You are on page 1of 6

Universal Transmission Line Protection Intelligent Electronic Devices

A.P. Apostolov, Senior Member, IEEE


ALSTOM T&D
Los Angeles, CA, 90064USA

Abstract: The paper addresses the concept of a Universal Overhead lines, ranging from 12 kV distribution lines to
Transmission Line Protection IED designed to meet the complex 500kV transmission lines, are the most fault susceptible
requirements for primary and backup protection under different equipment in a modern power system. It is therefore
fault conditions and power system configurations. It has a modular essential that the protection associated with them provides
architecture in order to allow adaptation of the hardware and
software to different transmission line protection configurations.
secure and reliable operation for different abnormal system
Multiple operating principles are included and can be combined in conditions.
order to ensure correct operation for any condition. The majority of faults on overhead lines are transient or
The functioning of the Universal Transmission Line Protection as a semi-permanent in nature. Multi-shot autoreclose cycles are
communications based unit type protection using differential or therefore commonly used in conjunction with instantaneous
directional comparison mode is described. Digital communications tripping elements to increase system availability. For
based permissive or blocking schemes are addressed as well. permanent faults it is essential that only the faulted section
Local and remote backup operation of distance, high and low set of system is isolated. As such, high speed, discriminative
overcurrent, overload and broken conductor detection functions are fault clearance is often a fundamental requirement of any
presented.
The application of the Universal Transmission Line Protection to
protection scheme on a distribution network.
two and three terminal lines, mutually coupled lines, transmission The requirements for a transmission network must also take
line - transformer circuits or ring-bus and breaker and a half- into account system stability. Where systems are not highly
configurations are discussed. interconnected the use of single phase tripping and high
Advanced Breaker Failure Protection and Reclosing with speed autoreclosure is often required. This in turn dictates
Synchronism Check, as well as Programmable Scheme Logic, the need for very high speed protection to reduce overall
Metering, Recording and Monitoring functions are described later fault clearance times.
in the paper. Many line configurations exist which need to be addressed.
Transmission applications may typically consist of 2 or 3
terminal applications, possibly fed from breaker and a half
Keywords: Transmission Line Protection, Line Differential
or ring bus arrangements. Lower voltage applications may
Protection, Distance Protection, Multifunctional
again be 2 or 3 terminal configurations with the added
Microprocessor Relays
complications of in zone transformers or small teed load
transformers.
I. INTRODUCTION
Fault sensitivity is an issue common to all voltage levels. For
transmission systems tower footing resistance can be high.
Intelligent (microprocessor-based) Electronic Devices (IED)
Also high resistance faults may be prevalent, particularly
for data acquisition, protection, metering, and control have
where lines pass over sandy or rocky terrain. Fast,
gained widespread acceptance and are recognized as
discriminative fault clearance may still be required for such
essential to the efficient and cost-effective operation and
fault conditions.
management of substations.
The effect of fault resistance is more pronounced on lower
Transmission line protection is an extremely important and
voltage systems, resulting in potentially lower fault currents,
very complex field. Protection IEDs designed to protect
which in turn increases the difficulty in their detection. In
transmission line should meet many different requirements
addition, many distribution systems use grounding
in order to provide primary and backup protection and at the
arrangements designed to limit the passage of ground fault
same time ensure correct operation for different fault and
current. Methods such as resistance grounding, Petersen Coil
other abnormal power system conditions.
grounding or insulated systems make the detection of ground
faults difficult. Special protection requirements are often
used to overcome these problems.
Charging current may also adversely affect protection. This
is a problem particularly with cables and long transmission
lines. Both the initial inrush and steady state charging
current must not cause relay mal-operation and preferably
should not compromise protection performance.
Physical distance must be taken into account. Some EHV
transmission lines can be up to several hundred miles in
length. If high speed, discriminative protection is to be
applied, it will be necessary to transfer information between
line ends.

