ELECTRICAL DESIGN ANALYSIS

FOR THE
TWO STOREY RESIDENTIAL BUILDING

PREPARED FOR:

CRYSTAL DREAMS DEVELOPMENT CORPORATION

ABUAB ROAD 2, GUITNANG BAYAN 2, SAN MATEO, RIZAL

PREPARED BY:

ENGINEER RAMON T. TALAVERA

PRC #:

TIN#:

PTR #:

ISSUED AT:

TWO STOREY RESIDENTIAL BUILDING DESIGN ANALYSES


TYPICAL TWO STOREY RESIDENTIAL BUILDING (LOAD SCHEDULE)

General Lighting and Convenience Receptacle Load:

61.90 sq.m x 24 volts-amperes per sq = 1,485.60 volt-amperes

Provide two (2) 20-amperes lighting outlets

NOTE: Actual computed lighting load shall be used if the total volt-ampere exceeds that
obtained from the 24 volt ampere per square meter method.

Small Appliance Load:

Provide two (2) 20 amperes for convenience outlets = 3,000 volt-amperes

NOTE: Actual computed lighting load shall be used if the total volt-ampere exceeds that
obtained from the 24 volt ampere per square meter.

_____________________________ __________________________

Sub-Total = 4,485.60 VOLT AMPERES

Application of Demand Factor:

First 3,000 v.a @ 100% Demand Factor = 3,000 volt-amperes

Remainder @ 35% D.F. (1,485.60 x 0.35) = 519.96 volt-amperes

Air-conditioning Loads:

One (1) ACU, 1 HP @100% D.F

Provide one (1) 30-ampere aircon circuit = 1,500 volt-amperes

_______________________________ ____________________________

Total Net Computed Load = 5,019.96 VOLT-AMPERES

TWO STOREY RESIDENTIAL BUILDING DESIGN ANALYSES


SHORT CIRCUIT CURRENT CALCULATIONS:

Calculating short circuit current during system upgrade and design are life-safety in order to
protect personnel and equipment. It is required to check or select the equipment rating. Hand
calculations can be used for small system. Engineering software is a necessity for large system.

From Electrical Plan

Total current = 129.40 amperes

KVA X’former = 31.27 x 230 = 8 kva say 50 kva

1000

USE: #2 – 14.0mm² THHN, 1 – 8.0mm² THHN (G) in 25 mm Dia. RSC

Main Breaker: 60 AT / 100 AF, 2P, 230Volys, 18 KAIC

FAULT CURRENT CALCULATION ANALYSIS:

USING PER UNIT IMPEDANCE METHOD:

GIVEN: 1. AVAILABLE UTILITY SHORT CIRCUIT CAPACITY IS 1000 MVA

2. SELECTED BASE KVA: 50 KVA X’FORMER WITH 15% IMPEDANCE WHERE

LOAD CENTER IS CONNECTED.

SINGLE LINE DIAGRAM:

TWO STOREY RESIDENTIAL BUILDING DESIGN ANALYSES


COMPUTE FOR UTILITY PER UNIT IMPEDANCE puZs

pUzs = KVA BASE = _______50_________ = 0.00005pu

UTILTY SC KVA 1000000

COMPUTE FOR WIRE IMPEDANCE:

FROM STANDARD ELECTRICAL HANDBOOK:

TABLE FOR COPPER WIRE AND CABLE ELECTRICAL CHARACTERISTICS:

NO.8 AWG WIRE (14.0 mm² WIRE)

R = 2.41 OHMS/MILE

XL= 0.628 OHMS/MILE

XC= 0.1419 OHMS/MILE

Z = √R² + (XL-XC) ²

= √2.41² + (0.628 – 0.1419)²

= 2.4585 OHMS/MILE

CONVERSION:

Z=2.4585 OHMS x 1 MILE x 40 METERS

MILE 1600

= 0.0615 OHMS

COMPUTE FOR PER UNIT IMPEDANCE FOR FEEDER puZw

PuZw = IMPEDANCE IN OHMS x KVA BASE

KV² 1000

= 0.0615 x 100 = 0.1163 pu

0.23²(1000)

TWO STOREY RESIDENTIAL BUILDING DESIGN ANALYSES


SIMPLIFIED DIAGRAM:

Zs= 0.0001

Zt= 0.025

Zw= 0.1163

Fault

puZT = puZs + puZt + puZw

= 0.0001 + 0.025 + 0.1163

= 0.1414 pu

Isc (sym) = 1 x KVA BASE = 1 x 100000

puZt 230V 0.1414 230

= 3074.826 AMPERES RMS

KAIC = 3074.826 x 125% SF = 3.8435 KAIC

1000

TWO STOREY RESIDENTIAL BUILDING DESIGN ANALYSES


THEREFORE USE: 15 KAIC MINIMUM RATING FOR MCB OF PANEL BOARD 18 KAIC
RATNG FOR PB BRANCH CIRCUITS

Service Equipment:

(a) Maximum rating/ setting of protective devices


Branch Circuit short – circuit ground fault protective devices

(1) Non- time delay fuse

(3000 VA + 1344 VA + 300% (1500 VA) + 1500 VA / 230 V)

= 44.97 Amperes

(2) Inverse Time circuit breaker

(3000 VA + 1,344 VA + 250% (1500 VA) + 1500 VA / 230 V)

Service Equipment Rating

Use one 60-ampere 2P, 2T, 230 – volt safety switch with two 60-Ampere fuse; or use two 60
ampere trip, 2 poles, 230-volt molded case circuit breaker.

Circuit Requirement:

USE two (2) 20- AMPERE

TWO (1) 20-AMPERE 2- WIRE BRANCH CIRCUITS,

ONE (1) 30- AMPERE 2- WIRE BRANCH CIRCUITS

FOR THE PROVISION AND SPARE CIRCUIT BREAKER;

USE ONE (1) 20- AMPERE 2- WIRE BRANCH CIRCUITS

TWO STOREY RESIDENTIAL BUILDING DESIGN ANALYSES


Service Entrance Conductors:

Total full load current:

(5019.96 VA + 25% (1500 VA) / 230 = 23.456 AMPERES

For main Feeder Wire:

Use 2 – 14.0mm² THHN/THWN, 1 – 8.0mm² THHN/THWN wire (Ground)

In 25mm dia. RSC

For Main Circuit Breaker:

Note: (Consider conductor and over current protection for ampere rating)

Use: 1- 60 AT/100 AF, 2P, 230V, 60HZ Modified Case Circuit Breaker

Voltage Drop Calculations:

Voltage drop: √R² + X²

Where:

I = Line Current in Amperes

R = Line AC Resistance; Ohms

X = Line Reactance at 60 HZ; Ohms

From Handbook:

R (1-PH) = 0.02555 Ohm/305M (75°C) 32mm² Cable in steel conduit

= 1.196 Ohm/305M (75°C) 30mm² Cable in steel conduit

X (1-PH) = 0.0314 Ohm/305M (75°C) 32mm² Cable in steel conduit

= 0.04414 Ohm/305M (75°C) 30mm² Cable in steel conduit

Based on IEEE STD 241-1990

Voltage Drop + 0.48% based on IEEE Std. (REMARKS PASSED)

The Philippine Electrical Code have specified the allowable voltage drop at the maximum load current, 5% for
feeders and 3% for branch circuits