You are on page 1of 6

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.

0 2013 Spring
web.itu.edu.tr/yumakk
1

Distance Protection
Announcement: You are not supposed to prepare a pre-report. But there will be an oral examination, so you
are strongly advised to study this note regarding to the pre-study questions below. After the lab, you will need
to deliver a post-report which contains what you have done in the lab, data, related graphs and answers of the
questions.
Pre-Study Questions
1. Why do we use relays in the power systems?
2. What is the ANSI/IEEE code of distance relays?
3. What is the basic principle of distance protection? How it works?
4. What is the purpose of reach point? How will relays operate regarding to this setting?
5. What are the basic distance protection zones? Why different zones should be defined?
6. What are the main tripping characteristics for distance protection?
7. What is the difference between impedance and mho characteristic?
8. Why modern distance relays offer quadrilateral characteristics?
9. Why R-X diagram is commonly used?
10. What do the four quadrants of the R-X diagram show?

1. Objective
To study the principles of distance protection.
2. Theory [1-4]
Relays are used to detect abnormal conditions in the power systems. After detection of a fault,
relays close circuit breakers and disconnect faulty circuits from the general supply system in order to
minimize the damage. There is a list of ANSI/IEEE codes of different types of protection relays as
follows [5, 6]:





2 - Ti me Del ay Starti ng or Cl osi ng Rel ay 67 - AC Di recti onal Overcurrent Rel ay
21 - Distance Relay 68 - Bl ocki ng or out of step Rel ay
25 - Synchroni zi ng or Synchroni sm-Check Devi ce 69 - Permi ssi ve Control Devi ce
27 - Undervol tage Rel ay 74 - Al arm Rel ay
30 - Annunci ator Rel ay 76 - DC Overcurrent Rel ay
32 - Di recti onal Power Rel ay 78 - Phase-Angl e Measuri ng Rel ay
37 - Undercurrent or Underpower Rel ay 79 - AC-Recl osi ng Rel ay
38 - Beari ng Protecti ve Devi ce 81 - Frequency Rel ay
40 Fi el d (over/under exci tati on) Rel ay 85 Pl i ot Comm., Carri er or Pi l ot-Wi re Rel ay
46 Rev. phase or Phase-Bal . Current Rel ay 86 - Lockout Rel ay
47 - Phase-Seq. or Phase-Bal . Vol tage Rel ay 87 - Di fferenti al Protecti ve Rel ay
49 - Machi ne or Transformer Thermal Rel ay 94 - Tri ppi ng or Tri p-Free Rel ay
50 - Instantaneous Overcurrent
51 - AC Ti me Overcurrent Rel ay B Bus
59 - Overvol tage Rel ay F - Fi el d
60 - Vol tage or Current Bal ance Rel ay G Ground or generator
63 - Pressure Swi tch N Neutral
64 - Ground Detector Rel ay T Transformer
ANSI /IEEEStandard Device Numbers
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring
web.itu.edu.tr/yumakk
2

2.1. Basic Principle
A distance relay has the ability to detect a fault within a pre-set distance along a transmission line or
power cable from its location. Every power line has a resistance and reactance per kilometer related
to its design and construction so its total impedance will be a function of its length. A distance relay
therefore looks at current and voltage and compares these two quantities on the basis of Ohms law.

Since the impedance of a transmission line is proportional to its length, for distance measurement it
is appropriate to use a relay capable of measuring the impedance of a line up to a predetermined
point (the reach point).
Distance relay is designed to operate only for faults occurring between the relay location and the
predetermined (reach) point, thus giving discrimination for faults that may occur in different line
sections.
The basic principle of distance protection involves the division of voltage at the relaying point by the
measured current. The calculated apparent impedance is compared with the reach point impedance.
If the measured impedance is less than the reach point impedance, it is assumed that a fault exists
on the line between the relay and the reach point.
2.2. Zones of Protection
Careful selection of the reach point settings and tripping times for various zones of measurement
enables correct coordination between distance relays on a power system. Basic distance protection
will comprise one instantaneous (Zone 1) and one or more time delayed zones (Zone 2, Zone 3, Zone
4 ). Typical reach and time settings for a 3-Zone distance protection are shown below:

Zone 1: this is set to protect between 80% of the line length AB and operates without any
time delay. This under-reach setting has been purposely chosen to avoid over-reaching
into the next line section to ensure selectivity since errors and transients can be present in
the voltage and current transformers. Also manufacturing tolerances limit the measurement
accuracy of the relays.
Zone 2: this is set to protect 100% of the line length AB, plus at least 20% of the shortest
adjacent line BC and operates with time delay t2. (0.5s)
It not only covers the remaining %20 of the line, but also provides backup for the next line
section.
Zone 3: this is set to protect 100% of the two lines AB, BC, plus about 25% of the third line
CD and operates with time delay t3. (1.5s)
It should be noted that, digital distance relays may have up to six zones, some set to measure in the
reverse direction.
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring
web.itu.edu.tr/yumakk
3

2.3. Tripping Characteristics
The shape of the operation zones has developed throughout the years. An overview of relay
characteristics can be seen below:


i. Impedance Characteristic:
If the relays operating boundary is plotted on an R-X diagram, its impedance characteristic is a circle
with its center at the origin of the coordinates and its radius will be the setting (the reach point) in
ohms. The relay will operate for all values less than its setting i.e. for all points within the circle. This
type of relay, however, is non-directional. It can operate for faults behind the relaying point. It takes
no account of the phase angle between voltage and current. It is also sensitive to power swings and
load encroachment due to the large impedance circle.

ii. Mho Characteristic:
The limitation of the impedance characteristic can be overcome by a technique known as self-
polarization. Additional voltages are fed into the comparator in order to compare the relative phase
angles of voltage and current, so providing a directional feature. This has the effect of moving the
circle such that the circumference of the circle passes through the origin. Angle is known as the
relays characteristic angle. It appears as a straight line on an admittance diagram.


TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring
web.itu.edu.tr/yumakk
4

By use of a further technique of feeding in voltages from the healthy phases into the comparator
(known as cross polarization) a reverse movement or offset of the characteristic can be obtained.
This is called the offset mho characteristic.

iii. Combined Characteristic:
Relays with combined characteristics are obtained by added a mho circle with lines parallel to the
resistive and reactive axes which cross each other at the setting point

.

iv. Quadrilateral Characteristic:
Modern distance relays offer quadrilateral characteristic, whose resistive and reactive reach can be
set independently. It therefore provides better resistive coverage than any mho-type characteristic
for short lines. This is especially true for earth fault impedance measurement, where the arc
resistances and fault resistance to earth contribute to the highest values of fault resistance.
Polygonal impedance characteristics are highly flexible in terms of fault impedance coverage for
both phase and earth faults. For this reason, most digital relays offer this form of characteristic.


2.4. Significance of R-X Diagram
In general, all electromechanical relays respond to one or more of the conventional torque-
producing input quantities: (a) voltage, (b) current, (c) product of voltage, current and the angle
between them and (d) a physical or design force such as a control spring. Similar considerations hold
for solid-state relays as well. For distance relay, analyzing the response of the relay for all conditions
is difficult because the voltage varies for each fault, or varies for the same fault but with different
system conditions.

To resolve this difficulty, it is common to use an RX diagram. By utilizing only two quantities, R and
X (or Z and ), we avoid the confusion introduced by using the three quantities E, I and . There is an
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring
web.itu.edu.tr/yumakk
5

additional significant advantage in that the RX diagram allows us to represent both the relay and
the system on the same diagram.

Consider an ideal (zero resistance) short circuit at location F in the single-phase system shown
below. The distance relay under consideration is located at line terminal A.

The subscript p represents primary and s represents secondary quantities. In terms of the
secondary quantities of voltage and current transformers, the relay sees

as



where

and

are the current transformer (CT) and voltage transformer (VT) turns ratios.

When a fault occurs, this impedance

may be plotted as a point on the complex RX plane. Now


consider the fault at location F as shown in the figure below. The line AB makes an angle with the R
axis, where is the impedance angle of the transmission line. (For an overhead transmission line,
lies between 70 and 88). When the fault is on the transmission line, the apparent impedance plots
on the line AB; for all other faults or loading conditions, the impedance plots away from the line AB.
Often it is convenient to plot the source impedance

also on the RX diagram.




3. Practical Information
In this lab, the distance protection function (21) of SIPROTEC 4 - 7SA610 [7] and Kingsine K68i
Protection Relay Test Set [8] will be used. Order number of the relay is as follows: 7SA610
Order number includes many information about the relay, such as; housing, binary inputs and
outputs, measuring inputs, language settings and its functions. It can be seen in the catalog of the
relay.
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v1.0 2013 Spring
web.itu.edu.tr/yumakk
6

The relay supports distance protection (21/21N), high resistance earth-fault protection for single and
three phase tripping (50N, 51N, 67N), pilot protection (85), fault locator (FL), phase overcurrent
protection (50/51/67), over/under voltage protection (59/27), over/under frequency protection
(81O/U) and auto-reclosure function (25). For communication, the relay supports IEC 61850
Ethernet, IEC 60870-5-103, Profibus, RS232 and RS 485.
For distance protection, the relay provides 6 zones that can be set to forward, reverse,
nondirectional and inactive. Load zones for phase-phase and phase-earth can be set separately.
4. Procedure
You dont need to set up any connection. Only study the connection scheme. In the lab, you will
measure several distance and trip time values from the relay regarding to specified fault impedances
in the relay test set.
5. Connection Scheme
Connection scheme will be provided soon.
6. References
1. L. G. Hewitson, M. Brown, R. Balakrishnan, Practical Power System Protection, Elsevier, 2005.
2. S. H. Horowitz, A. G. Phadke, Power System Relaying, John Wiley & Sons, 2008.
3. H. M. Tran, H. Akyea, Numerical Distance Protection Relay Commissioning and Testing, MSc Thesis,
Chalmers University of Technology, Gteborg, Sweden, 2005.
4. http://www.fecime.org/referencias/npag/chap11-20-170-191.pdf
5. IEEE Standard C37.2 - 2008 : IEEE Standard for Electrical Power System Device Function Numbers,
Acronyms, and Contact Designations.
6. http://www.ee.uidaho.edu/ee/power/EE525/Lectures/L9/RelayDeviceNumbers.pdf
7. Catalog of Siemens SIPROTEC 4 - 7SA6 : Distance Protection Relay for all Voltage Levels.
8. http://www.kingsine.com.cn/UserFiles/download/1713062151.pdf

7. Questions for the Post-Report

1. What is the meaning of mho? Is there any relation between the units mho and ohm?

2. What is the key advantage of distance protection over overcurrent protection? (look up in
[4])

3. What are the under-reach and over-reach concepts? (look up in [4])

You might also like