RESIDENTIAL BUILDING DESIGN

A.Y. 2023 - 2024


DESIGN COMPUTATION OR ANALYSIS ( GROUND FLOOR)

LIGHTNING & CONVENIENCE RECEPTACLE LOAD: (SEE SEC. 2.20.3.23, PEC-2017)


44.20 sq. m x 24 VA/sq.m =1061VA
VOLT – AMPERE ACTUAL LOAD
PROVIDE 5-15A and 3-20A FOR LIGHTING
& CONVENIENCE RECEPTACLE CIRCUITS

COOKING LOAD: (SEE SECTION 2.20.3.16, PEC - 2017)


ONE-12KW ELECTRICAL RANGE W/OVEN
(SEE TABLE 2.20.3.16, COLUMN C, PEC – 2017)
PROVIDE 1- 40A ELECTRICAL RANGE CIRCUIT

TOTAL LOAD: =6400VA

ONE-800W MICROWAVE OVEN


(SEE TABLE 2.20.3.16, COLUMN C, PEC – 2017) =1500VA
PROVIDE 1- 30A ELECTRICAL RANGE CIRCUIT

TOTAL LOAD: =7900VA

OTHER LOADS:
ONE-800W REFRIGERATOR: =1500VA
PROVIDE 1-30A REFRIGERATOR CIRCUIT

ONE-800W WASHING MACHINE: =1500VA


PROVIDE 1-30A REFRIGERATOR CIRCUIT

TOTAL OTHER LOADS: =4500VA

Application of Demand Factor:


3000volt-amperes x 0.40 =1200VA

TOTAL NET COMPUTED LOAD:


(6,400+ 7,900 + 1,200 )VA =15,500VA

CIRCUIT REQUIREMENTS:
USE 5-15A 2-WIRE BRANCH CIRCUITS, 3 - 20A 2-WIRE BRANCH CIRCUITS

SERVICE FEEDER CONDUCTORS:


TOTAL FULL LOAD CURRENT: (SEE SECTION 4.30.2.4 AND 4.40.17)
[15,500VA + 25%(1500VA)]/230V = 69.02A

USE TWO 30MM2 THHN WIRES.

SERVICE EQUIPMENT:
(A) MAXIMUM CURRENT RATING OF PROTECTIVE DEVICE

DESIGN ANALYSIS CALCULATION 1


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
(SEE SECTION 4.30.4.2 AND TABLE 4.30.4.2)
(1) NONTIME DELAY FUSE
[300%(1500) +6,400+ 7,900 + 1,200] / 230V =86.96A

(2) INVERSE TIME CIRCUIT BREAKER


[250%(1500) +6,400+ 7,900 + 1,200] / 230V =83.69A

(B) SERVICE EQUIPMENT RATING


USE ONE 100 – AMPERE, 2PST, 250V SAFETY SWITCH WITH 1 – 100A FUSE OR
USE 1 – 100A TRIP , 2 POLE 240 – VOLT 10 KAIC MOLDED CASE CIRCUIT
BREAKER (SEE SECTION 2.40.1.6, PEC 2017).

DESIGN COMPUTATION OR ANALYSIS ( SECOND FLOOR)

AIR CONDITIONING LOAD: (SEE SEC. 2.20.3.23 & TABLE 4.30.14.2, PEC-2017)
ONE 1HP ROOM AIR CONDITIONING UNIT
12A x 230V x 3 =8,280VA
PROVIDE 4-30A ROOM ACU CIRCUIT

TOTAL LOAD: =8,280VA

LIGHTNING & CONVENIENCE RECEPTACLE LOAD: (SEE SEC. 2.20.3.23, PEC-2017)


44.60 sq. m x 24 VA/sq.m =1071VA
VOLT – AMPERE ACTUAL LOAD
PROVIDE 4-15A and 4-20A FOR LIGHTING
& CONVENIENCE RECEPTACLE CIRCUITS

OTHER LOADS:

ONE- WATER HEATER OUTLET @1500VA


3 x 1500VA =4500VA
PROVIDE 3-30A WATER HEATER CIRCUIT

TOTAL OTHER LOADS: =4500VA

Application of Demand Factor:


