You are on page 1of 8

1-800-500-4SKM | sales@skm.

com | Shopping Cart

CELEBRATING 50 YEARS
OF EXCELLENCE

Home Products Support Training Contact My SKM

Frequently Asked Questions Downloads Application Guides Power Systems Study Specs Tutorial Videos

Equipment Damage Curves Transformers

The information presented in this application guide is for review, approval, interpretation and application by a registered professional engineer only. SKM
disclaims any responsibility and liability resulting from the use and interpretation of this information.

Reproduction of this material is permitted provided proper acknowledgement is given to SKM Systems Analysis Inc.

Purpose

The purpose of this guide is to provide basic information about transformer through-fault damage curves and characteristic landmarks necessary for plotting
on time-current curves, for the purpose of equipment overcurrent protection. Damage curves are defined in the IEEE standards in per unit on the nominal
base rating (kVA) of the transformer, and are not adjusted with changes to the core, winding material or method of cooling.

Full Load Amps (FLA)

FLA is the rated continuous current carrying capacity of a transformer at a referenced ambient temperature and allowable temperature rise, see table 1. The
FLA label is located on a time-current curve (TCC) in top decade at 1000 seconds.
The total temperature rise of an OA 65°C transformer, at an average/maximum ambient temperature of 30/40°C, is 110/120°C. These temperatures do
exceed the transformer insulation rating of 105°C, and are allowed by the standards.
Table 1 Transformer temperature ratings

Cooling Ave/Max Hot Spot Temp. Total Temp. Insul. Max Winding
Method Amb. Temp. Temp. Rise Rise Temp. SC Temp.

15°C 75°C 120°C/130°C 130°C 300°C


20°C 90°C 140°C/150°C 150°C 350°C
AA 30°C/40°C 25°C 115°C 170°C/180°C 180°C 400°C
30°C 130°C 190°C/200°C 200°C 425°C
30°C 150°C 210°C/220°C 220°C 450°C

10°C 55°C 95°C/105°C 200°C-Al


ONAN (OA) 30°C/40°C 105°C
15°C 65°C 110°C/120°C 250°C-CU

SC Withstand Capability (Damage) Curves

ANSI C57.109 defines damage characteristics for oil-filled, power transformers see tables 2-5. ANSI C57.12.59 defines damage characteristics for dry-type
transformers see table 6 and 7. The through-fault current damage curves are not intended for overload capability. The standards state, “if fault current
penetrates the limits of the thermal damage curve insulation may be damaged, or if fault current penetrates the limits of the mechanical damage curve
cumulative mechanical damage may occur. The validity of these damage limit curves can not be demonstrated by test, since the effects are progressive over
the transformer lifetime. They are based principally on informed engineering judgment and favorable, historical field experience."
The damage curves are plotted in the top 3 decades of a TCC from 2 to 1000 seconds.

Table 2 Category I Liquid-Immersed Transformers

5-500kVA 1-φ
15-500kVA 3-φ
Frequent (Mechanical Damage)
or Infrequent Faults (Thermal Damage)
x Rated Current Time I2t 1-φ 3- φ
(A p.u.) (sec.) (A p.u.-sec.) (kVA) (kVA)
2 1800 7200 5-500 15-500
3 300 2700 5-500 15-500
4.75 60 1354 5-500 15-500
6.3 30 1191 5-500 15-500
11.3 10 1277 5-500 15-500
25 2 1250 5-500 15-500
35 1.02 1250 5-100 15-300
40 0.78 1250 5-75 15-75

Table 3 Category II Liquid-Immersed Transformers

501-1667kVA 1- φ
501-5000kVA 3- φ
Infrequent Faults (Thermal Damage)

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

2 1800 7200

3 300 2700

4.75 60 1354

6.3 30 1191

11.3 10 1277

25 2 1250

Frequent Faults (Include Infrequent Points Plus)

Mechanical Damage Points

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

0.7 / Z 2551 Z2 1250

0.7 / Z 4.08 K

1.0 / Z 2 K

Table 4 Category III Liquid-Immersed Transformers

1668-10,000kVA 1- φ

5001-30,000kVA 3- φ
Infrequent Faults (Thermal Damage)

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

2 1800 7200

3 300 2700

4.75 60 1354

6.3 30 1191

11.3 10 1277

25 2 1250

Frequent Faults (Include Infrequent Points Plus)

