You are on page 1of 6

High Impedance Fault Detection In Distribution System Using Wavelet

Transform
V. Torres Garcia1, H. Ruiz Paredes1
1
Electrical Engineering Department, Technological Institute of Morelia, Mexico
Phone (443) 312-1570 Fax (443) 345-6789 E-mail: vtg_1982@hotmail.com

Abstract –– A High Impedance Fault (HIF) is generated II. TIPYCAL CURRENT VALUES
when an overhead power line physically breaks and falls to the
ground or when two phases make contact with a solid The conventional overcurrent protection devices in
grounding. Such faults are difficult to detect in Electrical
electric distribution systems have not been able to detect
Distribution Systems and often draw small currents which
cannot be detected by conventional protection. Furthermore, high impedance to ground is the current level. According to
arcing accompanies high impedance fault, resulting in a fire specialized literature the main characteristics of HIF is the
hazard, damage to electrical devices and risk to human life. low magnitude of current. Table I shows typical current
This paper presents a technique based on Discrete Wavelet levels for different surfaces.
Transform (DWT) for high impedance fault detection in power
distribution system. The algorithm is based on a windowing
approach of DWT. TABLE I
TYPE OF SURFACES AND CURRENT VALUES AT 12.5 KV
Keywords –– Electric distribution system, Discrete wavelet
transform, High impedance fault, Detail coefficients.
Surface Current (A)
Dry asphalt 0
I. INTRODUCTION Dry sand 0
Concrete(non-reinforced) 0
A High impedance fault occurs when an energized
conductor of a primary feeder makes contact with the Wet sand 15
ground or any other grounded objet, either by the network Dry sod 20
design or characteristics of the involved object. These faults Dry grass 25
generate a risk of fires and endanger life through the
Wet sod 40
possibility of electric shock. Such faults are undetectable by
conventional overcurrent devices. According to the IEEE Wet grass 50
PSRC the high impedance faults as those that do not Concrete (reinforced) 75
produce enough current to be detected reliably by
conventional devices such as relays and fuses [1].

Since the early seventies, it has been researched and As is shown in Table I the currents level vary from zero
proposed several algorithms and techniques for the detection to 75 amperes at 12.5 kV class feeders and depending of
of such faults, including the application of harmonics [2, 3, surface type [12]. In the case of phase conductors to ground
4], Kalman filtering method [5], artificial neural networks where the soil is a major source of resistivity, the ground
[6,7], wavelet transform [8,9,10,11]. Today, only a few resistance will be considered as the fault resistance.
commercial protection devices, i.e: the GE F60 DFM, SEL
451, ABB’s REF550, claim that they perform high The fault resistance is a function of the total surface area
impedance fault detection in overhead lines, with a good of the conductor in contact with environment. Generally, the
success. conductivity of the ground increases with increasing
moisture content, temperature and mineral content. It is
This paper shows the potential of discrete wavelet necessary to validate the table with on-site experiments.
transform (DWT) in digital signal processing to detect High
Impedance Faults (HIF). The methodology is based on
multirresolution analysis of DWT and results are presented
in a windowing approach. Also data obtained from a field
test are shown.

Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 27,2022 at 09:56:37 UTC from IEEE Xplore. Restrictions apply.
III. FIELD TEST The Fig. 3 presents the first cycles of high impedance
fault current and voltage as a reference.
To analyze the behavior of the HIF, the CFE DCO
conducted field test. Data records were obtained from this 1.5
4
x 10

study. It was reproduced the fall of a cover 13.8 kV feeder Voltage


Current*1e3
on dry grass, as is shown in Fig. 1. 1

13.8 kV
0.5

Voltage (V)
Current (A)
ACSR 3/0 Cover Conductor 0

RTP RTC -0.5


120:1 10:5
Register -1

-1.5
0.94 0.96 0.98 1 1.02 1.04 1.06 1.08 1.1
time (s)
Fig. 3. Voltage and Current for field test.

In addition Fig. 3 shows the relation between current and


Soil voltage, the current grows up at the first cycles, also it is
Fig. 1. Field test. observed that the waveform of the current is asymmetric and
an important feature for study is that the current is in phase
Fig. 1 corresponds to the fall of a cover conductor, with the voltage due a mainly resistive behavior.
phenomenon which caused concern for dealing with high
impedance faults mainly because the overcurrent protection The Fig. 4 shows the voltage-current relationship of the
did not operate. high impedance fault in the first cycles.