4500volt-amperes x 0.40 =1800VA

TOTAL NET COMPUTED LOAD:


(8,280+ 1071 + 1,800 )VA =11,151VA

CIRCUIT REQUIREMENTS:
USE 4-15A 2-WIRE BRANCH CIRCUITS, 4 - 20A 2-WIRE BRANCH CIRCUITS, 6 - 30A 2 -
WIRE BRANCH CIRCUITS

DESIGN ANALYSIS CALCULATION 2


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
SERVICE FEEDER CONDUCTORS:
TOTAL FULL LOAD CURRENT: (SEE SECTION 4.30.2.4 AND 4.40.17)
[11,151VA + 25%(2760VA)]/230V = 51.48A

USE TWO 30MM2 THHN WIRES.

SERVICE EQUIPMENT:
(C) MAXIMUM CURRENT RATING OF PROTECTIVE DEVICE
(SEE SECTION 4.30.4.2 AND TABLE 4.30.4.2)
(3) NONTIME DELAY FUSE
[300%(2760) + 11,040+ 6,260 + 1,200 ] / 230V =84.48A

(4) INVERSE TIME CIRCUIT BREAKER


[250%(2760) + 11,040+ 6,260 + 1,200 ] / 230V =78.48A

(D) SERVICE EQUIPMENT RATING


USE ONE 100 – AMPERE, 2PST, 250V SAFETY SWITCH WITH 1 – 100A FUSE OR
USE 1 – 100A TRIP , 2 POLE 240 – VOLT 10 KAIC MOLDED CASE CIRCUIT
BREAKER (SEE SECTION 2.40.1.6, PEC 2017).

MAIN SERVICE FEEDER CONDUCTORS:


TOTAL FULL LOAD CURRENT: (SEE SECTION 4.30.2.4 AND 4.40.17)
[11,151VA+ 15,500VA + 25%(2760VA)]/230V = 118.87A

USE TWO 60 MM2 THHN WIRES.

MAIN SERVICE EQUIPMENT:


(E) MAXIMUM CURRENT RATING OF PROTECTIVE DEVICE
(SEE SECTION 4.30.4.2 AND TABLE 4.30.4.2)
(5) NONTIME DELAY FUSE
[300%(2760) + 26651 ] / 230V =151.87A

(6) INVERSE TIME CIRCUIT BREAKER


[250%(2760) +26651 ] / 230V =145.87A

(F) SERVICE EQUIPMENT RATING


USE ONE 200 – AMPERE, 2PST, 250V SAFETY SWITCH WITH 1 – 200A FUSE OR
USE 1 – 200A TRIP , 2 POLE 240 – VOLT 10 KAIC MOLDED CASE CIRCUIT
BREAKER (SEE SECTION 2.40.1.6, PEC 2017)

DESIGN ANALYSIS CALCULATION 3


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
VOLTAGE DROP CALCULATION

1. VOLTAGE DROP AT MAIN DISTRIBUTION PANELBOARD

CONDUCTOR SIZE : 60mm2 COPPER WIRE


LENGTH : 20m
RESISTANCE (R) : 0.10ohm/305m
INDUCTIVE REACTANCE (XL) : 0.043ohm/305m
CURRENT (I) : 118.87A
SOLUTION:
L 20
VDL-L = 2(I × √R2 + XL2 × 305) = 2(118.87 × √0.102 + 0.0432 × 305) = 1.70V
VD 1.70
%VD = × 100 = × 100 = 0.74%
V 230

2. VOLTAGE DROP AT DISTRIBUTION PANEL BOARD (DP1)

CONDUCTOR SIZE : 30mm2 COPPER WIRE


LENGTH : 4m
RESISTANCE (R) : 0.19ohm/305m
INDUCTIVE REACTANCE (XL) : 0.045ohm/305m
CURRENT (I) : 69.02A
SOLUTION:
L 4
VDL-L = 2(I × √R2 + XL2 × ) = 2(93.97 × √0.192 + 0.0452 × ) + 1.70 = 2.05V
305 305
VD 2.05
%VD = V
× 100 = 230
× 100 = 0.89%