Mechanical Damage Points

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)


0.5 / Z 5000 Z2 1250

0.5 / Z 8 K

1.0 / Z 2 K

Table 5 Category IV Liquid-Immersed Transformers

Above 10,000kVA 1- φ

Above 30,000kVA 3- φ
Frequent (Mechanical Damage)
or Infrequent Faults (Thermal Damage)

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

2 1800 7200

3 300 2700

4.75 60 1354

6.3 30 1191

11.3 10 1277

25 2 1250

Frequent (Mechanical Damage)


or Infrequent Faults (Thermal Damage)

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

0.5 / Z 5000 Z2 1250

0.5 / Z 8 K

1.0 / Z 2 K

IEEE Std C57.12.01 defines 3 categories of dry-type transformers. However, IEEE Std C57.12.59 only defines damage curves for Category I and II
transformers.  Damage curves for Category III transformers, 1668-10,000kVA 1- φ, 5001-30,000kVA 3-φ are not defined.

Table 6 Category I Dry-Type Transformers

1-500kVA 1- φ

15-500kVA 3- φ
Frequent (Mechanical Damage)
or Infrequent Faults (Thermal Damage)

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

3.5 100 1250

11.2 10 1250

25 2 1250
Table 7 Category II Dry -Type Transformers

501-1667kVA 1- φ

501-5000kVA 3- φ
Infrequent Faults (Thermal Damage)

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

3.5 100 1250

11.2 10 1250

25 2 1250

Frequent Faults (Include Infrequent Points Plus)

Mechanical Damage Points

x Rated Current Time I2t

(A p.u.) (sec.) (A p.u.-sec.)

0.7 / Z 2551 Z2 1250

0.7 / Z 4.08 625

1.0 / Z 2 625

Magnetizing Inrush Current Point(s)

One or more inrush current points may be plotted on a TCC.  Inrush currents are expressed in peak amps.  The most common point is 8-12 times rated FLA
at 0.1 seconds.  Another less common point is 25 times rated FLA at 0.01 seconds. 

Example 1

Plot the characteristic landmarks for a 1000kVA, 65°C, 4160-480/277V, Δ-YG, oil-filled, substation transformer with an impedance of 6.0%.  Consider both the
frequent and infrequent fault cases for this application. 

Solution

Step 1 – Calculate the FLA


FLA = 1000kVA / (1.732 x 4.16kV) = 139 amps 
Step 2 – Determine the Applicable Category
This is a Category II transformer based on the nominal rating of 1000kVA
Step 3 – Calculate the infrequent fault data points from Table 3
I 1800 sec = 2 x 139 amps = 278 amps
I 300 sec = 3 x 139 amps = 417 amps
I 60 sec = 4.75 x 139 amps = 660 amps
I 30 sec = 6.3 x 139 amps = 876 amps
I 10 sec = 11.3 x 139 amps = 1571 amps
I 2 sec = 25 x 139 amps = 3475 amps

Since the transformer is connected Δ-YG a separate set of data points must be calculated for primary-side protective devices.  Primary-side devices will only
see 58% of a secondary-side, single-line-to-ground fault.
I 1800 sec = 0.58 x 2 x 139 amps = 161 amps
I 300 sec = 0.58 x 3 x 139 amps = 242 amps
I 60 sec = 0.58 x 4.75 x 139 amps = 383 amps
I 30 sec = 0.58 x 6.3 x 139 amps = 508 amps
I 10 sec = 0.58 x 11.3 x 139 amps = 911 amps
I 2 sec = 0.58 x 25 x 139 amps = 2016 amps
Step 4 – Calculate the frequent fault data points from Table 3
I 2 sec = 139 amps / Z = 139 amps / 0.06 = 2316 amps
I 4.08 sec = 0.7 x 139 amps / Z = 97.3 amps / 0.06 = 1622 amps
t 1622 amps = 2551 (0.06)2 = 9.2 seconds
Again, shift the data points by 0.58.
I 2 sec = 0.58 x 139 amps / 0.06 = 1344 amps
I 4.08 sec = 0.58 x 97.3 amps / 0.06 = 941 amps
Step 5 – Calculate Inrush Points
12 x Inrush = 12 x 139 amps = 1668 amps
25 x Inrush = 25 x 139 amps = 3475 amps
The results are plotted in figure 1.

