Professional Documents
Culture Documents
Abstract—This paper introduces novel methods for the identi- fault currents. The fault current can be further limited by con-
fication and location of very high impedance one phase-to-earth necting a suitable reactance between the neutral point of the net-
faults in medium-voltage (MV) networks in order to improve the work and the earth. This so-called Petersen coil has a positive
electrical safety and reduce the number and duration of outages to
customers. The examination is restricted to neutral compensated effect on the extinction of the earth fault arc too. Neutral com-
and isolated MV systems which are the prevailing neutral treat- pensated MV networks are widely used in Europe. In the Nordic
ment practices in Europe. The main target of the study was the countries, MV networks have mainly isolated or compensated
development of the new method for the identification and loca- neutrals. The neutral compensated MV networks have increased
tion of earth faults up to very high fault resistances. The method rapidly during the past years due to, for example, increasing un-
is technically applicable in actual use because it utilizes standard
measurements available at all 110/20 kV primary substations. No derground cabling also in rural areas and high-quality require-
new measuring instruments or devices are needed. The major al- ments of electricity distribution. Customers have become less
gorithm is based on the calculation of the fault resistance for every tolerant of even short interruptions of supply. These days, short
MV feeder. Field experiments in real networks have also been con- interruptions due to autoreclosing are taken into account in net-
ducted for testing the methods. The indication method presented work business regulation.
can identify and locate faults approximately up to 100–200 k .
An HIEF leads to very low fault current whose magnitude
Index Terms—Distribution network, earth fault, high- can be only some tenths of amperes. Thus, the detection of such
impedance earth fault, medium-voltage (MV) network. faults is a very challenging task. The continuous supervision
of each MV feeder in order to make the early detection of the
developing earth faults possible is clearly needed. It supports
I. INTRODUCTION preventive maintenance strategies too.
In a general sense, the term “HIEF” means an earth fault
whose resistance is above the tripping range of the conven-
0885-8977 © 2014 IEEE. Personal use is permitted, but republication/redistribution requires IEEE permission.
See http://www.ieee.org/publications_standards/publications/rights/index.html for more information.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
falls to the ground with high resistivity. These faults also de- of the algorithm are evaluated in [9]. Reference [3] presents
velop when the load-side end of the broken conductor has an a corresponding method for earth fault indication. The fault
earth contact. Faults with covered conductors often have very impedance can be determined in terms of the measured voltages
high impedance. A broken overhead line pin insulator, cable ter- and the zero-sequence impedance of the network. The method
minal, or faulty surge arrester can also cause a HIEF. All such detects the existence of the fault somewhere in the network
faults tend to evolve into a full-scale earth fault. The location and faulty phase. The change of zero-sequence current of the
of HIEFs is largely based on information from the public. The individual feeder caused by an earth fault is compensated by
situation is problematic from the safety point of view. using the zero-sequence impedance of the appropriate feeder
The fault current with HIEF is very small and difficult to dis- [3]. Reference [10] proposes a phase asymmetry parameter for
tinguish from current due to capacitive unbalance of the system. improving the reliability and efficiency of the HIEF detection
The second problem is that there are almost always very small process especially with neutral compensated systems.
variations of neutral voltage in the sound system too. These vari- References [11] and [12] present a wavelet-based
ations can be from conditions such as: high-impedance fault detector for arching faults. In [4], the
• weather conditions (e.g., snowfall, rain, thunderstorms); condition monitoring and fault detection of the MV covered
• switching operations (change of galvanic length and un- conductor lines has been studied based on partial-discharge
balance of system); (PD) measurements.
• opening or closure of disconnector poles at slightly dif-
ferent times;
B. Neutral Grounded Networks
• adjustment of compensation coil.