3. VOLTAGE DROP AT DISTRIBUTION PANEL BOARD (DP2)

CONDUCTOR SIZE : 30mm2 COPPER WIRE


LENGTH : 4m
RESISTANCE (R) : 0.19ohm/305m
INDUCTIVE REACTANCE (XL) : 0.045ohm/305m
CURRENT (I) : 51.48A
SOLUTION:
L 4
VDL-L = 2(I × √R2 + XL2 × ) = 2(51.48 × √0.192 + 0.0452 × )+ 1.70 = 1.96V
305 305
VD 1.96
%VD = × 100 = × 100 = 0.85%
V 230

DISTRIBUTION PANEL 1

1. VOLTAGE DROP AT LIGHTING OUTLET (C1)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 13.37m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 1.00A
SOLUTION:

VOLTAGE DROP CALCULATION 1


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
L 13.37
VDL-L = 2(I × √R2 + XL2 × 305
) = 2 (1.00 × √3.12 + 0.0582 × 305
)+ 2.05 = 2.32V
VD 2.32
%VD = V
×
100 = 230
×
100 = 1.00%
2. VOLTAGE DROP AT LIGHTING OUTLET (C2)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 12.00m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 1.30A
SOLUTION:
L 13.37
VDL-L = 2(I × √R2 + XL2 × 305) = 2 (1.00 × √3.12 + 0.0582 × 305 ) + 2.05 = 2.37V
VD 2.37
%VD = × 100 = × 100 = 1.03%
V 230

3. VOLTAGE DROP AT LIGHTING OUTLET (C3)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 14.00m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 1.39A
SOLUTION:
L 20.85
VDL-L = 2(I × √R2 + XL2 × 305) = 2(1.39 × √3.12 + 0.0582 × 305 ) + 2.05 = 2.45V
VD 2.45
%VD = × 100 = × 100 = 1.06%
V 230

4. VOLTAGE DROP AT LIGHTING OUTLET (C4)


CONDUCTOR SIZE : 2.0mm2 COPPER WIRE
LENGTH : 20.52m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 0.65A
SOLUTION:
L 20.52
VDL-L = 2(I × √R2 + XL2 × 305) = 2 (0.65 × √3.12 + 0.0582 × 305 ) + 2.05 = 2.32V
VD 2.32
%VD = V
× 100 = 230
× 100 = 1.00%

5. VOLTAGE DROP AT LIGHTING OUTLET (C5)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 16.20m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 2.26A
SOLUTION:
L 21.47
VDL-L = 2(I × √R2 + XL2 × 305) = 2(2.26 × √3.12 + 0.0582 × 305 ) + 2.05 = 2.79V

VOLTAGE DROP CALCULATION 2


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
VD 2.79
%VD = V
× 100 = 230
× 100 = 1.21%

6. VOLTAGE DROP AT CONVENIENCE OUTLET (C6)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 12.12m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 3.13A
SOLUTION:
L 12.12
VDL-L = 2(I × √R2 + XL2 × 305) = 2(3.13 × √22 + 0.0542 × 305 ) + 2.05 = 2.55V
VD 2.55
%VD = × 100 = × 100 = 1.11%
V 230

7. VOLTAGE DROP AT CONVENIENCE OUTLET (C7)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 11.18m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 3.13A
SOLUTION:
L 11.18
VDL-L = 2(I × √R2 + XL2 × ) = 2(3.13 × √22 + 0.0542 × ) + 2.05 = 2.51V
305 305
VD 2.51
%VD = × 100 = × 100 = 1.09%
V 230

8. VOLTAGE DROP AT CONVENIENCE OUTLET (C8)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 12.10m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 4.70A
SOLUTION:
L 12.10
VDL-L = 2(I × √R2 + XL2 × 305) = 2(4.70 × √22 + 0.0542 × 305 ) + 2.05 = 2.80V
VD 2.80
%VD = × 100 = × 100 = 1.22%
V 230

