Professional Documents
Culture Documents
Abstract—This paper presents an improved distance protection However, reliable pilot communication channel unfortunately
algorithm for detecting ground faults in transmission systems with cannot be sometimes laid in the cable trench. As example, for
cascaded overhead-submarine cable segments. The mathematical the 400 kV inter-tie Egypt and Jordan with a composite
core of the proposed distance protective function considers the transmission line crossing the Aqaba Gulf, it is not appropriate
charging currents of both overhead and underground cable to include a pilot circuitry. Therefore, distance protection is
segments. Hence, an accurate detection of the fault event van be
considered as a primary protection for the composite
realized. On the other hand, the proposed algorithm overcomes
the non-homogeneity of the composite transmission systems, via transmission line [5], [6].
updating the calculated impedance for faults in the remote section.
For evaluation purposes, a detailed simulation is utilized for a real
400 kV Taba-Al-Aqaba inter-tie composite transmission using the Distance protection concept depends on simple RL model
ATPDraw program. However, developing the phasor computation in measuring the impedance between the relay and fault point.
and the distance relaying algorithm are processed in Matlab. The Distance protection operates when the measured impedance
obtained results are analyzed and compared with the conventional enters the adopted operation characteristics. The non-
core of the distance relaying function, where the results emphasize homogeneity of the cable and overhead sections results in
the efficacy of the presented distance scheme for composite inconsistent ratios of reactance to resistance and the zero
overhead-cable lines. sequence to the positive sequence impedances for each line
segment. Thus, combining overhead line and cable segments
Index Terms— Transmission systems, Composite lines,
together influences the performance of the distance function
Distance relays, Shunt capacitors.
letting the fault be more distant from its geometrical point [7-
9]. Moreover, the significant shunt capacitors with the cable
I. INTRODUCTION
segments may seriously affect the performance of the distance
T
RANSMISSION systems have been established for function with simple series RL model in particular. These
transferring the electrical energy from the power plants to effects may lead to unnecessary tripping of the local relay or
the substations near the loads. Power is usually transmitted undesirable acceleration of the remote one [5].
through overhead transmission lines. However, the majority of
the new construction looping is underground transmission cable
due to environmental and aesthetic concerns. These cables are In 1997, the IEEE Relaying Committee suggested different
connected to the existing overhead lines forming cascaded setting rules for composite lines. Since, these suggestions
depend strongly on the cable parameters, setting calculations
overhead-cable transmission lines [1]. Unfortunately, cables
for such lines become more complicated [10]. Another method
have impedance lower than the overhead line due to the smaller
was proposed in [11] for composite lines by identifying the
spacing between the cable conductors. Furthermore, the cable
faulted segment whether to be either in the cable section or in
zero-sequence impedance angle is less than the corresponding the overhead section. This was done by extracting the DC
angle for the overhead lines owing to the cable sheath. Also, component of the fault current using the DFT (Discrete Fourier
the smaller spacing between the cable conductors and the Transform) digital filtering computation and its derivates with
sheath as well as the higher dielectric constants of the cable respect to time. However, the shunt capacitance may affect its
insulations enlarge its capacitances significantly [2-3]. performance remarkably [12-13].
Due to environmental conditions, more than 80% of the In 2005, Moore et. al. employed the conventional distance
transmission lines faults are single phase to earth ones. computation depending on lumped element network modeling
Therefore, a reliable protection for this fault type is required with PI representation to include the shunt capacitances in
[4]. On the other hand, unit protection tools with pilot schemes computation [14]. However, using the conventional distance
such as current differential, phase comparison, and directional protection function in fault impedance measurements may
comparison methods can be used with underground affect its performance seriously [15-17]. Therefore, modifying
transmission lines as a result of their relatively short lengths. the distance protection core considering the electrical
characteristics of both the cable and the overhead line in
addition to the shunt capacitances is clearly required.