0-7803-7285-9/01/$17.00 (C) 2001 IEEE 693


0-7803-7287-5/01/$17.00 (C) 2001 IEEE
It is obvious that the security of communications between protection element for the relay. Provides high speed,
the protection devices at each end of the line is extremely discriminative protection for all fault types.
important and that some forms of protection must be • Transformer inrush restraint and ratio/vector
available in the event of loss of this signal. compensation – Allows the differential elements to be
Back-up protection is also an important feature of any applied on transformer feeders where the transformer
protection scheme. In the event of equipment failure, such as forms part of the protected zone.
communications equipment or switchgear, for example, it is • Distance protection – 3 zones of distance protection
necessary to provide alternative forms of fault clearance. It providing back-up to the current differential.
is desirable to provide back-up protection which can operate • Phase fault overcurrent protection – Four stage
with minimum time delay and yet discriminate with both the directional/non-directional back- up protection.
main protection and protection elsewhere on the system. • Ground Fault Protection – Four stage directional backup
protection.
II. TRANSMISSION LINE PROTECTION RELAY • Sensitive ground fault protection – Four stage
FUNCTIONS directional/non-directional backup protection. Can be
configured to provide ground fault protection on arc
A multifunctional transmission line protection relay should suppression coil grounded systems.
provide a highly selective relaying system that is immune • Thermal protection – 2 stage thermal protection for
from changes in the surrounding power system. Applications line/cable/transformer.
to two and three terminal lines, cables and transformer
• Broken conductor protection – To detect open circuit
feeders should also be supported. The relay must provide
faults
adequate protection with or without a communications
• Stub bus protection: Applied for 1 1 /2 switched and
channel to the remote end of the transmission line. The
ring bus arrangements.
integration of many functions allows application to a wide
range of electrical power systems, providing both local and • Circuit breaker fail protection – Two stage breaker fail
remote backup protection. protection
Most of the time state-of-the-art protection IEDs are • Autoreclose facility: Integral three phase or single/three
performing as universal metering, control and recording phase multi-shot autoreclose
devices. They provide multiple communications interfaces, • Check synchronism facility – To provide a synchronism
that allow them to become the servers in an integrated check function for manual or automatic reclosure of
substation automation system over a substation local area circuit breakers.
network. • Direct/permissive inter-trip – Independent inter-tripping
One of the main goals in today's extremely competitive facility using the relay’s protection communications
utility environment, is to switch from scheduled to event channels.
driven maintenance. A universal protection IED can • Dual redundant communications – Option for dual
significantly help achieving this goal, by providing tools communications channels to provide a high degree of
monitoring substation primary equipment and indicating to security.
the maintenance teams when they need to take specific • Protection communications supervision – To detect
actions. failure of protection communications and enable
All of the above listed requirements are taken in remedial action to be taken, ie. switch in communication
consideration in the concept of a Universal Transmission independent back-up protections.
Line Protection IED. • Voltage transformer supervision – To prevent
maloperation of voltage dependent protection elements
Universal Transmission Line Protection (UTLP) IED upon loss of a VT input signal.
The universal IED [1] has been designed for the protection • Programmable scheme logic – Allowing user defined
of a wide range of overhead lines and underground cables protection and control logic to suit particular customer
for subtransmission to transmission voltage levels. It also applications.
includes a comprehensive range of non-protection features to
meet the requirements for substation and power system Non-Protection Features
integration and aid the user with power system diagnosis and Below is a summary of the relay non-protection features.
fault analysis. All these features can be accessed locally, • Local/remote measurements – Various measurement
through the substation LAN or remotely from one of the values from the local and remote line ends available for
relays serial communications ports. display on the relay or accessed from the serial
communications.
Protection Features • Fault/event/disturbance records – Available from the
The protection features of each model are summarized serial communications or on the relay display. (Fault
below: and event records only).
• Phase current differential protection – Phase segregated • Fault locator
restrained differential protection provides the main