These changes of neutral voltage are difficult to distinguish The behavior of the solidly earthed or low-resistance earthed
from HIEFs. This type of fault can even reduce a neutral voltage MV system is completely different with an earth fault compared
by accidentally compensating the capacitive unbalance of the to neutral isolated and compensated systems. Thus, the indica-
system. Thus, the monitoring of only the effective value of the tion of the high-impedance fault (HIF) in a network with such
neutral voltage may be ineffective. The detection of the HIEF neutral earthing practices is a completely different task than in
can, to some degree, be achieved by neutral voltage relays. The a network with an isolated or resonant earthed neutral system.
lowest chosen voltage threshold value depends on the neutral Earth faults in networks with a solidly earthed neutral with an
voltage present during the normal operating state. equipotential earth bounding system are normally detected by
According to [3], the typical resistance of an unseasoned tree simple overcurrent relays. Fuses are also commonly used for
is in the range of 20–80 k . According to [4], the typical fault the overcurrent protection. An HIF in solidly earthed networks
resistance that is composed of an unseasoned tree is approxi- is characterized by a fairly low fault current and random arcing
mately in the range of 15–200 k , including the resistance of between a downed conductor and earth [13]. HIFs typically
the tree and its grounding resistance. These resistance values occur when an overhead line conductor breaks and falls to the
are valid in those seasons when the earth is not frozen. In the ground. This results in an energized high-voltage (HV) con-
winter, much higher resistances, ranging up to several hundreds ductor coming within the reach of the personnel. In addition,
of kilo-ohms or some megohms can be found. Most faults of arcing accompanies many HIFs, resulting in a fire hazard. Al-
this type are out of range of the neutral overvoltage relays. though the fault current with HIF may be several tens of am-
peres, it is unlikely that conventional protection (e.g., fuses, re-
III. INDICATION OF HIEFS lays, reclosers) will operate [14]. The dimensioning of the fuse
can be, for example, 100 A. Phase relays function as an overcur-
A. Neutral Isolated and Compensated Networks rent protection and the settings are typically much higher than
There is a group of methods developed to detect phase-to- the current rating of the fuses. Thus, HIFs must be cleared man-
earth faults using steady-state data. These methods are based ually in such systems [13].
on the calculation of the phase-to-earth resistance of the feeders Generally, a “high impedance fault” is a broad classification
[5]–[7]. In [6], the method is based on the superposition of the for all faults not classified as overcurrent faults. Hence, there
voltage signals of a certain frequency for the detection of low- is no unique set of characteristics attributable to such a wide
current phase-to-earth faults. range of fault activity. One fault may arc, another may not. One
In [5], [8], and [9], three methods are presented for the may have high harmonic content, another may not. One may
detection of resistive single-phase-to-earth faults in a neutral result from a broken conductor with a corresponding load loss.
compensated system. The algorithm called DESIR is based Another might result in increased current from contact with a
on the comparison of the residual currents of the feeders or tree limb without breaking the conductor [13]. Because of the
their variations. The method called DDA also uses the varia- widely varying characteristics of HIFs, it is unrealistic to expect
tion of the residual currents. In addition, the variation of the a single algorithm to detect even the majority of faults reliably
neutral voltage, phase-to-earth voltages, and the values of the and safely.
phase-to-earth admittances of the feeders are needed [5], [8]. There is a large range of methods for the detection of HIFs
The DDA algorithm requires a periodic injection of a residual in solidly or low-resistance earthed distribution networks based
current by the automatic tuning system for the arc suppres- on energy variance and randomness algorithms [15], harmonic
sion coil. The influence of the fault resistance, fault duration, analysis [16], fuzzy set theory [17], and artificial-intelligence
and the frequency of transient oscillations on the accuracy methods [14], [18].
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
where
(5)
(10) (13)
The theory of compensated power systems defines the unbal-
where ance of the system using the unbalance coefficient [19]. The
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
total phase-to-earth capacitance depends on the electrical length neutral voltage during the healthy state of the
of the feeders of the system. It is advisable to use the total network;
phase-to-earth capacitance of the system in its normal
neutral voltage during the faulty state of the
state as a reference. Then, the sum of the unbalances of the
network.
feeders is equal to the unbalance of the entire system. The value
for can be obtained by measurements or using network (16) can also be applied for determining for a healthy
data. By using coefficient and capacitance , the sum feeder. According to (17) the fault impedance for all feeders can
current of the healthy feeder i can be written in the following be calculated applying the following formula [5].
form:
(18)
TABLE I
CALCULATED FAULT RESISTANCES (LENGTH
OF THE FAULTY FEEDER WAS 18 km)
(22)
where
VIII. CONCLUSION
The method for indicating the high-impedance earth faults
was developed and presented. The method was tested by ar-
ranging the field experiments in neutral isolated and compen-
sated networks. According to the tests, the indication algorithm
was able to detect and locate faults up to 100–200 k . Indi-
cation of the faulty phase and faulty feeder operating reliably,
and the accuracy of the calculated fault resistances seemed to be
adequate for reliable indication. The method is technically ap-
plicable in actual use because it utilizes standard measurements
available at all 110/20 kV substations.
