Professional Documents
Culture Documents
Overcurrent Relays Directional OC Relays Voltage Relays Differential Relays Pilot Protection
Impedance relays are used whenever overcurrent relays do not provide adequate protection. They
function even if the short circuit current is relatively low. The speed of operation is independent of
current magnitude.
Impedance relays monitor the impedance between the relay location and the fault. If the impedance falls
within the relay setting, the relay will operate. The basic construction for impedance relays on which the
principle of operation is easily explained is the balanced beam.
The relay consists of a balanced beam. At each end of the balanced beam is a coil that exerts a force on
the beam at that end. One coil is connected to a current from a current transformer, the other coil is
connected to a potential transformer. The voltage coil functions as a restraining coil, the current coil
functions as an operating coil. Under normal conditions, the contact of the relay is kept open. During a
fault, the voltage drops, and the current rises. The torque due to the current coil overpowers the torque
due to the voltage coil, and the relay closes its contact.
The ratio of voltage and current is the impedance the relay detects at the point of its connection.
The contacts will close anytime the impedance the relay sees is less than a preset value given by
This type of impedance relay is not directional. It will detect a fault in any direction. If it is used, it is used
together with a directional relay that eliminates half of its characteristic.
Offset impedance relay is also known under names ADMITTANCE RELAY or MHO RELAY
Phasor Diagram
Relay operates if
The phase angle θ depends on impedance Zs . Zs can be chosen so that θ = 0. Also, both voltage coils are
It follows that
Similarly as for the impedance relay, this impedance can be represented by an X vs R graph. This time
the circle is offset from the center.
Figure: Operating Diagram for an Offset Impedance Relay with Characteristic Angle equal to 0
Figure: Operating Diagram for an Offset Impedance Relay with Characteristic Angle Different from 0
For impedance relays detecting short circuits on transmission lines, impedance Zs is chosen so that θ is
the same as the impedance angle of the line. This relay will detect a fault in only one direction.
Relay operates if
The phase angle θ depends on impedance Zs . Zs can be chosen so that θ = 0. Also, both current coils are
connected to the same current I.
It follows that
All distance relays are connected to the power system through instrument transformers. The relay
monitors the impedance in secondary ohms. Secondary ohms are related to the primary ohms by the
equation
Zones of Protection
In general, distance protection includes three steps of protection, with each step reaching a fixed preset
distance and operating in a preset time.
Zone 2 extends beyond the protected line up to about 50% of the adjacent line. The tripping has a time
delay, usually set to a value between 0.3 s to 0.5 s.
Zone 3 covers the protected line, the adjacent line, and up to 25% of the line next to the adjacent line.
Tripping is delayed between 0.6 s to 1.0 s.
Overcurrent Relays Directional OC Relays Voltage Relays Differential Relays Pilot Protection