0-7803-7285-9/01/$17.00 (C) 2001 IEEE 694


0-7803-7287-5/01/$17.00 (C) 2001 IEEE
• Real time clock/time synchronization through IRIG-B Where transformer inrush restraint is used, the resultant
input. second harmonic current produced from CT saturation may
• Four setting groups – Independent setting groups to cause slow relay operation. The high set element will be
adapt for alternative power system arrangements or automatically enabled when inrush restraint is enabled,
customer specific applications. otherwise it is not operational. The high set element should
• Circuit breaker state monitoring – Provides indication of be set in excess of 35% of the magnetizing inrush level.
discrepancy between circuit breaker auxiliary contacts. To calculate differential current between line ends it is
• Circuit breaker control: Control of the circuit breaker necessary that the current samples from each end are taken
can be achieved either locally via the user interface or at the same moment in time. This can be achieved by time
remotely. synchronizing the sampling, or alternatively, by the
• Circuit breaker condition monitoring – Provides continuous calculation of the propagation delay between line
records/alarm outputs regarding the number of CB ends.
operations, sum of the interrupted current and the
breaker operating time.
• Commissioning test facilities.
• Remote serial communications – To allow remote
access to the relays.
• Continuous self monitoring – Power on diagnostics and
self checking routines to provide maximum relay
reliability and availability.

III. SEGREGATED PHASE CURRENT DIFFERENTIAL


PROTECTION

The primary protection element of the relay is segregated


phase current differential protection. This technique involves
the comparison of the currents at each line terminal. A
communications path is therefore an essential requirement of
any such scheme. The relays utilize a 56/64 Kbits/s digital
communications system either for direct optical connection
between multiple line ends, or via a multiplexed link.
The basic operating principle of differential protection is to
calculate the difference between the currents entering and
leaving a protected zone. The protection operates when this
difference exceeds a set threshold. Fig. 1 Restrained characteristic for a segregated phase
Differential currents may also be generated during external differential protection function with transient shift
fault conditions due to CT saturation. To provide stability
for through fault conditions, the relay adopts a restraining Note that the sampling instants at the two ends will not, in
technique. This method effectively raises the setting of the general, be coincidental or of a fixed relationship, due to
relay in proportion to the value of through fault current to slight drifts in sampling frequencies.
prevent relay mal-operation. The relay assumes that the transmit and receive channels
Figure 1 shows the operating characteristics of the follow the same path and so have the same propagation
segregated phase differential element. delay time. This time (based on the times shown in Fig. 2)
The differential current is calculated as the vector can therefore be calculated as:
summation of the currents entering the protected zone. The
restrain current is the average of the measured current at tp1 = tp2 = 1 /2(tA* – tA1 – td) (1)
each line end. It is found by the scalar sum of the current at
each terminal, divided by two. The propagation delay time is measured for each received
Each of these calculations is done on a phase by phase basis. sample and this can be used to monitor any change on the
The level of restrain used for each element is the highest of communication link.
the three calculated for optimum stability. To calculate the differential and restrain currents, the vector
When a trip is issued by the differential element, in addition samples at each line end must correspond to the same point
to tripping the local breaker, the relay will send a differential in time. It is necessary therefore to time align the received
inter-trip signal to the remote terminals. This will ensure tB3* data to tA3 and tA4. This can be achieved by rotating
tripping of all ends of the protected line, even for marginal the received current vector by an angle corresponding to the
fault conditions. time difference between tB3* and tA3 (and tA4). The
An unrestrained differential high set element is designed to current vectors of the three phases need to be time aligned
provide high speed operation in the event of CT saturation. separately.

