ELECTRICAL GENERAL NOTES:

SYMBOLS: ALL ELECTRICAL WORKS SHALL COMPLY WITH THE APPLICABLE PROVISIONS OF
- CIRCUIT HOMERUN THE LATEST APPROVED EDITION OF THE PHILIPPINE ELECTRICAL CODE; WITH THE RULES
AND REGULATIONS OF THE LOCAL AND NATIONAL AUTHORITIES CONCERNED IN THE
- 6'' Ø PIN LIGHT W/ LED BULB ENFORCEMENT OF ELECTRICAL LAWS AND ORDINANCES, AND REQUIREMENTS OF THE
LOCAL UTILITY COMPANIES.
- CONVENIENCE OUTLET
1. SERVICE TO THE BUILDING SHALL BE
- PANEL BOARD 230 V, 1 PHASE, 60 HZ., 2 WIRES.
2. MINIMUM CONDUIT SIZE SHALL BE IN 20 MM DIA. TRADE SIZE, AND MINIMUM SIZE
S# - SWITCH
OF WIRES SHALL BE 2.0 MM. SQ. INSULATED FOR 600 VOLTS TYPE THHN/THWN OR THW.
3. TYPE OF WIRINGS TO BE USED SHALL BE UPVC PIPE UNDER FLOOR AND UPVC PIPE
- FIRE ALARM ABOVE CEILING, USE SCHEDULE 40.
- FIRE EXTINGUISHER 4. ALL ELECTRICAL MATERIALS AND EQUIPMENTS TO BE USED SHALL BE NEW AND OF
THE APPROVED STANDARD SIZES AND RATINGS FOR LOCATION AND PURPOSES.
5. MOUNTING HEIGHTS SHALL BE AS FOLLOWS:

5.1 WALL OUTLETS AND RECEPTACLES


- 300 MM ABOVE FLR. FINISH @ CENTER (300 MM ABOVE COUNTER)
LOAD PANEL BOARD MAIN: 60 AT, 150AF, 2P, 220V 5.2 SWITCHES
DESCRIPTION "PB" 15 KAC, MCCB - 1400 MM ABOVE FLR. FINISH @ CENTER
CKT. NO. & VA TOTAL VA CIRCUIT BREAKER
5.3 PANEL BOARD (MCB)
LOAD DESCRIPTION PER OUTLET PER CIRCUIT POLE FRAME TRIP
NO. WIRE CONDUIT
- 1600 MM ABOVE FLR. FINISH @ CENTER
1 LIGHTING OUTLET 3 X 60 180 2 15 2-2.0 THW 15mmØ PVC
2 DUPLEX CO 3 X 360 1080 20 2-3.5 THW
5.4 KWH-METER
2 20mmØ PVC
3 DUPLEX CO 1 X 360 360 2 20 2-3.5 THW 20mmØ PVC - 1800 MM ABOVE FLR. FINISH @ CENTER
5.5 ACU COMPRESSOR
4 LIGHTING OUTLET 6 X 60 360 2 15 2-2.0 THW 15mmØ PVC - 600 MM ABOVE FLR. FINISH @ CENTER & 600 MM ABOVE ANOTHER
5 DUPLEX CO 4 X 360 1440 2 20 2-3.5 THW 20mmØ PVC ACU COMPRESSOR @ CENTER
TOTAL: 3420
6. ALL METAL RACEWAYS, BOXES, CABINETS AND NON-CURRENT CARRYING METALLIC
SIZE OF WIRE: USE 2 - 22 sq.mm. THW CU. WIRE IN 32 mmØ RSC
PART OF ELECTRICAL EQUIPMENTS SHALL BE EFFECTIVELY GROUNDED,
MAIN CIRCUIT BREAKER: USE : 60 AT, 125 AF, 2P, 220 V, 15 KAC MOLDED CASE CIRCUIT BREAKER AS MAIN PROTECTION WITH IN ACCORDANCE WITH THE REQUIREMENTS OF THE PHILIPPINE ELECTRICAL CODE.
16 BRANCH CIRCUIT
7. ALL ELECTRICAL WORKS SHALL BE UNDER THE DIRECT SUPERVISION OF A DULY
LICENSED ELECTRICAL ENGINEER OR A REGISTERED MASTER ELECTRICIAN.
Computation:

IT = 3,420VA / 220 V = 15.54 AMPS

PROFESSIONAL ELECTRICAL ENGINEER OWNER: PROJECT TITLE REVISION DESIGNED: SHEET CONTENT: SHEET NO:
DRAWN BY:
GENERAL NOTES
ANITA JIMENEZ PROPOSED TWO STOREY APARTMENT CHECKED:
LEGEND E
BUILDING DATE:
LOAD COMPUTATION
PLACE: 1
ADDRESS : LIBIS, PUERTO PRINCESA CITY, PALAWAN PROJECT LOCATION : LIBIS, PUERTO PRINCESA CITY, PALAWAN

You might also like