9. VOLTAGE DROP AT REFRIGERATOR OUTLET (C9)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE

VOLTAGE DROP CALCULATION 3


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
LENGTH : 10.85
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 6.52A
SOLUTION:
L 10.85
VDL-L = 2(I × √R2 + XL2 × 305) = 2(6.52 × √22 + 0.0542 × 305 ) + 2.05 = 2.98V
VD 2.98
%VD = V
× 100 = 230
× 100 = 1.29%

10. VOLTAGE DROP AT MICROWAVE OVEN OUTLET (C10)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 12.10m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 6.52A
SOLUTION:
L 12.10
VDL-L = 2(I × √R2 + XL2 × ) = 2(6.26 × √22 + 0.0542 × ) + 2.05 = 3.60V
305 305
VD 3.60
%VD = V
× 100 = 230
× 100 = 1.57%

11. VOLTAGE DROP AT WASHING MACHINE OUTLET (C11)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 13.06m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 6.52A
SOLUTION:
L 13.06
VDL-L = 2(I × √R2 + XL2 × 305) = 2(6.52 × √22 + 0.0542 × 305 ) +2.05 = 3.17V
VD 3.17
%VD = × 100 = × 100 = 1.38%
V 230

12. VOLTAGE DROP AT RANGE OUTLET (C12)

CONDUCTOR SIZE : 8.0mm2 COPPER WIRE


LENGTH : 10.15m
RESISTANCE (R) : 0.78ohm/305m
INDUCTIVE REACTANCE (XL) : 0.052ohm/305m
CURRENT (I) : 27.83A
SOLUTION:
L 10.15
VDL-L = 2(I × √R2 + XL2 × ) = (27.83 × √0.782 + 0.0522 × ) + 2.05 = 3.45V
305 305
VD 3.45
%VD = V
× 100 = 230
× 100 = 1.52%

VOLTAGE DROP CALCULATION 4


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024

DISTRIBUTION PANEL 2

1. VOLTAGE DROP AT LIGHTING OUTLET (C1)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 13.37m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 1.74A
SOLUTION:
L 13.37
VDL-L = 2(I × √R2 + XL2 × 305) = 2 (1.74 × √3.12 + 0.0582 × 305 ) + 1.70 = 2.43V
VD 2.43
%VD = V
× 100 = 230
× 100 = 1.05%

2. VOLTAGE DROP AT LIGHTING OUTLET (C2)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 18.18m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 2.07A
SOLUTION:
L 18.18
VDL-L = 2(I × √R2 + XL2 × 305) = 2 (2.07 × √3.12 + 0.0582 × 305 ) + 1.96 = 2.73V
VD 2.73
%VD = V
× 100 = 230
× 100 = 1.19%

3. VOLTAGE DROP AT LIGHTING OUTLET (C3)

CONDUCTOR SIZE : 2.0mm2 COPPER WIRE


LENGTH : 10.85m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m
CURRENT (I) : 1.30A
SOLUTION:
L 10.85
VDL-L = 2(I × √R2 + XL2 × 305) = 2(1.30 × √3.12 + 0.0582 × 305 ) + 1.96 = 2.25V
VD 2.25
%VD = V
× 100 = 230
× 100 = 0.98%

4. VOLTAGE DROP AT LIGHTING OUTLET (C4)


CONDUCTOR SIZE : 2.0mm2 COPPER WIRE
LENGTH : 18.63m
RESISTANCE (R) : 3.1ohm/305m
INDUCTIVE REACTANCE (XL) : 0.058ohm/305m

VOLTAGE DROP CALCULATION 5


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
CURRENT (I) : 1.30A
SOLUTION:
L 18.63
VDL-L = 2(I × √R2 + XL2 × 305) = 2(1.30 × √3.12 + 0.0582 × 305 ) + 1.96 = 2.45V
VD 2.45
%VD = × 100 = × 100 = 1.065%
V 230

5. VOLTAGE DROP AT CONVENIENCE OUTLET (C5)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 21.18m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 6.26A
SOLUTION:
L 21.18
VDL-L = 2(I × √R2 + XL2 × 305) = 2(6.26 × √22 + 0.0542 × 305 ) + 1.96 = 3.70V
VD 3.70
%VD = V
× 100 = 230
× 100 = 1.61%

