be potential, the DIR sees apparent impedance, which is larger
schematically presented as shown in Fig. 1. than the real impedance, (dZ + Zf ). Thus, it can be said that
The notation used in the given circuit has the following this current introduces a certain deviation in the
meaning: measurement data for determination of the fault location (Va
and Ia).
TN (DN) – transmission (distribution) network For a more accurate estimation of the fault location, it is
F – fault place necessary to investigate the influence of the unknown (not
d – distance to the fault place expressed in relation to the total available by measurements) quantities on the data obtained
line length by measurements. In the circuit shown in Fig. 1, the
Vf – potential at the fault place grounding impedance at fault place represents only one part
If – total ground-fault current, or current through the fault of the loop impedance measured at the relay location or in
place the local station. However, in practice, this is the equivalent
Ia , Ib – currents coming to the fault place from the impedance of the spontaneously formed and very complex
transmission and distribution network electrical circuit.
Zf – fault impedance At the faulted tower, the ground-fault current leaves the
Z – impedance of the faulted phase conductor. phase conductor and continues its flow through many
different paths. Owing to inductive coupling between the
The total ground-fault current is, according to the given phase conductors and the ground wire(s), a part of this
circuit, determined by the following relation current circulates only through metal paths (in the line,
through the ground wire(s) and in the station, through the
If = Ia + Ib = (Ia′ + Il ) + (Ib′ − Il ) (1) grounding connections). The remaining part of the fault
current returns conductively to the power system, through
where Ia′ , Ib′ are the components of ground-fault current the earth via ground wire(s), through a large number of
coming from the transmission and distribution network and towers and through the grounding grid of all substations
Il is the load current at the moment of a ground fault. with grounded neutral point(s).
It is necessary to determine the fault place on the basis of
the quantities measurable on the left line terminal (voltage
Ua and current Ia). The single phase-to-ground fault DIR, 3 Apparent fault impedance
based on the conventional method [1], measures the
impedance to the fault location using the following algorithm We will start our consideration by assuming that the
substations at the line terminals are the only substations
Ua with grounded neutral(s) in the whole power system. This
Za = (2) means that the total ground-fault current If returns to the
Ia − (z0 − z)I0 z−1 power system only through the grounded neutral(s) of these
two substations (A and B in Fig. 2).
where Ua is the relay place phase voltage, Ia is the relay place The real physical model of the transmission line under the
phase current, I0 is the relay place zero-sequence current and conditions of the ground fault at an arbitrary tower is
z, z0 are the positive- and zero-sequence line impedance per schematically presented in Fig. 2.
unit length. By forming the presented transmission line model, the
The impedance to the fault location can be expressed as a following idealisations and simplifications of the real
multiple of positive line impedance and a line length to the physical model were used
fault location. Thus, the distance to the fault location is

Fig. 1 Faulted power system Fig. 2 Transmission line with ground fault

IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226– 232 227
doi: 10.1049/iet-gtd.2011.0439 & The Institution of Engineering and Technology 2012
www.ietdl.org
† tower footing resistances are mutually equal and any potentials Vn(rI a′ ), Vn(rI b′ ), V0(rI a′ ), V0(rI b′ ) and V0(rIf ) can be
mutual interference to their own ground current is negligible, disregarded. Then we obtain
† impedances of the ground wire(s) between the two
adjacent towers are mutually equal.
Un0 ≃ Vf = Vn (rIf ) = rIf Zn (8)
In order to obtain better insight into the problem, we will
consider only the elements representing the ground-fault where Zn is the grounding impedance of the transmission line
current return paths through the earth as shown in Fig. 3. ground wire at the fault place.
The notation used in the given circuits has the following Impedance Zn can be determined by measurement at the
meaning: moment immediately before putting the line into operation,
or estimated by calculations [21].
r – reduction factor of the line Finally, the apparent (measured) impedance for the ground-
ZA(ZB) – impedance of the grounding system of the fault current return paths can be, according to Figs. 1 and 3,
substation A (B) which does not include the grounding expressed as
effects of the ground wire(s) of the line under consideration
Zs – self-impedance of the ground wire(s), per span Vf