Example 2

Repeat Example 1 but now assume the secondary is high-resistance grounded (HRG). 

Solution

Step 1 – Same as Example 1


Step 2 – Same as Example 1
Step 3 – Same as Example 1
No shifting of the damage curve is required with a HRG secondary.  In this case the primary-side protective devices will not see a ground fault on the
secondary-side.  Ground fault magnitudes will always be much lower than load current levels. 
Step 4 – Same as Example 1
Again, no shifting of data points is required.
Step 5 – Same as Example 1
The results are plotted in figure 2.

Fig. 1 1000kVA, Δ-YG, liquid-immersed transformer damage curves


Fig. 2 1000kVA, Δ-YG (HRG), liquid-immersed transformer damage curves

Example 3

Plot the characteristic landmarks for a 1500kVA, 150°C, 13800-480/277V, Δ-Δ, dry-type, substation transformer with an impedance of 5.75%.  Consider the
infrequent fault case for this application.

Solution

Step 1 – Calculate the FLA


FLA = 1500kVA / (1.732 x 13.8kV) = 62.8 amps 
Step 2 – Determine the Applicable Category
This is a dry-type, Category II transformer based on the nominal rating of 1500kVA
Step 3 – Calculate the infrequent fault data points from Table 7
I 100 sec = 3.5 x 62.8 amps = 220 amps
I 10 sec = 11.2 x 62.8 amps = 703 amps
I 2 sec = 25 x 62.8 amps = 1570 amps

Since the transformer is connected Δ-Δ a separate set of data points must be calculated for primary-side protective devices.  Primary-side devices will only
see 87% of a secondary-side, line-to-line fault.
I 100 sec = 0.87 x 3.5 x 62.8 amps = 191 amps
I 10 sec = 0.87 x 11.2 x 62.8 amps = 612 amps
I 2 sec = 0.87 x 25 x 62.8 amps = 1366 amps
Step 4 – Calculate Inrush Points
12 x Inrush = 12 x 62.8 amps = 754 amps
25 x Inrush = 25 x 62.8 amps = 1570 amps
The results are plotted in figure 3.
Fig. 3 1500kVA, Δ- Δ, dry-type transformer damage curves

References

•   Other Application Guides offered by SKM Systems Analysis at www.skm.com


•   ABB Protective Relaying Theory and Application, 2nd Edition, 2004
The latest revision of:
•   IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (IEEE Buff Book)
•   EEE Std C57.12.00, IEEE Standard General Requirements for Liquid-Immersed Distribution, Power and Regulating Transformers
•   IEEE Std C57.12.01, IEEE Standard General Requirements for Dry-Type Distribution and Power Transformers Including Those with Solid-Cast and/or
Resin-Encapsulated Windings
•   IEEE Std C57.12.59, IEEE Guide for Dry-Type Transformer Through-Fault-Current Duration
•   IEEE Std C57.109, IEEE Guide for Liquid-Immersed Transformer Through-Fault-Current Duratio

Insulating materials

Insulation Maximum
Insulating Materials
Class Temperature

Cotton, silk, paper, wood,


Y 90°C cellulose, fibre without
impregnation or oil-immersion

Class Y impregnated with natural


resins,
A 105°C
cellulose esters, insulating oils, etc.,
also laminated wood, varnished paper

TInsuldur® InsulationT
Hybrid A 110°C Kraft paper with epoxy binders
activated under pressure

Synthetic-resin enamels, cotton


E 120°C and paper Laminates 
with formaldehyde bonding

Mica, glass fibre, asbestos, etc., with


suitable bonding substance; built-up
B 130°C
mica,
glass-fibre and asbestos laminates

The materials of Class B with more


F 155°C
thermally-resistant bonding materials
H 180°C Glass-fibre and asbestos materials,
and built-up mica, with appropriate
Silicone resins

Mica, ceramics, glass, quartz, and


asbestos without binders or with
C >180°C
silicone
resins of superior thermal stability

TNOMEX® insulation,
>H 220°C varnish dipped and vacuum pressure
impregnated (VPI)

back to Application guides

| HOME | PRODUCTS | SUPPORT | TRAINING | CONTACT | MY SKM | CAREER OPPORTUNITIES | DISTRIBUTORS |


© Copyright SKM Systems Analysis Inc. All rights reserved.

You might also like