6. VOLTAGE DROP AT CONVENIENCE OUTLET (C6)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 22.12m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 4.70A
SOLUTION:
L 22.12
VDL-L = 2(I × √R2 + XL2 × ) = 2(4.70 × √22 + 0.0542 × ) + 1.96 = 3.32V
305 305
VD 3.32
%VD = V
× 100 = 230
× 100 = 1.45%

7. VOLTAGE DROP AT CONVENIENCE OUTLET (C7)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 20.07m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 3.13A
SOLUTION:
L 20.07
VDL-L = 2(I × √R2 + XL2 × 305) = 2(3.13 × √22 + 0.0542 × 305 ) + 1.96 = 2.78V
VD 2.78
%VD = V
× 100 = 230
× 100 = 1.21%

8. VOLTAGE DROP AT CONVENIENCE OUTLET (C8)

CONDUCTOR SIZE : 3.5mm2 COPPER WIRE


LENGTH : 21.18m
RESISTANCE (R) : 2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.054ohm/305m
CURRENT (I) : 4.70A

VOLTAGE DROP CALCULATION 6


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
SOLUTION:
L 21.18
VDL-L = 2(I × √R2 + XL2 × 305) = 2(4.70 × √22 + 0.0542 × 305 ) + 1.96 = 3.27V
VD 3.27
%VD = V
× 100 = 230
× 100 = 1.42%

9. VOLTAGE DROP AT WATER HEATER (C9)

CONDUCTOR SIZE : 5.5mm2 COPPER WIRE


LENGTH : 11.86m
RESISTANCE (R) : 1.2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.050ohm/305m
CURRENT (I) : 6.52A
SOLUTION:
L 11.86
VDL-L = 2(I × √R2 + XL2 × 305) = 2(6.52 × √1.22 + 0.0502 × 305 ) + 1.96 = 2.57V
VD 2.57
%VD = × 100 = × 100 = 1.12%
V 230

10. VOLTAGE DROP AT WATER HEATER (C10)

CONDUCTOR SIZE : 5.5mm2 COPPER WIRE


LENGTH : 18.60m
RESISTANCE (R) : 1.2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.050ohm/305m
CURRENT (I) : 6.52A
SOLUTION:
L 18.60
VDL-L = 2(I × √R2 + XL2 × 305) = 2(6.52 × √1.22 + 0.0502 × 305 ) + 1.96 = 2.92V
VD 2.92
%VD = V
× 100 = 230
× 100 = 1.27%

11. VOLTAGE DROP AT WATER HEATER (C11)

CONDUCTOR SIZE : 5.5mm2 COPPER WIRE


LENGTH : 16.80m
RESISTANCE (R) : 1.2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.050ohm/305m
CURRENT (I) : 6.52A
SOLUTION:
L 16.80
VDL-L = 2(I × √R2 + XL2 × ) = 2(6.52 × √1.22 + 0.0502 × ) + 1.96 = 2.82V
305 305
VD 2.82
%VD = V
× 100 = 230
× 100 = 1.23%

12. VOLTAGE DROP AT AIR CONDITIONING UNIT (C12)

CONDUCTOR SIZE : 5.5mm2 COPPER WIRE


LENGTH : 15.20m
RESISTANCE (R) : 1.2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.050ohm/305m

VOLTAGE DROP CALCULATION 7


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024
CURRENT (I) : 12A
SOLUTION:
L 15.20
VDL-L = 2(I × √R2 + XL2 × 305) = 2(12 × √1.22 + 0.0502 × 305 ) + 1.96 = 3.39V
VD 3.40
%VD = × 100 = × 100 = 1.48%
V 230

13. VOLTAGE DROP AT AIR CONDITIONING UNIT (C13)

CONDUCTOR SIZE : 5.5mm2 COPPER WIRE


LENGTH : 16.00m
RESISTANCE (R) : 1.2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.050ohm/305m
CURRENT (I) : 12A
SOLUTION:
L 16.00
VDL-L = 2(I × √R2 + XL2 × 305) = 2(12 × √1.22 + 0.0502 × 305 ) + 1.96 = 3.47V
VD 3.47
%VD = V
× 100 = 230
× 100 = 1.43%