Zm – mutual impedance between the ground wire(s) and the Zf a ≃ = grZn (9)
faulted phase conductor with common earth return, per span Ia
Rt – average tower footing resistance
n – number of spans to the fault place, counted from where
substation A
N – total number of spans
Ib I ′ − Il
G – remote ground g=1+ = 1 + b′ (10)
Ia Ia + Il
The reduction factor of the line is determined by
Many of the quantitative analyses already performed show
Z′
 
that the reduction factor r represents a complex number
r = 1− m (4)
Zs with a negligible imaginary part. Its value varies along the
line in a very narrow range of values [21] and can be
′ determined by pre-calculation or by pre-measurement.
Impedances Zs and Z m can be either calculated by using
formulae based on Carson’s theory of the ground-fault When the line is not transposed, this factor has the same
current return path [21], or measured. value along the whole line length, but different for each of
Since a transmission line is usually transposed, the value of the phase conductors because of their different specious
the reduction factor varies from tower to tower. However, positions in relation to the ground wire(s).
these variations are limited between the values The variations of the effective value of impedance Zn along
corresponding to the closest and the farthest positions of the the line are considered in [4], whereas a quantitative analysis
phase conductor with respect to the ground wire(s). of the real and the imaginary parts of this impedance is
By using the superposition principle, the potentials at performed in [3].
points 0 and n are determined as the sum of the potentials Finally, it should be said that the potential of the faulted
that currents rI a′ , rIf and rI b′ (parts of currents If , I a′ and I b′ ) phase conductor at fault location Vf (Fig. 1) for certain
flowing through the earth, separately produce at these value of current Ia depends on the following factors: r, g
places, or and Zn , or Zn + Ra , in the case when a fault is followed by
arc [11]. Their values for concrete transmission line depend
V0 = V0 (rIa′ ) + V0 (rIf ) + V0 (rIb′ ) (5) on the fault location and cannot be exactly determined if
the fault location is unknown.
Vn = Vn (rIa′ ) + Vn (rIf ) + Vn (rIb′ ) (6)

On the basis of (5) and (6), the voltage drop on the ground- 4 Algorithm derivation
fault current return paths can be expressed as
4.1 Impedance at a fault location equals Zn , or,
Un0 = Vn (rIa′ ) + Vn (rIf ) + Vn (rIb′ ) − V0 (rIa′ ) − V0 (rIf ) − V0 (rIb′ ) for arcing faults Zn + Ra
(7) According to the circuit shown in Fig. 1, the measured
voltage, Ua , is the sum of the voltage drop in the line to the
In practical conditions, the relations between the considered fault place and the potential, Vf . Thus, by using (9) the
quantities are such (ZA ≃ ZB ≪ Zn and I a′ , If ) that the following is obtained

Ua
Zm = = dZ + grZf (11)
Ia

The notation used in the above equation has the following


meaning:
Zm is the impedance determined on the basis of the
measured quantities Ua and Ia and Z is the line impedance
Fig. 3 Ground-fault current return paths through the earth determined, in accordance with [1], by the following