REFERENCES
[1] Elsäkerhetsverket, Starkströmsföreskrifterna (in Swedish) Stockholm,
feeder was composed of overhead lines and underground cables. Sweden, 1999:5, 1999. [Online]. Available: http://www.elsaker-
The neutral voltage in normal operating conditions was about hetsverket.se/Global/F%c3%b6reskrifter/%c3%84ldre%20f%c3%b-
6reskrifter/1999-5.pdf
1363 V with resonance tuning of the coil (83 A). Cable current [2] Earthing of Power Installations Exceeding 1 kV a.c., European Stan-
transformers with a transformation ratio of 100/1 were avail- dard EN 50522, European Committee for Electrotechnical Standard-
able at the substation. The measurements were made using an ization (CENELEC), Nov. 2010, Anon.
[3] S. Hänninen and M. Lehtonen, “Method for detection and location of
8-channel Yokogawa measuring instrument and a digital four- very high resistive earth faults,” Eur. Trans. Elect. Power Eng., vol. 9,
channel oscilloscope. The sampling frequency was 10 kHz and no. 5, pp. 285–291, 1999.
the length of the recording was 1.5 s. The fault was connected by [4] P. Pakonen, “Detection of incipient tree faults on high voltage covered
conductor lines,” Ph.D. dissertation, Tampere Univ. Technol., Tam-
the switching device situated at the fault location. Two healthy pere, Finland, 2007, Publ. 681.
feeders were also measured and calculated as a reference. Fault [5] V. Leitloff, R. Feuillet, and D. Griffel, “Detection of resistive single-
resistances over 40 k reduced the neutral voltage of the system. phase earth faults in a compensated power-distribution system,” Eur.
Trans. Elect. Power Eng., vol. 7, no. 7, pp. 65–73, 1997.
Table III presents the fault resistances calculated using (21) [6] I. Zamora, A. J. Mazón, K. J. Sagastabeitia, and J. J. Zamora, “New
for one faulty and two healthy feeders. The phase-to-earth sus- method for detecting low current faults in electrical distribution sys-
ceptance of the faulty feeder, healthy Feeder 1, and healthy tems,” IEEE Trans. Power Del., vol. 22, no. 4, pp. 2072–2079, Oct.
2007.
Feeder 2 were , , and , [7] J. J. Zamora, I. Zamora, A. J. Mazón, and K. J. Sagastabeitia, “Optimal
respectively. The term “u” refers to the undercompensated and frequency value to detect low current faults superposing voltage tones,”
“o” to the overcompensated system. IEEE Trans. Power Del., vol. 23, no. 4, pp. 1773–1779, Oct. 2008.
[8] O. Chilard, L. Morel, and D. Renon, “Compensated grounded medium
In all cases up to 240 k , the value calculated for fault re- voltage network protection against resistive phase to ground faults,” in
sistance was obviously the lowest with the faulty feeder. Thus, Proc. CIRED, Nice, France, Jun. 1999, pp. 139–142.
fault indication was feasible up to a fault resistance of 240 k . [9] T. Welfonder, V. Leitloff, R. Feuillet, and S. Vitet, “Location strategies
and evaluation of detection algorithms for earth faults in compensated
The condition for a faulty phase of a compensated system de- MV distribution systems,” IEEE Trans. Power Del., vol. 15, no. 4, pp.
fined in Section V-B was valid with every case. Phase angles 1121–1128, Oct. 2000.
of the phase-to-earth voltages of the healthy phases are outside [10] K. J. Sagastabeitia, I. Zamora, A. J. Mazón, Z. Aginako, and
G. Buigues, “Phase asymmetry: A new parameter for detecting
the defined region. Thus, reliable indication of the faulty phase single-phase earth faults in compensated MV networks,” IEEE Trans.
could also be achieved. Power Del., vol. 26, no. 4, pp. 2251–2258, Oct. 2011.