779
zero which is equivalent to the summation of the sequence
components such as:
E af = E1 f + E 2 f + E 0 f = 0 (5)
E1mZ 1 −1 I 1Y1 −1
E af = E1 − mZ 1 − 1 I 1 −
2
E 2 mZ 1 −1 I 2Y1 −1 (6)
+ E 2 − mZ 1 −1 I 2 −
2
E 0 mZ 0 − 1 I 0Y0 −1
+ E0 − =0
2
Considering,
E1 + E 2 + E 0 = E a ሺሻ
ǡ
Am 2 − Bm + C = 0 ሺͳͲሻ
ǡ
§ EZ Y ·
A = 0.5Y1−1Z1−1 ¨¨ E1 + E2 + 0 0 −1 0 −1 ¸¸ ǡ
© Y1−1Z1−1 ¹
780
section (overhead sgment). It is worthy to note that (10) is TABLE I
computed based on the associated line parameters of the first ACTUAL AND CALCULATED FAULT DISTANCE FOR 10:100% FAULTS ALONG
section with reasonably accurate estimated fault distance. Then, COMPOSITE LINE WITH MEASURING FROM THE OVERHEAD SIDE.
the relay measured impedance up to the fault point is computed Calculated
Calculated
as, fault
Actual fault Calculated fault Final
Fault distance
distance fault distance estimated
Z R = mZ 1− 1 (11) location (km) using
Faulted (km) from distance (km) using fault
(% line updating at
Section the relay (km) using updating at distance
length) the first
When the per unit estimated fault distance m from (10) is point (11)
junction (19)
the second
greater than one, this can be interpreted as the fault is in the junction.
second section. Then, a remarkable error is expected for the 10 4.36 4.3780 -21.2965 -25.0019 4.3780
estimated fault distance m owing to performing the related First 20 8.72 8.6827 -15.4796 -20.6708 8.6827
computation based on the parameters of the first line section section 30 13.08 13.0785 -9.5110 -16.2513 13.0785
40 17.44 17.4455 -3.5211 -11.8712 17.4455
only. Then, the need for updating the corresponding fault
50 21.8 21.4325 2.0982 -7.7805 22.098
distance estimation procedure based on the parameters of the Second
60 26.16 23.3327 4.9916 -5.7519 24.99
Section
second line segment after the junction point of both line 70 30.52 26.9879 10.6948 -1.9089 30.6948
sections. In this case, the new equivalent circuit in Fig. 1.c is Third
80 34.88 30.7390 16.8518 2.0366 35.6366
utilized to calculate accurately the measured impedance using a 90 39.24 34.8372 23.4104 6.2175 39.8175
Section
100% 43.6 33.1380 20.6228 9.3 42.9
new estimated fault distance m as follows.
Y1−1 Y
I1J = I1 − E1 − 1−1 E1 J (15)
The updated voltage and current values at the junction point 2 2
between the first and the second sections are first compensated Y1−1 Y
and then used to compute the updated voltage drop as, I2J = I2 − E 2 − 1 −1 E 2 J (16)
2 2
E 1Y1−1 (12)
E 1 J = E 1 − Z 1 −1 ( I 1 − ) Y0 −1 Y
2 I0J = I0 − E 0 − 0 −1 E 0 J (17)
EY 2 2
E2 J = E 2 − Z 1−1 ( I 2 − 2 1−1 ) (13)
These values are then used to compute the new per-unit length
2
fault distance m in the second section from the junction point.
E0Y0−1
E0 J = E0 − Z 0−1 ( I 0 − ) (14) Then, (9) is modified as,
2
§ E Z Y ·
0.5Y1−2 Z1−2 ¨¨ E1 J + E2 J + 0 J 0−2 0−2 ¸¸ m 2
© Y1−2 Z1−2 ¹ (18)
− Z1−2 ( I aJ + k 0−2 I 0 J ) m + EaJ = 0
where Z1-2 and Z0-2 as well as Y1-2 and Y0-2 are the corresponding
values for the second section. Then, the final updated fault
impedance is estimated as,
781
The system was modeled using the ATPDraw program. The included in the fault path is an overhead line. Similarly, the
prepared simulated fault cases are extracted from the ATP to be response a fault at 70% of the cable sectionis demonstrated in
processed by the proposed distance relay function described in Fig. 6 for a fault at 60% of the total Taba-Aqaba composite line
the previous section. Also, a conventional quadrilateral digital length. Unlike the proposed algorithm, the conventional one
distance relay is also modeled for comparison purposes. The allocated the fault as an external one out of Zone1. The
first zone was set to 80 % of the circuit positive phase sequence response for faults external of Zone1 at 90% of the total
impedance. Where the first part of considered transmission line composite line length is shown in Fig. 7 having a clear
represents 46% of the total line length, the second part is ended underreach with the conventional distance protectionas well.