228 IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226 –232
& The Institution of Engineering and Technology 2012 doi: 10.1049/iet-gtd.2011.0439
www.ietdl.org
expression parameters including those that are, because of simpler
presentation of the real electrical circuit, disregarded in the
I0 previous consideration are expressed only through R, X, Rm ,
Z = Z1 + (Z0 − Z1 ) (12) Xm and wf . Line parameters R and X represent a priori
Ia
known, whereas Rm and Xm represent input data that will be
where Z1 is the positive-sequence impedance of the entire line obtained through the data acquisition system for each
and Z0 is the zero-sequence impedance of the entire line. ground fault appearing on the transmission line.
Impedances Z1 and Z0 can be obtained by measurement at Unfortunately, the value of wf cannot be a priori known, or
the moment immediately before putting the line into obtained through the data acquisition system. However,
operation. Thus, it can be said that impedance Z is an a having in mind the task of the DIRs in a power system, the
priori known line parameter. following question arises: whether the exact location of
By dividing the complex equation (11) into its real and each fault along the line is essential for its correct
imaginary parts, the following two equations are obtained operation? The answer is negative since it suffices only that
the DIR exactly differentiates the faults occurring on zone-1
Re{Zm } = dR + Re{grZf }, V (13) from those occurring in zone-2. This goal can be achieved
with an algorithm highly accurate only for faults occurring
Im{Zm } = dX + Im{grZf }, V (14) on the border between zone-1 and zone-2 and in its vicinity.
On the basis of the quantitative analysis given in Section 5
Then, by dividing (13) with the real part of impedance Z, and for a concrete line, we can adopt one value for angle wf
(14) with the imaginary part of this impedance, we obtain exactly corresponding to only one of the possible power
system configurations and only to the faults on the border
Re{grZf } between zone-1 and zone-2. In this way, all other power
dr = d + (15) system configurations and all other faults along the line are
R
also involved, but with a certain approximation. According
Im{grZf } to this, the algorithm (20) can be modified into
di = d + (16)
X
d = c1 Xm − c2 Rm (21)
In these equations dr and di represent relative distances to the
fault location obtained by using the known Zm and Z, and by
totally ignoring the potential at the fault location (Zf ¼ 0). Coefficients c1 and c2 represent a priori determined
These two distances are mutually different (dr = di), since, parameters that can be calculated by
according to the quantitative analysis [2, 3, 20], the real and
the imaginary parts of the impedances Z and Zf are 1
generally not proportional (R/X = Rf/Xf ). Also, because the c1 = (22)
ratio between Re{grZf} and Im{grZf} changes from tower to X − cR
tower [3], it is realistic to assume that the proportion R/
X ¼ Re{grZf}/Im{grZf} in an actual case does not exist. c
c2 = (23)
The product of g, r and Zf is an unknown quantity at the X − cR
moment of a ground fault. Nevertheless, there is something
about it that is known. The real and the imaginary parts of where c is the tan wf (L1), wf (L1) is the angle wf determined
this product are mutually connected by for the fault at the distance L1 and adopted on the basis of
ground-fault current analysis performed for different
Im{grZf } = Re{grZf } tan wf (17) possible power system configurations and L1 is the distance
corresponding to the foreseen end of the zone-1.
In the given expression, wf denotes the angle between the The adopted value of wf should satisfy criteria that the DIR
potential of the faulted phase conductor at fault place and correctly operates for any power system configuration.
current Ia . It can be presented as

wf = wg + wr + wn (18) 4.2 High resistance at the fault location

where wg is the phase angle of the coefficient g, wr is the In some relatively rare cases the ground fault on a
phase angle of the reduction factor r and wn is the phase transmission line appears as a consequence of accidental
angle of the impedance Zn . contact between the phase conductor and the earth (directly,
Finally, on the basis of (15) – (17), the following algorithm or through some object standing on the earth, e.g. falling
is obtained down of the phase conductor). Thus, instead of impedance
Zf (Figs. 1 and 2) we have a grounding resistance of the
Xdi − Rdr tan wf phase conductor at the fault place. The value of this
d= (19) resistance depends on many local factors and circumstances,
X − R tan wf and varies within a very wide range from case to case.
Owing to this, the value of this resistance cannot be known
or, in somewhat simpler form in advance. However, something about this resistance is
well known. This resistance is so large (usually above
Xm − Rm tan wf 50 V) that its value is significantly larger than the real part
d= (20)
X − R tan wf of impedance Zm that can be obtained in the previous case.
On the basis of this and Figs. 1 and 3, for the identification
The effects of the numerous line and power system of this type of ground fault, the following criteria can be

IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226– 232 229
doi: 10.1049/iet-gtd.2011.0439 & The Institution of Engineering and Technology 2012
www.ietdl.org
established † distribution network: Z1B ¼ 0, Z2B ¼ 0, Z0B ¼ j27 V;
† grounding impedances: ZA ≃ 0 and ZB ≃ 0.
Re{Zm } . R + Ra + |ZB | (24)
Line parameters:
dr = di (25)

