DISTRIBUTION
TRANSFORMER
LINE FROM
SOCOTECO II
2
2-30 MM THW WIRE IN 32 MM
MAIN FEEDER
RSC LEGEND:
CT METER CEILING LIGHT OUTLET
1 1 1 M
CONVENIENCE OUTLET
FUSE
POWER LINE
S2 S2 S2
25MM RSC 25MM RSC 25MM RSC 25MM RSC 25MM RSC 25MM RSC
UP SWITCH LINE
2 2 2
1 1 1
SCHEDULE OF LOADS
SWITCHES
CKT. NO. NO. OF C.O. NO OF L.O. AMPS. VOLTS BREAKER WATTAGE SIZE OF WIRE SIZE OF PIPE
S-1 S-2 S-3
S2 S1 S2 S1 S2 S1 C-1 7 220 1 2
SAFETY SWITCH OR PANEL BOARD
C-2 6 220
C-3 220
C-4 220
C-5
S2 S2 S2 C-6
UP
2 2 2
I = 14.84 + 14.84(0.25)
P = 1600 + 2160 = 3760 W
T I = 18.55A
W
SECOND FLOOR ELECTRICAL LAY-OUT PLAN IST 3000 (100% DF) = 3000 W
SCALE 1: 100 EXCESS 760 (35% DF) = 266 W
3266 W USE 2
2-#14mm THW CU. WIRE IN 25 mm dia, RSC PIPE
2-60 AMP CKT BREAKER 1 0, 220V
PLUG-IN TYPE IN MOLDED CASE
I = 6266 /220 = 14.84 A
PREPARED BY: REG. No.: 2228 PROJECT TITLE/LOCATION: PROJECT OWNER: SHEET CONTENT: SHEET No.