This article has been accepted for inclusion in a future issue of this journal. Content is final as presented, with the exception of pagination.
[11] M. Michalik, W. Rebizant, M. Lukowicz, S.-J. Lee, and S.-H. Kang, [20] V. Leitloff, J. Bergeal, R. Feuillet, and L. Pierrat, “Messung der Param-
“High impedance fault detection in distribution networks with use of eter eines kompensierten Netzes durch Injektion eines Stromes in den
wavelet based algorithm,” IEEE Trans. Power Del., vol. 21, no. 4, pp. Sternpunkt (Measurement of parameters of compensated network by
1793–1802, Oct. 2006. injecting current in neutral point),” (in German) Elektrizitätswirtschaft,
[12] T. M. Lai, L. A. Snider, E. Lo, and D. Sutano, “High impedance vol. 93, no. 22, pp. 1371–1376, 1994.
fault detection using discrete wavelet transform and frequency range [21] J. Valtari and P. Verho, “Requirements and proposed solutions for fu-
and RMS conversion,” IEEE Trans. Power Del., vol. 20, no. 1, pp. ture smart distribution substations,” J. Energy Power Eng., vol. 5, no.
397–407, Jan. 2005. 8, pp. 766–775, 2011.
[13] B. M. Aucoin and R. H. Jones, “High impedance fault detection imple- [22] A. Nikander, J. Valtari, O. Raipala, and E. Kettunen, “Verifying the
mentation issues,” IEEE Trans. Power Del., vol. 11, no. 1, pp. 139–148, indication method for high-resistance earth faults implemented in
Jan. 1996. centralized protection system,” presented at the CIRED, Stockholm,
[14] C. L. Benner and B. D. Russel, “Practical high-impedance fault detec- Sweden, Jun. 2013.
tion on distribution feeders,” IEEE Trans. Ind. Appl., vol. 33, no. 3, pp.
635–640, May/Jun. 1997.
[15] K. Y. Lien, S. L. Chen, C. J. Liao, T. Y. Guo, T. M. Lin, and J. S. Ari Nikander (M'13) received the M.Sc., Licentiate of Technology, and
Shen, “Energy variance criterion and threshold tuning scheme for high- Dr.Tech. degrees in electrical engineering from Tampere University of Tech-
impedance fault detection,” IEEE Trans. Power Del., vol. 14, no. 3, pp. nology, Tampere, Finland, in 1991, 1998, and 2002, respectively.
810–817, Jul. 1999. Currently, he is a Senior Researcher in the Department of Electrical Engi-
[16] B. D. Russell, K. Mehta, and R. P. Chinchali, “An arcing fault detec- neering, Tampere University of Technology. His main interests focus on the
tion technique using low frequency current components—Performance protection, fault location, and earth fault issues of electricity distribution.
evaluation using recorded field data,” IEEE Trans. Power Del., vol. 3,
no. 4, pp. 1493–1500, Oct. 1988.
[17] P. R. S. Jota and F. G. Jota, “Fuzzy detection of high impedance faults
in radial distribution feeders,” Elect. Power Syst. Res., vol. 49, pp. Pertti Järventausta (M'12) received the M.Sc. and Licentiate of Technology
169–174, 1999. degrees in electrical engineering from Tampere University of Technology, Tam-
[18] B. D. Russell and C. L. Benner, “Arcing fault detection for distribu- pere, Finland, in 1990 and 1992, respectively, and the Dr.Tech. degree in elec-
tion feeders: Security assessment in long term field trials,” IEEE Trans. trical engineering from Lappeenranta University of Technology, Lappeenranta,
Power Del., vol. 10, no. 2, pp. 676–683, Apr. 1995. Finland, in 1995.
[19] V. Leitloff, L. Pierrat, and R. Feuillet, “Study of the neutral-to-ground Currently, he is a Professor with the Department of Electrical Engineering
voltage in a compensated power system,” Eur. Trans. Elect. Power of Tampere University of Technology. His main interests focus on electricity
Eng., vol. 4, no. 2, pp. 145–153, 1994. distribution and the electricity market.