The main characteristic of this type of ground fault is in the † phase conductor: Z1 ¼ (0.1199 + j0.4086) V/km and
following: the fault currents appearing because of these Z0 ¼ (0.3242 + j1.2614) V/km in the case of steel ground
ground faults are relatively small. As a consequence, these wire and Z0 ¼ (0.3005 + j0.9864) V/km in the case of
currents cannot provoke any damages to the electrical ACSR ground wire;
equipment even if they last significantly longer. Owing to † total line length: 5 and 2.5 km;
this, these ground faults could be treated as faults that occur † average tower footing resistance: Rt ¼ 20 V;
in the zone-2 independent of where they actually occurred. † average span length: 250 m;
Finally, open-circuit faults representing another type of fault † load current is disregarded, or: Il ¼ 0.0 [in accordance with
are also involved through the proposed algorithm. (10), for a radial sub-transmission systems this is the worst
case from the standpoint of algorithm accuracy];
† arc resistance: Ra ¼ 0.2 V
5 Quantitative analysis of essential
a. steel ground wire;
parameters
† self-impedance of ground wire, ZS ¼ (0.8750 + j0.3046)
As has been shown, angle wf consists of three separately V per span;
defined angles (18). Thus, the value of this angle can be † reduction factor of the line with steel ground wire,
estimated through consideration of each of these angles r ¼ 0.963 2 j0.065
separately. b. ACSR ground wire;
The value of the phase angle of impedance Zn(wn) in different † self-impedance of ground wire, ZS ¼ (0.0896 + j0.1820) V
practical conditions is separately considered in [3]. The reason per span;
for this is, in fact, that the values of tower footing resistance † reduction factor of the line with ACSR ground wire,
may vary within a wide range from tower to tower, depending r ¼ 0.669 2 j0.091.
on the type of soil, the ageing of the metal in the soil and the
season of the year. The quantitative analysis performed in [3] The values of the equivalent impedances substituting
shows the following: the different variations in the value of the transmission and distribution network correspond to
the tower footing resistance, even at their extreme values, the prevailing power system operation conditions. The
have no significant influence on the value of the angle, wn . necessary calculations are performed by using the analytical
Another important observation is that the so-called ‘end procedure presented in [21].
effects’ influencing the effective value of grounding The calculation results obtained by using the given relevant
impedance [2, 20], also influence the phase angle of this data in the case of a line with steel ground wire are presented
impedance. However, these two influences produce effects on in Tables 1 and 2.
the accuracy of the algorithm (20) that almost completely On the basis of the results presented in the given tables, it is
cancel each other out and can practically be disregarded [3]. evident that the value of angle wg changes along the line
The most important observation based on the mentioned within a very narrow range of values. The remarkable
quantitative analysis is: this angle can be considered as changes of the power system configuration expressed
approximately constant along the whole line length. through the value of the reactance X0A or X0B also have no
Having in mind the purpose of the derived algorithm it is greater influence on the value of this angle at any fault
sufficient if the value of angle wn is obtained by location along the line.
measurements (or by calculations) performed at only a It is also important to note that these variations are smaller
single tower located at the foreseen border between zone-1 when the line is shorter. On the basis of the given data, it is
and zone-2. Through the value of this angle, the influence
of the arc at fault location can also be taken into account. It
can be done by using the following relation Table 1 Values of angle wg along the line of 5 km in gradients (8)
X0A , V X0B , V d
Rn + Ra
wn = arctan (26)
Xn 0.0 0.2 0.4 0.6 0.8 1.0

The value of the phase angle of the reduction factor can be 2.1 27 0.23 20.43 21.17 22.01 22.97 24.08
treated as constant along the entire line length [20]. 6.3 27 0.62 20.04 20.78 21.62 22.58 23.69
Generally, the value of wg varies along the line and depends 2.1 54 0.08 20.35 20.82 21.32 21.85 22.43
on power system configuration at the moment the fault occurs.
The power system situation where this parameter has abrupt
changes is caused by different faults mainly short circuits that Table 2 Values of angle wg along the line of 2.5 km in gradients (8)
can be appeared at any time and anywhere in a power
system. The variations of this parameter we will consider in X0A , V X0B , V d
the case of the 110 kV line shown in Fig. 1. The necessary
relevant data are as follows: 0.0 0.2 0.4 0.6 0.8 1.0

2.1 27 0.15 20.26 20.75 21.24 21.82 22.35


Power system: 6.3 27 0.41 0.02 20.49 20.97 21.55 22.10
† transmission network: Z1A ¼ j4.3 V, Z2A ¼ j4.3 V, 2.1 54 0.05 20.20 20.47 20.74 21.04 21.16
Z0A ¼ j2.1 V;

230 IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226 –232
& The Institution of Engineering and Technology 2012 doi: 10.1049/iet-gtd.2011.0439
www.ietdl.org
not difficult to show that the value of angle wg in the case of the Table 5 Steel ground wire and faults with arc
lines with ACSR ground wire also changes in the similar limits.
Line length 2.5 km, or N ¼ 10