14. VOLTAGE DROP AT AIR CONDITIONING UNIT (C14)

CONDUCTOR SIZE : 5.5mm2 COPPER WIRE


LENGTH : 14.20m
RESISTANCE (R) : 1.2ohm/305m
INDUCTIVE REACTANCE (XL) : 0.050ohm/305m
CURRENT (I) : 12A
SOLUTION:
L 14.20
VDL-L = 2(I × √R2 + XL2 × ) = 2(12 × √1.22 + 0.0502 × ) + 1.96 = 3.30V
305 305
VD 3.30
%VD = V
× 100 = 230
× 100 = 1.44%

VOLTAGE DROP CALCULATION 8


RESIDENTIAL BUILDING DESIGN
A.Y. 2023 - 2024

Transformer Full Load Ampere (IFL)

IFL = KVA Rating x 1000 /EL−N


IFL = (75KVA x 1,000)/230
IFL = 326.10 Amperes

Transformer Multiplier, M.

M = 100 / % Z
M = 100/2.4
M = 41.67

Short Circuit Current of the Transformer,ISCT.

ISCT = IFL x M
ISCT = 326.10 x 41.67
ISCT = 13,586.96 Amperes

Calculate for the value of factor “f”.

f = (2 x L x ISC) / (c x n x EL−N)
f = (2 x L x ISC) /(c x n x EL−N )
f = (2 x 65.62 x 13,586.96) /(18594 x 2 x 230)
f = 0.104

Multiplier of the system , M2 .

M2 = 1/ (1 + f )
M2 = 1/1 + 0.104
M2 = 0.91

Short Circuit Symmetrical RMS current at the point of fault.

ISC sym rms = ISC x M2


ISC sym rms = 13,586.96 x 0.91
ISC sym rms = 12,304.37 Amperes

Therefore Use : 250AT, 250AF, 2P, 230V, 60Hz, 15kAIC Molded Case Circuit Breaker
Minimum Current Interrupting Capacity: 15kAIC

VOLTAGE DROP CALCULATION 1


BECHAYDA’S RESIDENTIAL
DESIGN ESTIMATE FOR RESIDENTIAL BUILDING

SERVICE ENTRANCE

Service Entrance Conductor = 20m of 60 mm2 THHN Copper Wire


Service Entrance Conduit = 20/3 = 7pcs. 63mm Ø PVC Pipe

SERVICE ENTRANCE - DP1

Distribution Panel Conductor = 4m of 30 mm2 THHN Copper Wire


Distribution Panel Conduit = 4/3 = 2pcs. 32mm Ø PVC Pipe

C1 – LIGHTING OUTLET

Lighting Outlet Conductor = 26.74m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 13.37/3 = 5 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 10 pcs.
No. of Utility Box = 3 pcs
Circuit Breaker = 15A, 2P, 230V

C2 – LIGHTING OUTLET

Lighting Outlet Conductor = 37.83m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 12/3 = 4 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 5 pcs.
No. of Utility Box = 1 pc.
Circuit Breaker = 15A, 2P, 230V

C3 – LIGHTING OUTLET

Lighting Outlet Conductor = 31.07m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 14/3 = 5 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 16 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V

C4 – LIGHTING OUTLET

Lighting Outlet Conductor = 46.40m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 20.52/3 = 7 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 1 pcs.
Circuit Breaker = 15A, 2P, 230V

C5 – LIGHTING OUTLET

Lighting Outlet Conductor = 64.41m of 2.0mm2 THHN Copper Wire


Lighting Outlet Conduit = 16.20/3 = 6pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 16 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V
ESTIMATE | 1
BECHAYDA’S RESIDENTIAL
C6 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 64.41m of 3.5mm2 THHN Copper Wire


Convenience Outlet Conduit = 12.12/3 = 5 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1 pcs.
No. of Utility Box = 4 pcs.
Circuit Breaker = 20A, 2P, 230V