0-7803-7285-9/01/$17.00 (C) 2001 IEEE 695


0-7803-7287-5/01/$17.00 (C) 2001 IEEE
to be taken into account. These include compensation for
any phase shift across the transformer, possible unbalance of
signals from current transformers either side of windings,
and the effects of the variety of grounding and winding
arrangements. In addition to these factors, which can be
compensated for by correct application of the relay, the
effects of normal system conditions on relay operation must
also be considered. The differential element must restrain for
system conditions which could result in maloperation of the
relay, such as high levels of magnetizing current during
inrush conditions.
In traditional transformer feeder differential schemes, the
requirements for phase and ratio correction were met by
correct selection of line current transformers. Software
interposing CTs are provided within the relay which can
give the required compensation. The advantage of having
replica interposing CTs is that it gives the relays the
flexibility to compensate for line CTs connected in either
star or delta, as well as a variety of system grounding
arrangements. The relays also include a magnetizing inrush
restraint facility.
The magnetizing inrush current to a transformer appears as a
large operating signal to the differential protection. Special
measures are taken with the relay design to ensure that no
Fig. 2 Time synchronization at two ends of the line
maloperation occurs during inrush.
Figure 3 shows a transformer magnetizing characteristic. To
The charging current of a line or cable will be seen as
minimize material costs, weight and size, transformers are
differential current. If this current is of a sufficiently high
generally operated near to the ‘knee point’ of the
magnitude, as is the case for cables and long transmission
magnetizing characteristic. Consequently, only a small
lines, then relay maloperation can occur. Two issues are
increase in core flux above normal operating levels will
apparent with charging current; the first being inrush during
result in a high magnetizing current.
line energization and the second being steady state charging
Under normal steady state conditions, the magnetizing
current.
current associated with the operating flux level is relatively
Inrush charging current is predominately high order
small (usually less than 1% of rated current).
harmonics (9 th and 11 th for example). The Fourier filtering
However, if a transformer winding is energized at a voltage
used by the relays will remove these frequency components
zero, with no remnant flux, the flux level during the first
and hence provide stability.
voltage cycle (2 x normal max. flux) will result in core
Steady state charging current is nominally at fundamental
saturation and in a high, non-sinusoidal magnetizing current
frequency and hence may cause relay maloperation.
waveform.
To overcome this problem the relays require a feature to
extract the charging current from the measured current
before the differential quantity is calculated.
The line charging current at a particular location is equal to
the voltage at that location multiplied by the line positive
sequence susceptance. It is therefore possible for the relays
at each line end to calculate the respective line charging
currents and compensate accordingly.
The differential current (Id) can be calculated as follows:
Id = IL + IR – (jVLBS/2) – (jVRBS/2) (2)
Id = IL– (jVLBS/2) + IR – (jVRBS/2) (3)
Id = Local relay current + remote relay current (4)
where BS is the line positive sequence susceptance.
This feature can be selectively enabled or disabled. If
selected, the normal phase current data in the protection
message is replaced by I – (jVBS/2)}.

Protection of Line-Transformer Circuits


In applying the well established principles of differential
Fig. 3 Transformer inrush current
protection to transformers, a variety of considerations have