at 77% of the total line length, and the third part is ended at Therefore, the conventional distance protection will underreach
100% of the total line length. Thereby, the first zone covers the for internal faults, while the proposed algorithm identified this
first and second parts. The responses of relays situated at Taba fault successfully as internal ones in both all cases.
substation was examined as evaluated in the following section.
FAULT DISTANCE
points. For each case, the proposed algorithm was first applied 60 single circuit single circuit Double circuit
cable section
to determine the fault impedance with taking into account the overhead section overhead section
distance protection using the same prepared test cases. Fig. 5 Fig. 5 Proposed and conventional distance protection performances for solid
shows the corresponing response of the proposed and the faults along the overhead section.
convetional algorithms for faults located along the first
overhead section by showing the impedance locus diagram for
different solid faults in the first section of the considered
composite line. As depicted from the results, both tested
algorithms shows similar performances as the line segment
782
18 18
16 16
14 14
12 12
10
X(ohm)
10
X(ohm)
8 8
6 6
4 4
setting charactristic setting charactristic
2 2
conventional distance performance conventional distance performance
proposed distance performance proposed distance performance
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8 0
0 0.5 1 1.5 2 2.5 3
R(ohm)
R(ohm)
Fig. 6 Impedance locus diagram for solid single phase-to-ground fault case at
60% of total Taba-Akaba line length using conventional and purposed Fig. 8 Impedance locus diagram for phase-to-ground external fault case at 90%
algorithms of total Taba-Akaba line length using conventional and proposed algorithms.
18
16
25
conventional algorithm
14
using updated compensation factor
12 Improved algorithm
20
10 J1 J2
X(ohm)
8
15
6
E rror(% )
4
setting charactristic 10
2 conventional distance performance
proposed distance performance
0
0 0.2 0.4 0.6 0.8 1 1.2 1.4 1.6 1.8
R(ohm) 5
Fig. 7 Impedance locus diagram for phase-to-ground internal fault case at 70%
of total Taba-Akaba line length using conventional and proposed algorithms.
0
10 20 30 40 50 60 70 80 90 100
Fig. 8 shows the impedance locus diagram for an external fault percentage(%ZL)
783
The afforementioned case was tested with the developed considered in the proposed algorithm. Moreover, the problems
simulatuon as well. As depicted in Fig. 10, the conventional of non-homogeneity of the parameters of different line sections
distance protection has a severe underreach status, while the parameters were perfectly eliminated by the proposed
resistive reach setting is extended to cover a wide range of algorithm. The proposed algorithm has been tested with a 400
fault resistances. With the extended resistive reach setting, kV inter-tie composite line which connecting both of the
overreach occurred similarly with the simulatd field test case as Egyptian and Jordanian networks. The performance of the
demonstrated in Fig. 11 showing a similar perofmance to those distance relay is investigated with both the conventional
practically in the recorded accident. The proposed algorithm, mathematical core and the improved algorithm. Results have
however, identified correctly such faults as into the second proved that the proposed scheme eliminates the effects of the
zone as seen in Fig. 10 and Fig. 11. This corroborated th remarkable error sources of distance relays with such lines
correct peformance for dealing with faults in composite lines. including the fault capacitance effects and fault distances as
compared with the conventional core of distance relays with an
18 average error lower than 2.5 % of the line length.
16
VII. ACKNOWLEDGEMENT
14
The authors are expressing their gratitude to the electrical
12 authorities of the Egyptian and Jordanian countries for
releasing the transmission system data and fault records.
10 Special thanks to the technical administration at Taba
X(ohm)
8
substation for their cooperation.