C7 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 32.16m of .3.5mm2 THHN Copper Wire


Convenience Outlet Conduit = 11.18/3 = 4 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1 pc.
No. of Utility Box = 4 pcs.
Circuit Breaker = 20A, 2P, 230V

C8 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 32.09m of 3.5mm2 THHN Copper Wire


Convenience Outlet Conduit = 21.18/3 = 5 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 6 pc.
Circuit Breaker = 20A, 2P, 230V

C9 – REF OUTLET

Ref Outlet Conductor = 24.55m of 3.5mm2 THHN Copper Wire


Ref Outlet Conduit = 10.85/3 = 4 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 20A, 2P, 230V

C10 – OVEN OUTLET

Oven Outlet Conductor= 39.13m of 3.5mm2 THHN Copper Wire


Oven Outlet Conduit= 12.10/3 = 8 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C11 – WASHING MACHINE OUTLET

Washing Machine Outlet Conductor= 30.45m of 8.0mm2 THHN Copper Wire


Washing Machine Outlet Conduit= 10.15/3 = 4 pcs. – 25mm Ø PVC Pipe
No. of Junction Box = 1pc.
ESTIMATE | 2
BECHAYDA’S RESIDENTIAL
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C12 – RANGE OUTLET

Range Outlet Conductor= 30.45m of 8.0mm2 THHN Copper Wire


Range Outlet Conduit= 10.15/3 = 4 pcs. – 25mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

SERVICE ENTRANCE - DP2

Distribution Panel Conductor = 4m of 30 mm2 THW Copper Wire


Distribution Panel Conduit = 4/3 = 2pcs. 32mm Ø PVC Pipe

C1 – LIGHTING OUTLET

Lighting Outlet Conductor = 62.73m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 13.37/3 = 5 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 8 pcs.
No. of Utility Box = 3 pc
Circuit Breaker = 15A, 2P, 230V

C2 – LIGHTING OUTLET

Lighting Outlet Conductor = 34.54m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 18.18/3 = 7 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 2 pcs.
Circuit Breaker = 15A, 2P, 230V

C3 – LIGHTING OUTLET

Lighting Outlet Conductor = 32.55m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 10.85/3 = 7 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 11 pcs.
No. of Utility Box = 1 pcs.
Circuit Breaker = 15A, 2P, 230V

C4 – LIGHTING OUTLET

Lighting Outlet Conductor = 15.89m of 2.0 mm2 THHN Copper Wire


Lighting Outlet Conduit = 18.63/3 = 7 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 6 pcs.
No. of Utility Box = 3 pcs.
Circuit Breaker = 15A, 2P, 230V

ESTIMATE | 3
BECHAYDA’S RESIDENTIAL
C5 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 64.41m of 3.5 mm2 THHN Copper Wire


Convenience Outlet Conduit = 21.18/3 = 8pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 5 pcs.
No. of Utility Box = 1 pcs.
Circuit Breaker = 20A, 2P, 230V

C6 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 34.41m of 3.5 mm2 THHN Copper Wire


Convenience Outlet Conduit = 22.12/3 = 8 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1 pcs.
No. of Utility Box = 5 pcs.
Circuit Breaker = 20A, 2P, 230V

C7 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 31.36m of 3.5mm2 THHN Copper Wire


Convenience Outlet Conduit = 20.07/3 = 8 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 6 pc.
Circuit Breaker = 20A, 2P, 230V

C8 – CONVENIENCE OUTLET

Convenience Outlet Conductor = 31.36m of 3.5mm2 THHN Copper Wire


Convenience Outlet Conduit = 21.18/3 = 8 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 6 pc.
Circuit Breaker = 20A, 2P, 230V

C9 – SPECIAL PURPOSE OUTLET (S.P.O) (WH)

S.P.OCONDUCTOR = 66.3m of 5.5mm2 THHN Copper Wire


S.P.OCONDUIT = 16.81/3 = 8 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C10 – SPECIAL PURPOSE OUTLET (S.P.O) (WH)

