FOR THE
TWO STOREY RESIDENTIAL BUILDING
PREPARED FOR:
PREPARED BY:
PRC #:
TIN#:
PTR #:
ISSUED AT:
NOTE: Actual computed lighting load shall be used if the total volt-ampere exceeds that
obtained from the 24 volt ampere per square meter method.
NOTE: Actual computed lighting load shall be used if the total volt-ampere exceeds that
obtained from the 24 volt ampere per square meter.
_____________________________ __________________________
Air-conditioning Loads:
_______________________________ ____________________________
Calculating short circuit current during system upgrade and design are life-safety in order to
protect personnel and equipment. It is required to check or select the equipment rating. Hand
calculations can be used for small system. Engineering software is a necessity for large system.
1000
R = 2.41 OHMS/MILE
Z = √R² + (XL-XC) ²
= 2.4585 OHMS/MILE
CONVERSION:
MILE 1600
= 0.0615 OHMS
KV² 1000
0.23²(1000)
Zs= 0.0001
Zt= 0.025
Zw= 0.1163
Fault
= 0.1414 pu
1000
Service Equipment:
= 44.97 Amperes
Use one 60-ampere 2P, 2T, 230 – volt safety switch with two 60-Ampere fuse; or use two 60
ampere trip, 2 poles, 230-volt molded case circuit breaker.
Circuit Requirement:
Note: (Consider conductor and over current protection for ampere rating)
Use: 1- 60 AT/100 AF, 2P, 230V, 60HZ Modified Case Circuit Breaker
Where:
From Handbook:
The Philippine Electrical Code have specified the allowable voltage drop at the maximum load current, 5% for
feeders and 3% for branch circuits