Professional Documents
Culture Documents
High
Resolution
SEF Protection
on the
Overhead
Distribution
Network
Sensitive Earth Fault (SEF) protection has been omnipresent in the Australian electrical
distribution network for many years. SEF Protection aims to address outlying fault conditions
that are not covered by conventional Overcurrent and Earth Fault (EF) protection relaying
techniques on distribution feeders.
A
ccordingly, SEF is often cited as the method for improving alone does not achieve practical improvement from a safety and
safety by detecting high impedance faults, progressive economic standpoint[4].
insulation failure, or even for fire mitigation purposes. Fortunately, modern distribution protection devices such as NOJA
SEF Protection and its implementation varies significantly across Power OSM Reclosers are capable of achieving SEF protection at
earthing schemes, and the ubiquitous Australian technique of 200 mA of primary current on a distribution network, through
resistance earthing using Neutral Earthing Resistors (NERs) may a combination of specialist sensor hardware, extensive system
facilitate the usage of SEF to detect failing insulators, but from a fire calibration and SEF protection algorithms honed from experience
mitigation point of view, the existing network settings of around 4 in European isolated/resonant earthed distribution networks. A
to 5 amps for a few seconds provides zero benefit [1]–[3]. shift towards high sensitivity without compromise on reliability is
The immediate insight then becomes a push to reduce SEF pickup possible today, with proven field installations in Australian networks
levels, but the existing technology is not necessarily designed to operating at 400 mA primary current pickup with effective rejection
facilitate accuracy at lower current measurement levels. Reducing of capacitive network effects.
SEF pickup levels may introduce additional spurious tripping, and
From an SEF Protection perspective, it is evident that while Isolated Figure 4 A Resonant Earthed Network with an Earth Fault [9]
Neutral and Resonant Earthed neutral networks reduce the earth
fault magnitude, they also introduce great challenges with detecting Figure 4 shows the fault case under a resonant earthed network.
faults. Aside from limiting fault currents to below the 0.1 A2s limit The capacitive current is cancelled by the inductive current. In the
required to meet fire mitigation practices, detecting these currents resonant earthed network, a neutral resistor is often connected in
requires entirely different algorithms to the systems designed to parallel to the Arc Suppression Coil (ASC) to provide some level of
work on large earth fault currents present in resistive and solid resistive current for earth faults, for protection purposes.
earthed networks. Under these conditions, conventional SEF protection based on
torque angles, Relay Characteristic Angles and phasor magnitudes
SEF PROTECTION become ineffective, as the system is not designed to handle such
Figure 3 demonstrates the typical behavior of a NER earthed network low currents. This presents a great challenge to network operator.
under a single line to ground earth fault. The faulted phase draws If devices such as reclosers, designed to segment the network, do
real power to the site, shown by the dark arrow. This is augmented not have algorithms designed to work with such low earth fault
by capacitive current, which is the capacitance of the lines over the currents, isolating faults becomes a significantly challenging task.
earth [6]. The amount of capacitive charge available is a function Accordingly, a new method for detecting genuine downstream
of the network topography and size, but generally, the longer the faults is required – the Watt metric, or Cos φ method.
lines, the more capacitive current will be present.
SEF PROTECTION TECHNIQUES FOR ISOLATED
NEUTRAL OR RESONANT EARTHING NETWORKS –
WATT METRIC/ COS Ф METHOD
Conventional SEF protection will first react to the magnitude of
the residual current and then attempt to ascertain direction to
determine whether the fault is downstream or not. When it comes to
detecting high impedance faults however, particularly in capacitive
environments, the capacitive magnitude will be far higher than the
resistive current, and accordingly using the “earth fault protection
set to low operating points” method does not provide sufficient
selectivity at low current.
Rather than simply acting on the phasor magnitude of the
Figure 3 A Resistive Earthed (NER) network with an Earth Fault [9] residual current, watt metric or cos φ sensitive earth fault
protection evaluates the phasor angle between the Neutral Voltage
Displacement and the measured residual current, taking IResidual cos fault current is to determine the flow direction of earth fault current.