0-7803-7285-9/01/$17.00 (C) 2001 IEEE 696


0-7803-7287-5/01/$17.00 (C) 2001 IEEE
The magnitude and duration of magnetizing inrush current
waveforms are dependent upon a number of factors, such as
transformer design, size, system fault level, point on wave of
switching, number of banked transformers, etc. Fig. 3 shows
typical transformer magnetizing currents for steady state and
inrush conditions. The magnetizing inrush current contains a
high percentage of second harmonic.
To ensure correct operation of the differential element, it is
important that under load and through fault conditions, the
currents into the differential element of the relay balance. In
many cases, the HV and LV current transformer primary
ratings will not exactly match the transformer winding rated
currents. Ratio correction factors are therefore provided. To
minimize unbalance due to tap changer operation, current
inputs to the differential element should be matched for the
mid-tap position.
To compensate for any phase shift between two windings of
a transformer, it is necessary to provide phase correction. Fig. 4 Distance characteristic
This was traditionally provided by the appropriate delta
connection of main line CTs. In the universal transmission All ground fault protection elements are also quadrilateral
line protection IED phase correction is provided via software shaped, and are directionalized as per the phase fault
interposing CTs. In addition to compensating for the phase elements. Residual compensation is used to ensure the
shift of the protected transformer, it is also necessary to correct reach for the ground fault elements. The residual
mimic the distribution of primary zero sequence current in compensation factor is applied to the respective phase fault
the protection scheme. reaches in order to obtain the ground fault characteristics.
The filtering of zero sequence current has traditionally been Operation of the power swing blocking element is menu
provided by appropriate delta connection of main line CT selectable to block the operation of all of the distance zones
secondary windings. Zero sequence current filtering is or to allow tripping. Power swing detection uses an
automatically implemented in software when a delta impedance band, which surrounds the entire phase fault trip
connection is called up for a software interposing CT. characteristic.
Since in today's dynamic utility environment it is possible to
reconfigure the transmission line by adding another terminal Thermal Overload Protection
in order to connect new generators or load, the relays should Thermal overload protection can be used to prevent
allow easy modification of the communications based electrical equipment from operating at temperatures in
protection scheme as well. They can be configured for the excess of the designed maximum withstand. Prolonged
protection of two or three terminal lines. overloading causes excessive heating, which may result in
premature aging of the insulation, or in extreme cases,
IV. BACKUP PROTECTION FUNCTIONS insulation failure.
The relay incorporates a current based thermal replica, using
Differential protection provides high speed, discriminative load current to model heating and cooling of the protected
protection of an item of plant, with relatively few application primary power system equipment. The element can be set
problems. One disadvantage of a differential scheme, with both alarm and trip stages.
however, is the lack of inherent back-up protection. For this The thermal time characteristic used in the relay is therefore
reason, the UTLP relays include various forms of integrated based on current squared, integrated over time. The relay
back-up protection. automatically uses the largest phase current for input to the
Distance Protection thermal model.
One of the back-up protections provided by the relays is A single or two time constants model can be used. This
distance protection. It can be selectively enabled or disabled. characteristic is used to protect oil-filled transformers with
It is also possible to set the relay such that the distance natural air cooling. The thermal model is similar to that with
protection is only enabled upon detection of a failure of the the single time constant, except that two time constants must
protection communications channel being used by the be set. The thermal curve is defined as:
differential elements. This can be set on a per Zone basis.
The distance elements can also be configured to initiate an 0.4 e (–t/τ1) + 0.6 e(–t/τ2) = (I2 – (k.IFLC)2 ) / (I2 – IP2 ) (5)
intertrip to the remote terminal. All phase and ground fault
protection elements are quadrilateral shaped, and are where:
directionalized as follows: τ1 = Heating and cooling time constant of the transformer
• Zones 1 and 2 – Directional forward zones. windings;
• Zone 3 – Directional reverse zone. τ2 = Heating and cooling time constant for the insulating oil.