6 VIII. REFERENCES
[1] O.D. Naidu ,and A. K Pradhan , "Adaptive Distance Relay Setting for
4
Hybrid Power Transmission Networks", Innovative Smart Grid
setting charactristic
Technologies Conference Europe (ISGT-Europe), Istanbul, October 12-
2 conventional distance performance
15, 2014.
proposed distance performance
0
0 0.5 1 1.5 2 2.5 [2] M. Popov, G. Rietveld, Z.Radojevic and V. Terzija" An Efficient
R(ohm) Algorithm for Fault Location on Mixed Line-Cable Transmission
Corridors", International Conference on Power Systems Transients
Fig. 10 Impedance locus diagram for solid single line to ground external fault (IPST2013), Vancouver, Canada 17-20 July, 2013.
case at 100% of total Taba-Akaba line length using conventional and proposed [3] T. Kawady, H. A. Darwish, A.-M. I. Taalab and N. El- Sokromy,
algorithms “Distance Relaying Field Problems for Composite Transmission Lines”,
15th International Conference on Power System Protection, Bled,
Slovenia, 6-8 Sept., 2006, pp. 171-177.
18
[4] ABB, BUTansmission Systems and Substations, “Protection Application
handbook,” in, 0 ed. Roma, , ch.1, sec. 1, pp. 98.
16
[5] J. Vargas, A. Guzmán, and J. Robles, "Underground/Submarine Cable
14
Protection Using a Negative-Sequence Directional Comparison
Scheme",26th Annual Western Protective Relay Conference, October
12 1999
[6] P. Sofroniou, A. D. Georgopoulos, “Protection challenges for the
10 overhead / underground / undersea double circuit 400 kV EHV GIS
X(ohm)
784
Capacitance". 2009 IEEE Power & Energy Society General Meeting, TABLE II
Print ISBN 978-1-4244-4241
[13] P. J. Moore, A. Q. Bo, R. K. Aggarwal, and A. Johns, ‘Digital simulation Dimensions of the used towers for the single circuit section (in meters)
of the effects of shunt capacitance on the operation of a digital distance
protection algorithm’. Proc. 3rd IEE Int. Conf. on Advances in Power
system communications operation and Management, Hong Kong,
1995, (November IEE Conference Publication), Vol. 417, 266–270. d1 h4 h3 h2 1
[14] P. J. Moore, Z. Q. Bo, and R. K. Aggarwal, “Digital distance 16.4 3.25 5.86 10.79 16.59
protection for composite circuit applications” IEE Proc.-Gener.
Transm. Distrib., Vol. 152, No. 2, March 2005.
[15] O. D. Naidu and A. K. Pradhan, “Adaptive distance relay setting for
hybrid power transmission networks”, Innovative Smart Grid
Technologies Conference Europe (ISGT-Europe), 2014 IEEE PES, 12-15
Oct. 2014.
[16] Junyu Han and Peter A. Crossley, “Fault location on mixed overhead line
and cable transmission networks”, PowerTech (POWERTECH), 2013
IEEE Grenoble, 16-20 June 2013.
[17] Claus Leth Bak and Christian F. Jensen, “Distance protection of cross-
bonded transmission cable-systems”, International Conference on
Developments in Power System Protection (DPSP 2014), IET, 31 March-
3 April 2014.
[18] New, Warren C, “Combined phase and ground distance relaying”,
American Institute of Electrical Engineers, Transactions ,Vol. 69,pp. 37 -
44, 02 June 2009.
[19] M. P. Thakre and V. S. Kale “Distance protection for long transmission
line using PSCAD” International Journal of Advances in Engineering &
Technology, Vol. 6, Issue 6, pp. 2579-2586, Jan. 2014.
[20] A. Zahran, M. Elsad, N. Elkalashy, T. Kawady, and A.-M. Taalab
"Improved Ground Distance Protection for overhead / Underground
Transmission Systems"17th international Middle East Power System
Conference (MEPCON2015), 1079, Mansoura university, Egypt, Dec.
2015.
[21] H. E. Prado-Félix , V. H. Serna-Reyna, M. V. Mynam, M. Donolo, and A. Fig. 13 Underground section configuration Taba-Aqaba Cascaded
Guzmán "Improve Transmission Fault Location and Distance Protection Transmission Line
Using Accurate Line Parameters". GRIDTECH 2015, New Delhi, India,
April 8–10, 2015.
IX. APPENDIX
d1
h1
h2
h3
h4
785