Purpose
The purpose of this guide is to provide basic information about conductor damage curves and characteristic landmarks necessary for plotting on time-current curves (TCC), for the
purpose of equipment overcurrent protection.
Ampacity
The rated continuous current carrying capacity of the conductor at a referenced ambient temperature, allowable temperature rise, geometry and installation. For bare overhead
conductors an ambient air temperature of 40°C is typical. For underground insulated power cables an ambient earth temperature of 20°C is typical. Temperature correction factors
are then given to adjust the base ampacity for other ambient temperature levels.
If a cable is loaded continuously above rated ampacity the insulation temperature design limits will be exceeded. This will lead to loss of insulation life, not instantaneous failure.
If a bare overhead conductor is loaded continuously above rated ampacity the mechanical strength of the conductor is reduced. This will lead to a loss of mechanical life, not
instantaneous failure.
Table 1 summarizes typical allowable conductor temperature limits under short circuit, emergency overload and normal operating conditions.
Table 1 Typical conductor operating temperature limits
The ampacity landmark is located in the top decade of a TCC at 1000 seconds.
Conductor overcurrent operating limit that if exceeded will reduce the insulation life of a cable or reduce the mechanical life of a bare overhead conductor beyond an acceptable
design loss of life limit.
Cable limit curves are based on the thermal inertia of the conductor, insulation and surrounding material. As a result, it can take from 1 to 6 hours for the temperature of a cable to
stabilize after a change in load current. Therefore, under these emergency operating conditions, currents much greater than the rated ampacity can be supported. Tables 2 and 3
provide factors and percent overload capability for various installations.
K Factors
http://www.skm.com/applicationguides4.html 12/9/2014
SKM Systems Analysis, Inc. - Power System Software and Arc Flash Hazard Analysis an... Page 2 of 4
Similar methods exist to determine the limit curve for bare overhead conductor applications, but are not covered in this guide.
Emergency overload curves are typically not shown on a TCC. However, when shown, are plotted in the upper 2 decades of the TCC.
Curve that describes the conductor short circuit current operating limit, which if exceeded, will damage the conductor insulation. The curve is calculated assuming all heat is
absorbed by the conductor metal, with no heat transmitted from the conductor to the insulation.
Separate equations are given for copper and aluminum cables. Both equations relate conductor temperature rise to conductor size, fault current magnitude and fault duration.
Insulated copper conductors
For bare conductors the short circuit damage temperature limit is much higher than those listed for insulated conductors. In this case the curve describes the conductor short circuit
current operating limit at which the maximum acceptable loss in conductor mechanical strength is reached. Therefore, if this limit is exceeded, the conductor will be damaged.
For bare stranded aluminum conductors the upper temperature limit is 340ºC (300ºrise over a 40ºC ambient). For bare stranded ACSR conductors the upper temperature limit is
645ºC (605ºrise over a 40ºC ambient).
t = (0.0671A/I)2 (3)
t = (0.0862A/I)2 (4)
where:
Example 1
Plot the conductor landmarks for 3-1/C, 500kCM, THWN copper cables installed in metallic conduit on a 480V distribution system.
Solution
http://www.skm.com/applicationguides4.html 12/9/2014
SKM Systems Analysis, Inc. - Power System Software and Arc Flash Hazard Analysis an... Page 3 of 4
10 2197 8,348
A = 500,000 cmils
t = time of short circuit – 0.01 to 10 seconds
T1 = 75°C (Table 1)
T2 = 150°C (Table 1)
10.00 8,371
0.01 264,711
Plot the conductor landmarks for 336.4 kCM ACSR conductors installed on a 138kV aerial distribution system.
Solution
FLA from the Electrical Transmission and Distribution Reference Book is 530A
Damage points calculated from (4) using:
http://www.skm.com/applicationguides4.html 12/9/2014
SKM Systems Analysis, Inc. - Power System Software and Arc Flash Hazard Analysis an... Page 4 of 4
A = 336,400 cmils
t = time of short circuit – 0.01 to 10 seconds
10.00 9,170
0.01 289,977
• Aluminum Electrical Conductor Handbook, The Aluminum Association Inc., Washington, D.C., 3rd edition, 1989.
• Electrical Transmission and Distribution Reference Book, ABB Power T&D Company, Raleigh, North Carolina, 1997.
• IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (IEEE Buff Book)