0-7803-7285-9/01/$17.00 (C) 2001 IEEE 697


0-7803-7287-5/01/$17.00 (C) 2001 IEEE
Overall, the dual time constant characteristic provided However, they will produce an unbalance and a resultant
within the relay serves to protect the winding insulation from level of negative sequence current, which can be detected.
aging, and to minimize gas production by overheated oil. On a lightly loaded line, the negative sequence current
resulting from a series fault condition may be very close to,
Circuit Breaker Fail Protection or less than, the full load steady state unbalance arising from
Following inception of a fault one or more main protection CT errors, load unbalance etc. A negative sequence element
devices will operate and issue a trip output to the circuit therefore would not operate at low load levels.
breaker(s) associated with the faulted circuit. The relay incorporates an element which measures the ratio
Operation of the circuit breaker is essential to isolate the of negative to positive phase sequence current (I2/I1). This
fault, and prevent damage / further damage to the power will be affected to a lesser extent than the measurement of
system. For transmission/sub-transmission systems, slow negative sequence current alone, since the ratio is
fault clearance can also threaten system stability. It is approximately constant with variations in load current.
therefore common practice to install circuit breaker failure Hence, a more sensitive setting may be achieved.
protection, which monitors that the circuit breaker has
opened within a reasonable time. If the fault current has not Protection and Control Signaling
been interrupted following a set time delay from circuit The relays using a digital communications channel can be
breaker trip initiation, breaker failure protection will operate. used for sending of direct, permissive, blocking or other
A two timer protection scheme is available. The first timer is required protection and control signalls . Upon receipt of this
used to route a trip to a second trip circuit of the same circuit message the remote relay will operate a user specified output
breaker. This requires duplicated circuit breaker trip coils, contact or can be used in a user defined programmable
and is known as re-tripping. Should re-tripping fail to open scheme logic.
the circuit breaker, a back-trip may be issued following an
additional time delay. V. CONCLUSIONS
It is common practice to use low set undercurrent elements
in protection relays to indicate that circuit breaker poles have Modern power systems require the development of
interrupted the fault or load current, as required. This covers multifunctional transmission line protection IEDs with
the following situations: numerous protection and non-protection functions.
• Where circuit breaker auxiliary contacts are defective, A universal transmission line protection relay with
or cannot be relied upon to definitely indicate that the segregated phase differential protection as the main function
breaker has tripped. and multiple backup protection functions, including 3 zone
• Where a circuit breaker has started to open but has distance protection was presented. The paper describes
become jammed. This may result in continued arcing at features allowing the application of the IED to multi-
the primary contacts, with an additional arcing terminal lines, mutual coupled lines, charging current
resistance in the fault current path. Should this compensation, transformer inrush current detection, breaker
resistance severely limit fault current, the initiating and a half and ring bus substation configurations.
protection element may reset. Thus, reset of the element
may not give a reliable indication that the circuit VI. REFERENCE
breaker has opened fully.
For any protection function requiring current to operate, the 1. Technical Guide MiCOM P54x Current Differential
relay uses operation of undercurrent elements to detect that Relays, Vol. 1, TG8613A, Stafford, UK, 1999
the necessary circuit breaker poles have tripped and reset the
CB fail timers. However, the undercurrent elements may not VII. BIOGRAPHY
be reliable methods of resetting circuit breaker fail in all
applications, for example if an overvoltage protection Alexander Apostolov received a MS degree in Electrical Engineering, MS in
Applied Mathematics and Ph.D. from the Technical University in Sofia,
operates with very light load of the transmission line. Bulgaria. He has worked for fourteen years in the Protection &Control Section
Resetting of the breaker failure protection is possible from a of Energoproject Research and Design Institute, Sofia, Bulgaria.
breaker open indication (from the relay’s pole dead logic) or From 1990-94 he was Lead Engineer in the Protection Engineering Group ,
from a protection reset. In these cases resetting is only New York State Electric & Gas where he worked on the protection of the six-
phase line, application of microprocessor relays, programmable logic and
allowed provided the undercurrent elements have also reset. artificial intelligence in protection. 1994-95 he was Manager of Relay
Applications Engineering at Rochester - Integrated Systems Division. 1995-96
Broken Conductor Detection he was Principal Engineer at Tasnet.
Another type of unbalanced fault which can occur on the He is presently Marketing Strategies Manager for ALSTOM T&D. He is a
Senior Member of IEEE and Member of the Power Systems Relaying
system is the series or open circuit fault. These can arise Committee and Substations Subcommittee. He serves on several IEEE PES
from broken conductors, maloperation of single phase Working Groups and is Chairman of Working Group C3: New Technology
switchgear, or the operation of fuses. Series faults will not Related to Power Systems Protection and Working Group C9: Guide for
cause an increase in phase current on the system and hence Abnormal Frequency Load Shedding and Restoration.
He is member of IEC TC57 and CIGRE WG 34.01.He holds three patents and
are not readily detectable by standard overcurrent relays. has authored more than 90 technical papers.

0-7803-7285-9/01/$17.00 (C) 2001 IEEE 698


0-7803-7287-5/01/$17.00 (C) 2001 IEEE

You might also like