Equipment Damage Curves Generators

The information presented in this application guide is for review, approval, interpretation and application by a registered professional engineer only. SKM disclaims any responsibility
and liability resulting from the use and interpretation of this information.

Reproduction of this material is permitted provided proper acknowledgement is given to SKM Systems Analysis Inc.

Purpose

The purpose of this guide is to provide basic information about generator thermal limit curves and characteristic landmarks necessary for plotting on time-current curves, for the
purpose of equipment overcurrent protection.

Full Load Amps (FLA)

Rated continuous current carrying capacity of a motor at a referenced ambient temperature and allowable temperature rise, see table 1.

Table 1 Generator Temperature Ratings

Max Amb. Hot Spot Temp. Temp. Total Temp. Insul. Insul.
Temp. Temp. Rise Rise Rise Temp. Temp.
40°C 5°C Class A 60°C 105°C Class A 105°C

40°C 10°C Class B 80°C 130°C Class B 130°C

40°C 10°C Class F 105°C 155°C Class F 155°C

40°C 15°C Class H 125°C 180°C Class H 180°C

40°C 10°C Class B 80°C 130°C Class F 155°C

40°C 15°C Class F 105°C 160°C Class H 180°C

Short-Time Thermal (Overload) Capability Curve

The short time thermal capability or overload curve represents the permissible output capability under emergency conditions. This curve is not meant as an indication of continuous
overload capability, and should never be used to schedule running overload operations. Repeated operation up to and beyond the running overload curve will reduce insulation life.
The short-time thermal capability of cylindrical rotor generators as defined in ANSI C37.50 is listed in Table 2.

Table 2 Shot-time thermal capability

Time (sec.) 10 30 60 120

<#2 AWG 226 154 130 116

Short Circuit Withstand Capability Point

The short circuit withstand capability point represents the maximum time the machine can withstand a 3-Øshort circuit at its terminals without damage when operating at rated kVA
and power factor, at 5 percent over-voltage, with field excitation.

Decrement Curve

The decrement curve represents the current output of the machine considering a 3-Øfault applied at or near its terminals. The current output is defined by the following equations.

http://www.skm.com/applicationguides5.html 12/9/2014
SKM Systems Analysis, Inc. - Power System Software and Arc Flash Hazard Analysis an... Page 2 of 4

Example

Plot the characteristic landmarks for a 750kVA, 480V, 902A synchronous generator with the following characteristics.

Xd” = 0.107 Ωp.u., Xd’= 0.154 Ωp.u., Xd = 1.54 Ωp.u.


Td” = 0.015 sec., Td’= 0.417 sec., Ta = 0.189 sec.
If = 3 A p.u., Ifg = 1 A p.u.

Solution

In the submittal package from the generator manufacturer the overload capability at rated operating (hot) temperature is listed as

Current (%) Time (sec.)

1.45 1080.0

1.65 420.0

2.00 180.0

The manufacturer also lists a sustained short circuit capability of 300% line current for 5 seconds. The decrement curve will be calculated using equation (1) from 0.01 to 5 seconds.

Time(sec.) C DC Total

10.00 7.9 12.5 14.8

0.01 5.8 7.8 9.7

0.2 5.2 4.6 7.0

0.4 4.5 1.6 4.7

0.6 4.0 0.6 4.0

0.8 3.7 0.2 3.7

1.0 3.5 0.1 3.5

2.0 3.2 0.0 3.2

3.0 3.2 0.0 3.2

4.0 3.2 0.0 3.2

5.0 3.2 0.0 3.2

The results are plotted in figure 1.

http://www.skm.com/applicationguides5.html 12/9/2014
SKM Systems Analysis, Inc. - Power System Software and Arc Flash Hazard Analysis an... Page 3 of 4

Fig. 1 750kVA generator damage curves


References

• Other Application Guides offered by SKM Systems Analysis at www.skm.com


• Electrical Transmission and Distribution Reference Book, ABB Power T&D Company, Raleigh, North Carolina, 1997
• Protective Relaying Theory and Applications, 2nd Edition, Marcel Dekker, New York, 2004

The latest revision of:

• IEEE Std 242, IEEE Recommended Practice for Protection and Coordination of Industrial and Commercial Power Systems (IEEE Buff Book)
• IEEE Std C37.102, IEEE Guide for AC Generator Protection
• IEEE Std C37.101, IEEE Guide for Generator Ground Protection
• ANSI C50.13, Cylindrical-Rotor Synchronous Generators
• NEMA MG-1, Motors and Generators

Insulating Materials

Insulation Class Maximum Temperature Insulating Materials


Cotton, silk, paper, wood, cellulose, fibre
Y 90°C
without impregnation or oil-immersion
Class Yimpregnated with natural resins,
A 105°C cellulose esters, insulating oils, etc., also
laminated wood, varnished paper
Insuldur® Insulation Kraft paper with epoxy
Hybrid A 110°C
binders activated under pressure
Synthetic-resin enamels, cotton and paper
E 120°C
Laminates with formaldehyde bonding
Mica, glass fibre, asbestos, etc., with
B 130°C suitable bonding substance;built-up mica,
glass-fibre and asbestos laminates
The materials of Class B with more
F 155°C
thermally-resistant bonding materials
Glass-fibre and asbestos materials, and built
H 180°C
-up mica, with appropriate Silicone resins
Mica, ceramics, glass, quartz, and asbestos
C >180°C without binders or with silicone resins of
superior thermal stability
NOMEX® insulation, varnish dipped and
Hybrid H 220°C
vacuum pressure impregnated (VPI)

http://www.skm.com/applicationguides5.html 12/9/2014
SKM Systems Analysis, Inc. - Power System Software and Arc Flash Hazard Analysis an... Page 4 of 4

back to Application guides

Home Products Support Downloads Training Contact Customer Service Career Opportunities Distributors

© Copyright 2012. SKM Systems Analysis Inc. All rights reserved.

http://www.skm.com/applicationguides5.html 12/9/2014

You might also like