6 Testing algorithm Rt , V ds grZf , V Zm , V d

20 0.60 2.4162 + j0.2635 2.6982 + j1.3028 0.5996


The proposed algorithm for ground-fault detection was tested
0.70 2.2843 + j0.2412 0.6133 + j1.4537 0.6949
using computer simulations. The faults were simulated in the
0.80 1.9697 + j0.2154 2.3457 + j1.6005 0.8000
case of the 110 kV line with data that are given in the previous
0.90 1.3156 + j0.1067 1.7386 + j1.6657 0.8779
section.
1.00 1.2540 2 j0.0104 0.7240 + j1.7217 0.9773
The adopted values of the average span length and average
tower footing resistance ensure a high participation of the
fault impedance in the value of measured impedance, Zm .
Thus, the influence of variations in the value of wf on the
accuracy of the proposed algorithm should be highly Table 6 ACSR ground wire and faults with arc
manifested through the results of testing. Due to this, the Line length 2.5 km, or N ¼ 10
adopted testing conditions are certainly more severe than
ones that can be encountered in practice. Rt , V ds grZfa , V Zm , V d
The necessary values of the parameters, wn and wg , are
20 0.60 0.4668 + j0.2809 0.7369 + j1.1827 0.6457
adopted to be equal to the corresponding values of these
0.70 0.4444 + j0.2470 0.7596 + j1.2991 0.7277
angles obtained for the fault on the distance that is equal to
0.80 0.4230 + j0.2012 0.7832 + j1.4036 0.8000
80% of the total line length. Certainly, such selection should
0.90 0.3411 + j0.1110 0.7463 + j1.4637 0.8603
ensure the highest degree of accuracy where such accuracy is
1.00 0.2489 2 j0.0100 0.6992 + j1.4930 0.9003
most desirable. This is at the foreseen end of zone-1, or at
the foreseen beginning of zone-2. Then, the results of the
numerical simulations were used as inputs for the proposed
algorithm. Afterwards the outputs of the algorithms were
tested by comparison with the corresponding distances of Table 7 Calculated fault distance; line length 5 km
simulated ground faults, ds . Even more important calculation X0A , V
results are presented in Tables 3–6.
The influence of the changes in the configuration of the Steel ground wire
transmission and distribution network on the algorithm 27 0.6899 0.7492 0.8058 0.8632 0.9178
accuracy has been separately considered. For this purpose it ACSR ground wire
was assumed that the reactance, X0A , has three times greater 27 0.7018 0.7499 0.7977 0.8402 0.8770
value, and, in the other case, that the resistance Z0B has two
times greater value. These changes cause variations in the
calculated fault distances for the faults simulated at towers
number 14, 15, 16, 17 and 18 (longer line), as well as at
the towers number: 6, 7, 8, 9 and at the line end (shorter Table 8 Calculated fault distance; line length 5 km
line), as is shown in Tables 7 – 10. X0B , V
As can be seen, a high degree of accuracy is obtained for all
considered lines and for all the considered fault locations. Steel ground wire
54 0.6933 0.7596 0.8132 0.8693 0.9458
ACSR ground wire
Table 3 Steel ground wire and faults with arc 54 0.7046 0.7535 0.8025 0.8467 0.8862

Line length 5 km, or N ¼ 20

Rt , V ds grZf , V Zm , V d
Table 9 Calculated fault distance; line length 2.5 km
20 0.70 2.7976 + j0.2132 3.4556 + j2.6382 0.6857
0.75 2.7079 + j0.2314 3.4129 + j2.8296 0.7436 X0B , V
0.80 2.5787 + j0.2409 3.3307 + j3.0124 0.8000 Steel ground wire
0.85 2.3465 + j0.2433 3.1455 + j3.1880 0.8571 27 0.6069 0.7012 0.8229 0.8792 0.9178
0.90 1.9540 + j0.2235 2.8000 + j3.3414 0.9121 ACSR ground wire
27 0.6539 0.7317 0.8020 0.8672 0.8890