φ to derive the resistive current. The protection then acts on this The watt metric method makes this innate to the protection itself,
derived quantity, rather than simply operating on the magnitude of providing equivalent functionality to conventional directional SEF at
the current. higher currents, but then also providing selectivity at lower currents
In practice, this angular shift is very low. A faulted feeder on as the resistive component is derived from the residual.
a resonant earthed network would have around 93 degrees In the context of distribution reclosers, when the watt metric
of shift, while the un-faulted phases would have 90 degrees (purely method is combined with a fully calibrated system and CT’s such as
capacitive)[7]. Even at 5% resistive current, Cos Ф SEF provides the OSM Reclosers, it is possible to reliably configure SEF protection
a method for differentiating between resistive currents and at current levels far lower than traditional levels.
fault currents. Conventional GOSS metal CT’s are often insufficient for such
applications, where the low currents sit below the CT energisation
level. Hybrid CT’s with a mixture of metals, such as the system in the
NOJA Power OSM Recloser are essential to provide accuracy at such
low levels of current.
The use of Rogowski coils is also generally not feasible for such
low current levels, as the requirement for an intermediary integrating
op-amp between the sensor and relay introduces noise that distorts
the performance of the system at such high resolution precision
applications [8].
The remaining limitation in application is the balance of the
distribution network which can be addressed with feeder balancing
and controllable capacitor balancing units, or CBUs.
CONCLUSION
Figure 5 Detection and Non – Detection Zones [7],
Watt metric Cos SEF Protection SEF Protection in the distribution network is undergoing a
renaissance of performance improvements. As fire mitigation
NOJA Power’s OSM Reclosers have the unique capacity to operate derived from protection devices can only be achieved by setting SEF
on such low currents, enabled by the combination of proprietary CT below 1 ampere, new algorithms and systems are required to be
design, end to end system calibration and the incorporation of these able to deliver selectivity and sensitivity at these low current levels.
advanced earth fault algorithms to provide sensitivity and selectivity NOJA Power’s OSM Recloser has been deployed in networks across
at this level of fault current. This implementation has been field the world with SEF levels below 1 ampere, providing reliable fault
proved at 400mA primary current pickup in Australian networks. detection in a network application that most other recloser products
simply cannot operate. This is enabled by the combination of high
performance CTs in a matched configuration, end to end factory
calibration and the application of watt metric cos Ф Sensitive Earth
Fault protection algorithms. T&D
References
1] T. Marxsen, ‘Prevention of Bushfires from Powerline
Vegetation Faults’, T&D Magazine Australia, Jun. 2018.
[2] T. Marxsen, ‘Vegetation Conduction Ignition Tests Final
Report’, Marxsen Consulting, 1, Jun. 2015.
[3] T. Marxsen, ‘New Research on Bushfire Ignition from Rural
Powerlines’, T&D Magazine Australia, Feb. 2012.
[4] Industry Safety Steering Committee of NSW, ‘ISSC 33
Guideline for Network Configuration During High Bush Fire
Risk Days’, Dec. 2010.
[5] A. Cerretti, F. M. Gatta, A. Geri, S. Lauria, M. Maccioni,
and G. Valtorta, ‘Ground Fault Temporary Overvoltages in
MV Networks: Evaluation and Experimental Tests’, IEEE
Trans. Power Deliv., vol. 27, no. 3, pp. 1592–1600, Jul.
2012, doi: 10.1109/TPWRD.2012.2192456.
[6] P. Colella et al., ‘Currents Distribution During a Fault in
an MV Network: Methods and Measurements’, IEEE Trans.
Ind. Appl., vol. 52, no. 6, pp. 4585–4593, Nov. 2016, doi:
10.1109/TIA.2016.2600672.
Figure 6 A NOJA Power OSM Recloser installed on a Resonant [7] G. Kaufmann and R. Vaitkevičius, ‘Sensitive ground fault
Earthed Network with 400 mA SEF Primary Pickup Configured detection in compensated systems (arc suppression coil).
What is influencing the sensitivity?’, J. Eng., vol. 2018, no.
THE APPLICABILITY OF ADVANCED SEF PROTECTION 15, pp. 971–977, 2018, doi: 10.1049/joe.2018.0147.
TO RESISTIVE NETWORKS [8] D. C. R. Hewson, ‘Application Notes’, p. 17, 2002.
Watt metric or Cos Ф EF protection techniques also has applicability [9] Prévé, C., ©2006 ISTE, “Protection of Electrical Networks”,
for resistive networks. The key to selectivity at low levels of earth ISBN-13: 978-1-905209-06-4