25 KVA

DISTRIBUTION
TRANSFORMER

LINE FROM
SOCOTECO II
2
2-30 MM THW WIRE IN 32 MM
MAIN FEEDER
RSC LEGEND:
CT METER CEILING LIGHT OUTLET
1 1 1 M
CONVENIENCE OUTLET

SAFETY SWITCH OR PANEL BOARD

3.00m M KILOWATT HOUR METER


S2 S1 S2 S1 S2 S1 100A,25KAIC,220V
MAIN CB
CIRCUIT HOMERUN

SERVICE ENTRANCE CAP


LANDING 1

S1 SINGLE GANG SWITCH


2
2-50 MM THW WIRE IN 32 MM RSC
MAIN FEEDER
S2 DOUBLE GANG SWITCH

FUSE

POWER LINE
S2 S2 S2
25MM RSC 25MM RSC 25MM RSC 25MM RSC 25MM RSC 25MM RSC
UP SWITCH LINE
2 2 2

PB-1 PB-2 PB-3 PB-4 PB-5 PB-6


60AT 20 AT 60AT 20 AT 60AT 20 AT 60AT 20 AT 60AT 20 AT 60AT 20 AT
1 1 1 1 1 1
15 AT 30 AT 15 AT 30 AT 15 AT 30 AT 15 AT 30 AT 15 AT 30 AT 15 AT 30 AT
2 3 2 3 2 3 2 3 2 3 2 3

GROUND FLOOR ELECTRICAL LAY-OUT PLAN


SCALE 1: 100

1 1 1
SCHEDULE OF LOADS
SWITCHES
CKT. NO. NO. OF C.O. NO OF L.O. AMPS. VOLTS BREAKER WATTAGE SIZE OF WIRE SIZE OF PIPE
S-1 S-2 S-3

S2 S1 S2 S1 S2 S1 C-1 7 220 1 2
SAFETY SWITCH OR PANEL BOARD
C-2 6 220

C-3 220

C-4 220

C-5

S2 S2 S2 C-6
UP
2 2 2

COMPUTATION: MAIN WIRES:

I = 14.84 + 14.84(0.25)
P = 1600 + 2160 = 3760 W
T I = 18.55A
W
SECOND FLOOR ELECTRICAL LAY-OUT PLAN IST 3000 (100% DF) = 3000 W
SCALE 1: 100 EXCESS 760 (35% DF) = 266 W
3266 W USE 2
2-#14mm THW CU. WIRE IN 25 mm dia, RSC PIPE
2-60 AMP CKT BREAKER 1 0, 220V
PLUG-IN TYPE IN MOLDED CASE
I = 6266 /220 = 14.84 A

PREPARED BY: REG. No.: 2228 PROJECT TITLE/LOCATION: PROJECT OWNER: SHEET CONTENT: SHEET No.

PTR No.: ELECTRICAL LAY-OUT PLAN


ISSUED ON: SCHEDULE OF LOADS
PROPOSED 2-STOREY MULTI-PURPOSE BUILDING ROLITO COBACHA RISER DIAGRAM
ISSUED AT: LOCATION: BRGY. CENTRAL, MATI CITY, DAVAO ORIENTAL
GENERAL NOTES
PROF. ELECTRICAL ENGINEER T.I.N. : 10-297-471 LEGEND