The Fig. 2 shows oscillographic data of high impedance


4
x 10
1.5
fault current on dry grass conditions.
1

1
0.5
0.8
Voltage (V)

0.6
0
0.4

0.2
Current (A)

-0.5
0

-0.2 -1
-0.4

-0.6 -1.5
-1 -0.8 -0.6 -0.4 -0.2 0 0.2 0.4 0.6 0.8
-0.8 Current (A)
Fig. 4. Voltage - Current for field test.
-1

1 1.2 1.4 1.6 1.8 2 2.2 2.4 2.6 2.8 3 Fig. 4 shows a nonlinear relation of fault current respect
time (s) to the voltage.
Fig. 2. HIF Current.

Data are in COMTRADE (Common Transient Data


Fig 2 shows that the fault current reaches up to 1 A peak
Exchange) and can be processed by ATP/EMTP.
and it is observed a highly random behavior, the current
grows up in the first cycles, then it grows and maintains
quasistable.

Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 27,2022 at 09:56:37 UTC from IEEE Xplore. Restrictions apply.
IV. DISCRETE WAVELET TRANSFORM

Wavelet transform has successful applications in many H P-High Pass Filter S[n] f
fields such as acoustics, signal and image processing, speech LP-Low Pass Filter
discrimination, optics and, recently, power system analysis. f-Samling Rate Hz
Its application in power systems has been researched and cA-Aproximation
HP h[n] g[n] LP
developed for the past several years. Typical applications cD-Detail Downsamplig
include power system protection [13], analysis of power
system transients [14], power quality detection and Level 1 f/4-f/2 A1 D1 <f/4
classification [15], etc. Unlike traditional Fourier transform,
a wavelet transform is capable of providing the time and HP h[n] g[n] LP
frequency information simultaneously, and hence, gives
multiple resolutions in frequency and time, which is a Downs amplig

potential feature for analyzing transient signals containing


Level 2 f/8-f/4 A2 D2 <f/8
both high and low frequency components together.

HP h[n] g[n] LP
Wavelet analysis is a method of signal processing so that,
after a series of decompositions, the signal is represented at Downsamplig

different frequency ranges. This is achieved by dilation and


Level 3 f/16-f/8 A3 D3 <f/16
translation of a mother wavelet over the signal. To process
the data in a digital sense the discrete wavelet transform
(DWT) is used which is given by: Fig. 5. Diagram of multiresolution analysis.

1 Fig. 5 presents the analysis called multi-resolution


, ψ , analysis. This algorithm delivers a description of signals
either currents or voltages as they change with respect to
time at different scales, where large scales are associated
(1) with low-frequency components and small scales are
associated with high frequency signatures.
Ψ is the mother wavelet, x[k] is the input signal and the
scaling and translation parameters “a” and “b” are function V. HIGH IMPEDANCE FAULT DETECTION USING DWT.
of integer parameters m. the result is geometric scaling (i.e.,
1, 1/a,1/a2, …) and translation by 0, n, 2n, …. This scaling For many years, protection engineers and researchers
gives the DWT a logarithmic frequency coverage and this is have looked for solutions to this long standing problem.
in marked contrast to the uniform frequency coverage of, This search has resulted in the development of several
i.e., the short time Fourier transform (STFT). techniques to detect HIFs. These groups of faults, in
addition to being characterized as low current faults, tend to
The DWT can be implemented by using a multistage filter exhibit random behavior with unstable and wide fluctuations
with the mother wavelet as the lowpass filter l(n) and its in current levels. They are also characterized by the
dual as the highpass filter h(n). Also, downsampling the presence of harmonics and high frequency components.
output of the lowpass filter l(n) by a factor of 2 effectively Most of the research on HIFs has focused on the
scales the wavelet by a factor of 2 for the next stage, thereby development of sensitive detectors to reliably detect such
simplifying the process of dilation. The output of the faults. Some of the techniques used are neural networks,
highpass filter gives the detailed version of the high- expert system, fuzzy logic, Fourier transformation, Kalman
frequency component of the signal. Also, the low-frequency filtering, relay logic, and recently Wavelets.
component is further split to get the other details of the input
signal. By using this technique, any wavelet can be Although wavelet analysis is more complex than other
implemented. The coefficients of the filters are associated signal processing, it is ideally suited for dealing with non
with the selected mother wavelet. The signal is decomposed stationary signals as are the high impedance faults. There
into two other signals as shown in Fig. 5 which represent a are many types of mother wavelets, such as Harr, Daubiches
smooth and detailed version of the original signal, termed (db), Coiflet (coif) and Symmlet (sym) wavelets. The choice
the approximation and detail respectively. This process is of mother wavelet plays a significant role in detecting and
repeated with the approximation being decomposed further localizing different types of fault transients. In addition to
to generate the next approximation (A) and detail (D). The this, the choice also depends on a particular application.
approximation and detail of the DWT is directly related to
the sampling rate of the original signal [16].

Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 27,2022 at 09:56:37 UTC from IEEE Xplore. Restrictions apply.
An arcing often accompanies many high impedance
VI. CASE OF STUDY. faults due the high harmonic content. In general, most of
these types of faults are rich in different frequencies, which
High impedance faults show relative small current values is an important feature for study and detection. Wavelet
in electric distribution systems. Discrimination of the high toolbox in MATLAB program [17] was used for this study.
impedance fault current is difficult because such current is Daubechies wavelet 4 (db4) is found appropriate for
often below load current on the feeder; in addition it is detecting this fault. Fig 8 shows four levels of wavelet
possible the confusion with currents from other electrical decomposition (db-4) in the fault phase.
equipment in normal conditions such as arc furnace loads,
switching, starting motors, inrush current, furnace induction 200
loads , electronic devices and others. The Fig. 6 shows an

A4
0
Electric distribution system with unbalanced loads. To -200
0 0.05 0.1 0.15
observe the behavior of the system with a high impedance 0.1
fault, the field record obtained were injected in the system

D4
0
and simulated in ATP/EMTP. -0.1
0 0.05 0.1 0.15
0.02

D3
0
-0.02
0 0.05 0.1 0.15
Zth LCC LCC LCC LCC LCC 0.02

D2
0
V

-0.02
5 km 5 km 5 km 5 km 5 km 0 0.05 0.1 0.15
ASCR 3/0 ASCR 3/0 ASCR 3/0 ASCR 3/0 ASCR 3/0 0.02
13.8KV
D1
0
LC C

Source 5 km -0.02
ASCR 3/0 0 0.05 0.1 0.15
I

LCC LCC HIF time (s)


Fig. 8.- DWT decomposition at phase a in the feeder.

5 km 5 km Fig. 8 shows 4 levels of DWT decomposition where A4


ASCR 3/0 ASCR 3/0
F is the low frequency and D4, D3, D2, D1 are the high
frequency decomposition.
Fig. 6.- Electric Distribution System
Fig. 9 shows the decomposition D3 of the faulted phase
Fig. 6 corresponds to the feeder of 13.8kV with overhead and healthy phases with high impedance fault. The fault is in
lines of 5 km each one with conductor of 3/0 ASCR (r = D3(a) and the healthy phases are D3(b) and D3(c).
0.1598, x = 0.4315 ohm/km), and different loads varying from
30 up to 300 kVA. Also HIF with cover conductor to ground D3(a)

at end of feeder and are simulated in ATP/EMTP. 0.02

Fig. 7 shows the total current at the substation, the load -0.02

current is higher than high impedance fault. 0 0.05 0.1 0.15


D3(b)
150 0.02
Ia
Ib 0
Ic
100
-0.02
0 0.05 0.1 0.15
50 D3(c)
Current (A)

0.02
0
0

-0.02
-50
0 0.05 0.1 0.15
time (s)
-100 Fig. 9.-Current at substation

-150
0 0.05 0.1 0.15
DWT and Details D3 are implemented in each phase as
time (s) is shown in Fig. 9.
Fig. 7. - Current at feeder with HIF.

Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 27,2022 at 09:56:37 UTC from IEEE Xplore. Restrictions apply.
The absolute sum value of the current detail D3 over a REFERENCES
period of the power frequency is computed in a discrete
form at each measuring node, as in [18]: [1] IEEE Power System Relaying Committee Working Group D15 Report,
“High Impedance Fault Detection Technology” March 1, 1996.
Available: http://grouper.ieee.org/groups/td/dist/documents/highz.pdf

| 3 | 2 [2] C. Huang, H. and Chu, M. Chen “Algorithm Comparison for High


Impedance Fault Detection Based on Staged Fault Test” IEEE
Transactions on Power Delivery, Vol. 3, No. 4, pp. 1427-1435,
October 1988.
Where S(k) means the detector in the discrete samples. n
is used for carrying out a sliding window covering 16.66 ms [3] A.E. Emmanuel, D. Cygansky, S. Shiller, and E. M. Gulachenski, ”High
Impedance Faul ton sandy soil in 15 KV Distribution Feeders:
and N is a number of window samples. S(k) performance is Contribution To The evaluation Of the low Frecuencie Spectrun” IEEE
shown in Fig. 10. Transactions on Power Delivery, Vol. 5, No. 2, pp. 676-686, April
1990.
2
D3(a)
[4] D. I. Jeerincs, and J. R. Linders, “A Practical Protective Relay for
D3(b)
1.8 Down-Conductor Faults” IEEE Transactions on Power Delivery Vol.
D3(c)
1.6
6, No. 2, pp. 565-573, April 1991.