S.P.OCONDUCTOR = 66.3m of 5.5mm2 THHN Copper Wire


S.P.OCONDUIT = 15.20/3 = 8 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C11 – SPECIAL PURPOSE OUTLET (S.P.O) (WH)


ESTIMATE | 4
BECHAYDA’S RESIDENTIAL
S.P.OCONDUCTOR = 30.45m of 5.5mm2 THHN Copper Wire
S.P.OCONDUIT = 16/3 = 4 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C12 – SPECIAL PURPOSE OUTLET (S.P.O) (ACU)

S.P.OCONDUCTOR = 47.82m of 5.5mm2 THHN Copper Wire


S.P.OCONDUIT = 15.20/3 = 6 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C13 – SPECIAL PURPOSE OUTLET (S.P.O) (ACU)

S.P.OCONDUCTOR =37.71m of 5.5mm2 THHN Copper Wire


S.P.OCONDUIT = 16/3 = 5 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

C14 – SPECIAL PURPOSE OUTLET (S.P.O) (ACU)

S.P.OCONDUCTOR = 46.44m of 5.5mm2 THHN Copper Wire


S.P.OCONDUIT = 14.20/3 = 4 pcs. – 20mm Ø PVC Pipe
No. of Junction Box = 1pc.
No. of Utility Box = 1 pc.
Circuit Breaker = 30A, 2P, 230V

ESTIMATE | 5
BECHAYDA’S RESIDENTIAL
ESTIMATE SHEET FOR RESIDENTIAL

NAME OF COMPANY: TADLONG COMPANY

ADDRESS: PUNTA TABUC, ROXAS CITY, CAPIZ

ESTIMATED BY: ROY MARSON BECHAYDA

COST ANALYSIS

UNIT TOTAL

QUANTITY UNIT DESCRIPTION PRICE PRICE

(PHP) (PHP)

WIRES & CABLE

341.94 m 2.0mm2 THHN 3,200 3,587.57

203.67 m 3.5mm2 THHN 4,200 2,804.64

217.02 m 5.5mm2 THHN 5,700 4,055.78

21.36 m 8.0mm2 THHN 7,450 521.74

21.45 m 14mm2 THHN 9,235 649.48

16 m 30 mm2 THW 10,550 168,800.00

45 m 60 mm2 THW 1157/m 60,750.00

CIRCUIT BREAKER

9 pcs. 15 Amperes 350 3,150.00

12 pcs. 20 Amperes 357 4,284.00

8 pcs. 30 Amperes 369 2,952.00

1 pcs. 40 Amperes 452 452.00

4 pcs. 100 Amperes 1080 4,320.00

1 pcs. 200 Amperes 1500 1,500.00

CASING

1 2 BRANCH CIRCUIT 2300 2,300.00

2 16 BRANCH CIRCUIT 8000 16,000.00

ESTIMATE | 6
BECHAYDA’S RESIDENTIAL
CONDUIT / RACEWAY

138 pcs. 20 mm ɸ PVC 95 13,110.00

6 pcs. 25 mm ɸ PVC 110 660.00

12 pcs. 63 mm ɸ PVC 189 2,268.00

BOXES, FITTINGS & WIRING FIXTURES

48 pcs. 25w lighting bulb 250 12,000.00

1 pcs. 70w Chandelier 950 950.00

63 pcs. 2 x 4 x 2 1/2 in. utility box 26 1,638.00

57 pcs. 4 x 4 x 2 1/2 in. junction box 35 1,995.00

32 set DUPLEX C.O. 221 7,072.00

14 set S.P.O 250 3,500.00

5 set 1 GANG Switch 161 805.00

3 set 2 GANG Switch 238 714.00

7 set 3 GANG Switch 313 2,191.00

MISCELLANEOUS

10 can Solvent Cement 500cc 195 170.00

13 pcs. Electrical Tape 45 112.00

8 pcs. Rubber Tape 120 240.00

5 pcs. Hacksaw Blade 60 120.00

8 kilo #16 GI Wire 40 120.00

TOTAL 323,792.21

ESTIMATE | 7