Professional Documents
Culture Documents
Introduction
Unit Protection
Summary
2
INTRODUCTION
Most high-voltage transmission systems are interconnected in a network
Overcurrent relays, which were quite adequate protective devices for radial
circuits.
3
Cont’d…
4
Cont’d…
Directional overcurrent relays are the simplest and least expensive, but are the
most difficult to apply. Overcurrent relays also have the disadvantage in changing
their coordination characteristics as the network and generation sources
change.
Overcurrent relays are widely used for ground protection.
Distance relays are often a first choice for replacing overcurrent relays when the
overcurrent relays are found to be inadequate for an application. Distance relays are
very common in applications for phase and ground protection of transmission
lines.
5
PROTECTION WITH OVERCURRENT RELAYS
certain conditions. Consider the simple network shown in Figure.1, where two
parallel transmission lines interconnect two systems, each of which contains
sources of fault.
Fig.1. Parallel transmission lines interconnecting two systems with generating sources. 6
Cont’d…
maintain a coordinating time interval between adjacent relays. Thus, for a fault
on line A-B, we reason, by inspection, that
𝑡𝐴 < 𝑡𝐶
𝑡𝐵 < 𝑡𝐷 …………………….(1)
Where t is the relay time for a given fault current magnitude and the subscript
7
Cont’d…
Similarly, if the fault is on line CD,
𝑡𝐷 < 𝑡𝐵
𝑡𝐶 < 𝑡𝐴 …………………….(2)
For proper coordination. Clearly, it is not possible to satisfy both (1) and (2)
One way of improving the selectivity of the overcurrent relay is the addition
of a directional element.
8
Cont’d…
The criteria for deciding whether directional relays should be required are
sometimes determined by the ratio of currents flowing in relays at the two ends
of a line.
Consider a portion of a large system in Figure 2, where we have numbered three
fault locations and have defined currents in breaker A corresponding to each
fault.
10
Cont’d…
Both load and fault currents are sensed at the bus G side of breaker A. The need
for directional capability depends, then, on the ratio of currents seen at the
breaker, where the current might be caused to flow in different directions.
Fault current for fault (1) flows toward a fault "behind" the relay at A,
while the faults at (2) and (3) are "in front" of the relay.
If the load current from H to G (𝐼𝐿𝑑 𝑜𝑢𝑡 ) is greater than that from G to H
(𝐼𝐿𝑑 𝐼𝑛 ) the use of directional relays will permit more sensitive settings.
11
Loops with One Current Source
First, consider the case of a looped transmission system where there is only one
source of fault current, such as the system shown in figure 3.
The source of fault current is to the left of bus R. Therefore, it is permissible to use
nondirectional overcurrent relays at 1 and 10, since a fault on bus R will not cause
currents to flow in the transmission loop in either direction.
Figure .3 A Transmission loop circuit with only one source of fault current. 12
Loops with Multiple Current Sources
For looped transmission systems with multiple sources, the coordination process
is much more complex. Now, all overcurrent relays must be directional and each
pair of relays must be coordinated, moving around the loop in both directions.
14
Figure 5 Relay currents at R and Q for faults between R and Q.
Cont’d…
Figure 5 shows the fault current seen at relay locations 1 and 4 as the fault is
Usually, the process is cut and try, and it may require several attempts to
realize complete coordination.
15
DISTANCE PROTECTION OF LINES
The distance relay operates on the principle of comparing the voltage and
current in some way to obtain a measure of the ratio between these quantities.
𝑉𝑅 = ℎ𝑆 𝑍𝐿 𝐼𝑅𝑆 ……………………………………………………………………….(4)
Where VR = voltage at the relay, IRS = current at the relay, ZL = total line impedance from G to H,
and hS = fraction of line impedance to balance point.
17
Cont’d…
Since the relay measures the ratio of relay voltage to relay current, compute the
VR
IRS
=ZRS = hS ZL ………………………………… ………………………….….(5)
if the fault is closer to G, the voltage at the relay will be slightly lower or the current
ZR ≤ hS ZL …………………………………….……………………………..(6)
18
Zoned Distance Relays
A distance relay will trip a faulted line in a very short time as long as the fault is
This is done by providing more than one distance relaying element within the
same relay package and setting the different elements to different thresholds and
with different relaying times.
Figure 7 shows a typical application. In the system illustrated, the distance relays
19
Cont’d…
Zone 1 is set to protect about 90% of the line length
and to operate with no intentional time delay.
Zone 2 is set for 100% of the protected line plus
about 50% of the shortest adjacent line, and is set to
operate with time delay 𝐓𝟐 .
Zone 3 is set to reach through 100% of the
impedance of two lines and 25% of the third line,
and to operate the zone 3 element with time delay 𝐓𝟑 .
The application of the timer, such as T2 , provides a
coordination time interval (CTI) for the relay
operation in the end zone of each line. Similarly, T3 is
set to provide a CTI with zone 2 relays. Figure 7: Step time and impedance zones for distance relays
20
UNIT PROTECTION
Distance protection for all types of faults makes this technique very difficult and the
The final method of transmission protection that will be addressed is the concept
With this concept, the protected line is defined by its protective zone, as shown in
figure 9. The zone of protection includes everything inside the current transformers
where current measurements are made for the protected component.
21
Cont’d…
All faults that occur on the protected line are monitored at the current
but it is the current transformers that define the protective zone boundaries.
Each terminal of the protected line to have two circuit breakers. Indeed,
22
Cont’d…
23
GROUND FAULT PROTECTION
An important aspect of transmission line protection is related to the fast
detection and clearing of ground faults on transmission systems that have
grounded neutrals. In the protection of transmission lines, ground faults are
given special treatment.
Most high-voltage and extra-high voltage transmission lines are grounded
neutral transmission systems, either solidly grounded or grounded through a
resistance or a reactance. It has been estimated that, on these high-voltage
systems, Over 90% of all transmission line faults are ground faults.
24
Types of Ground Relays
There are three basic types of relays that are used for ground relaying; overcurrent
Ground relays are almost always completely independent of phase relays, even
though any fault current, including ground fault current, will flow through one or
more of the phase relays.
The ground relays can be provided with much greater sensitivity to the zero-
sequence currents by using higher tap settings. This means that the ground relays
will pick up much faster than phase relays for a fault involving the ground.
25
Cont’d…
about one cycle in many cases, for faults on a large fraction of the line
length.