1.4 [5] A. Girgis, W. Chang, and E. Makram, “Analysis of high-impedance


fault generated signals using a Kalman Filtering Approach” IEEE
1.2 Transactions on Power Delivery, Vol. 5, No. 4, pp. 1714-1724 ,
Magnitude(A)

1
November 1990.

0.8 [6] S. Ebron, D. Lubkeman, and Mark White, “A neural network approach
to the detection of incipient faults on Power Distribution Feeders”
0.6 IEEE Transactions on Power Delivery, Vol. 5, No. 2, pp. 905-914,
0.4
April 1990.

0.2 [7] L.A Snider, and Y. Shan, “The ANN Based Relay Algorithm for
Distribution System High Impedance Fault Detection” Proceedings of
0
0 0.05 0.1 0.15 the 4th International Conference on Advances on Power System
time (s) Control Operation and Management, APSCOM-97 Honk Kong,
Fig.10.- Absolute Sum Values of D3. November 1992.

Discrete wavelet transform in high impedance fault gives [8] A. Lazkano, J. Ruiz, E. Aramendi, and L. A. Leturiondo, “A New
Approach to High Impedance Fault Detection Using Wavelet Packet
us the possibility to identify the characteristics of the fault at Analysis,” in Proc. IEEE 2000 Int. Conf. on Harmonics and Quality of
different frequencies because they cannot observe at a Power, pp. 1005-1010, 2000.
fundamental frequency.
[9] Chul-Hwan Kim, Hyum Kim, Young-Hun Ko, Sung-Hyun Byun, Raj
K. Aggarwal, Allan T. Johns “A Novel Fault-Detection Technique of
VI. CONCLUSION. High Impedance Fault in Transmission Lines Using the Wavelet
Transform” IEEE Transactions on Power Delivery, Vol. 17, No. 4, pp.
Mexico has an electrical distribution system with voltage 921-929, October 2002.
levels of 13.8 kV, 23 kV and 34.5 kV, so that HIF testing is
[10] N. I. Elkalashy, M. Lehtonen, H. A. Darwish, M. A. Izzularab and
expensive, dependant on time, on electrical condition and it A.M.I. Taalab,” DWT Based Investigation of Phase Currents for
is very difficult to simulate them in real condition, so the Detecting High Impedance Faults Due to Leaning Trees in Unearthed
High impedance fault computer modeling is a very useful MV Networks”, 2007 IEEE Power Engineering Society General
tool. Meeting, Tampa, Florida, USA, June 2428, 2007.

[11] Mudathir Funsho Akorede, James Katende” Wavelet Transform Based


In the analysis of field test there were important features Algorithm for High Impedance Faults Detection in Distribution
of the high impedance fault as are low current and arcing, Feeders”, European Journal of Scientific Research,Vol. 41, No. 2, pp.
also were observed that the current of high impedance fault 238-248, 2010.
has random behavior, nonlinearity, asymmetry and current [12] “Detection of Downed Conductors on Utility Distribution
in phase with the voltage due to a mainly resistive behavior. Systems”,IEEE PES Tutorial Course 90EH0310-3-PWR, 1989.

DWT was used to study signals at different frequencies, [13] D. C. Robertson, O. I. Camps, J. S. Mayer, and W. B. Gish, ‘‘Wavelets
and electromagnetic power system transients’’, IEEE Trans. Power
the tool allowed us to observe the behavior of current in the
Delivery, vol. 11, No. 2, pp. 1050-1056, April 1996.
frequency. The DWT analysis gives some signals from high
impedance fault which can be used for a successful [14] A. M. Gaouda and M. M. A. Salama, ‘‘Power quality detection and
detection. classification using wavelet multi-resolution signal decomposition’’,
IEEE Trans. Power Delivery, vol. 14, No. 4, pp. 1469-1475, Oct. 1999.

Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 27,2022 at 09:56:37 UTC from IEEE Xplore. Restrictions apply.
[15]Eric A. Wan, "Finite impulse response neural networks with
applications in time series prediction," Ph.D. dissertation, Dept. Elect.
Eng., Stanford Univ. 1993.

[16] P.L. Mao and R.K. Agarwal, "A novel approach to the classification of
the transient phenomena in power transformers using combined
wavelet transform and neural network," IEEE Trans. Power Delivery,
vol. 16, pp. 654-660, Oct. 2001.

[17] Wavelet Toolbox for MATLAB, Math Works 2005.

[18] J. Haung, C. Shen, S. Phoong and H. Chen "Robust Measure of Image


Focus in the Wavelet Domain" International Symposium on Intelligent
Signal Processing and Communication Systems, ISPACS2005, Hong
Kong, Dec. 13-16, 2006.

Authorized licensed use limited to: UNIV OF ENGINEERING AND TECHNOLOGY LAHORE. Downloaded on September 27,2022 at 09:56:37 UTC from IEEE Xplore. Restrictions apply.

You might also like