Table 4 ACSR ground wire and faults with arc

Line length 5 km, or N ¼ 20


Table 10 Calculated fault distance; line length 2.5 km
Rt , V ds grZf , V Zm , V d
X0B , V
20 0.70 0.6740 + j0.3949 1.3040 + j2.4991 0.7045
0.75 0.6321 + j0.3680 1.3075 + j2.6225 0.7532 Steel ground wire
0.80 0.5786 + j0.3295 1.2990 + j2.7931 0.8000 54 0.6114 0.7091 0.8148 0.8693 0.9458
0.85 0.5132 + j0.2770 1.2786 + j2.9878 0.9063 ACSR ground wire
0.90 0.4365 + j0.2060 1.2469 + j3.0674 0.9455 54 0.6463 0.7289 0.8046 0.8682 0.9132

IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226– 232 231
doi: 10.1049/iet-gtd.2011.0439 & The Institution of Engineering and Technology 2012
www.ietdl.org
Also, according to the results in Tables 3 – 6, the highest faults on the border between zone-1 and zone-2 and in its
degree of accuracy is obtained for a fault distance, d ¼ 0.8, vicinity. For application of the proposed algorithm one
where it is most desirable. preliminary ground-fault current analysis is necessary. A
When configuration of the power system is changed in such demonstrated high degree of accuracy in determination of
way that its equivalent reactance, X0A , or X0B , become ground-fault location enables a reliable and sensitive relay
significantly larger, zone-1 becomes slightly larger. In the operation. In the case of relatively short lines this quality
considered numerical examples, this increase is, according means the elimination of the coordination problem and the
to Tables 7 –10, smaller than one line span. Thus, it is not need for synchronous measurements or long-distance data
difficult to conclude that the correct DIR operation in the transfer.
considered cases is achieved by adopting the value of angle
wg that corresponds to the prevailing power system
operation conditions. However, in cases when these
variations are so great that correct DIR operation is
8 References
jeopardised, the other value of angle wg should be found 1 Lewis, J.L.J.: ‘Blackburn, protective relay principles and applications’
and adopted for calculations c1 and c2 . This value should (Marcel Dekker, New York, 1987)
be such that the mentioned variations do not exceed the 2 Popović, Lj.M., Radojević, Z.M.: ‘Digital fault-location algorithm
foreseen limits. It can be determined on the basis of the including grounding impedance at fault place’, IEE Proc. C, 2001,
148, (4), pp. 291–295
preliminary ground-fault current analysis and is placed 3 Popović, Lj.M.: ‘A digital-fault location algorithm taking into account
between the value that corresponds to the prevailing power the imaginary part of the grounding impedance at fault place’, IEEE
system conditions and the value that corresponds to the Trans. Power Deliv., 2003, 18, (4), pp. 1489–1497
power system conditions, when the equivalent power 4 Radojević, Z.M., Popović, Lj.M.: ‘Digital algorithm for distance relay
including grounding impedance at fault place’, Eur. Trans. Electr.
system impedances obtain their maximal anticipated values. Power, 2002, 4, (4), pp. 269–274
In this manner, correct digital DIR operation will be 5 Johns, A.T., Aggarwal, R.K., Bo, Z.Q.: ‘A novel nonunit protection
ensured for any possible power system configuration. technique for EHV transmission systems based on fault-generated
The effect of approximation made in the given numerical noise’, IEE Proc. C, 1994, 141, (2), pp. 133– 140
example, ZA ≃ 0, is certainly negligible (actual values of 6 AlFuhaid, A.S., Sayed, M.A.: ‘A recursive least-squares digital distance
relaying algorithm’, IEEE Trans. Power Deliv., 1999, 14, (4),
ZA are between 0.05 and 0.5 V). This impedance reduces pp. 1257– 1262
the relative participation of the fault impedance, Zf , in the 7 Sidhu, T.S., Ghotra, D.S., Sachdev, M.S.: ‘An adaptive distance relay
value of the measured impedance, Zm (Figs. 2 and 3). This and its performance comparison with a fixed data window distance
means that higher accuracy of the proposed algorithm will relay’, IEEE Trans. Power Deliv., 2002, 17, (3), pp. 691–697
be obtained in practical conditions. Under the unrealistic 8 Sidhu, T.S., Baltazar, D.S., Polomino, R.M., Sachdev, M.S.: ‘A new
approach for calculating zone-2 setting of distance relays and its use
assumption that this impedance is so large that the value of in an adaptive protection system’, IEEE Trans. Power Deliv., 2004,
V0 is equal to Vf (Fig. 3), the influence of the unknown 19, (1), pp. 70– 77
impedance, Zf , on the algorithm accuracy would be 9 Essa, M.: ‘Ground distance relay compensation based on fault
completely cancelled. The situation would be identical to resistance calculation’, IEEE Trans. Power Deliv., 2006, 21, (4),
pp. 1830– 1835
the idealised situation when this impedance is completely 10 Filomena, A.D., Salim, R.H., Resener, M., Bretas, A.S.: ‘Ground
disregarded. However, the influence of the grounding distance relaying with fault-resistance compensation for unbalanced
impedance ZB is completely different. For correct DIR systems’, IEEE Trans. Power Deliv., 2008, 23, (3), pp. 1319–1326
operation, this impedance should be sufficiently small, or 11 Djurić, M.B., Radojević, Z.M., Terzija, V.V.: ‘Time domain solution of
should, on the basis of (21), satisfy the following criteria fault distance estimation and arcing fault detection on overhead lines’,
IEEE Trans. Power Deliv., 1999, 14, (1), pp. 60– 67
12 Gapalakrishnan, A., Kezunovic, M., McKenna, S.M., Hamai, D.M.:
c1 X − L1 max ‘Fault location using the distributed parameter transmission line
|ZB | ≤ − R − Ra (27) model’, IEEE Trans. Power Deliv., 2000, 15, (4), pp. 1169–1174
c2
13 Segui, T., Guillot, M., Honchin, P., Bastord, P.: ‘Fundamental basis
distance relayng with parametrical estimation’, IEEE Trans. Power
where L1max is the maximal possible reach of zone-1. Deliv., 2001, 16, (1), pp. 99–104
For the considered lines of the length of 2.5 km, these 14 Dong, X., Ge, Y., Ne, J.: ‘Surge impedance relay’, IEEE Trans. Power
criteria are satisfied when |ZB| is smaller than 2.5 and Deliv., 2005, 20, (2), pp. 1247–1256
0.33 V for the steel and ACRS ground wire, respectively. 15 Spoor, D., Zhu, @.G.: ‘Improved single-ended traveling-wave
fault location algorithm based on experience with conventional
In the case of longer lines, the relative participation of the substation transductions’, IEEE Trans. Power Deliv., 2006, 21, (3),
fault impedance in the value of the measured impedance is pp. 1714– 1720
smaller (Zm ≫ Zf ) for faults in the vicinity of the end of 16 Vazquez, E., Costrasita, J., Chacon, O.L., Conde, A.: ‘A new approach
zone-1, and in accordance with this, higher accuracy in traveling-wave distance protection, part I: algorithm’, IEEE Trans.
application of algorithm (21) can be expected. Power Deliv., 2007, 22, (2), pp. 795 –800
17 Dog, X., Kong, W., Cui, T.: ‘Fault classification and faulted-phase
The demonstrated high accuracy can be explained by the selection based on the initial current traveling wave’, IEEE Trans.
following fact: The proposed algorithm takes into account Power Deliv., 2009, 24, (2), pp. 552 –559
all parameters necessary to characterise the return current 18 Kezunovic, M., Perunicic, B.: ‘Automated transmission line fault
paths of a single phase-to-ground fault at an overhead line. analysis using synchronized sampling at two ends’, IEEE Trans.
Power Syst., 1996, 11, (1), pp. 441– 447
As is already mentioned, a DIR of such accuracy is 19 Bo, Z.Q.: ‘Adaptive non-communication protection for power lines BO
specially required in cases of relatively short lines that are scheme 2- the instant operation approach’, IEEE Trans. Power Deliv.,
encountered sub-transmission systems. 2002, 17, (1), pp. 92–96
20 Popović, Lj.M.: ‘Analytical expression for voltage drops on return paths
of ground-fault current when faults occur in transmission lines’. IEEE
7 Conclusions PES Summer Meeting, 15– 19 June 2001, Paper: 01SM046
21 Popović, Lj.M.: ‘Practical method for evaluating ground fault current
This paper presents a novel DIR algorithm capable of distribution in station, towers and ground wire’, IEEE Trans. Power
computing correctly the distance to the ground fault for the Deliv, 1998, 13, (1), pp. 123– 128

232 IET Gener. Transm. Distrib., 2012, Vol. 6, Iss. 3, pp. 226 –232
& The Institution of Engineering and Technology 2012 doi: 10.1049/iet-gtd.2011.0439

You might also like