You are on page 1of 13

GENERAL NOTES: SPECIFICATIONS:

SERVICE ENTRANCE SERVICE ENTRANCE DETAIL


SINGLE PHASE, 240VAC, 60Hz
ALL ELECTRICAL WORKS HEREIN SHALL BE DONE IN ALL WORKS SHALL BE DONE UNDER THE DIRECT SUPERVISION OF 2 - 100 mm² THW Cu Wire
ACCORDANCE WITH THE NATIONAL BUILDING CODE, LICENSE DULY REGISTERED ELECTRICAL ENGINEER OR
1 - 22 mm² THW in 65 mm Ø RSC Pipe
PROVISIONS OF THE LATEST APPROVED PHILIPPINE ELECTRICAL REGISTERED MASTER ELECTRICIAN. NOTES:
SERVICE DROP LINE
CODE, THE LAWS AND ORDINANCES OF THE LOCAL CODE 1. THE LOCATION OF SERVICE ENTRANCE MAY DEPEND ON THE
1. POWER SUPPLY TO THE BUILDING SHALL BE 230V, THREE 2-100 mm² THW Cu Wire
ENFORCING AUTHORITIES AND REQUIREMENTS OF THE LOCAL 5 NEAREST ELECTRIC UTILITY SUPPLY
ELECTRIC, TELEPHONE COMPANY AND BUILDING PHASE, 3-WIRES + GROUND,60HZ. 1-22 mm² ACSR 8" Ø EYEBOLT
GALVANIZED 2. THE LOCATION OF PROPOSED EMERGENCY SUPPLY MAY
ADMINISTRATION REQUIREMENTS.
2. ALL MATERIALS TO BE USED SHALL BE NEW AND ALSO DEPEND ON THE SITE DEVELOPMENT
1. CONTRACTOR SHALL SECURE ALL ELECTRICAL PERMIT AND APPROVED TYPE FOR PURPOSE & LOCATION. CURRENT TRANFORMER 3. SEE DETAIL OF DISTRIBUTION PANEL AT E2-E4
ALL FEES REQUIRED FOR THE WORKS AND FURNISH THE ENCLOSED, CTR: 5:200
OWNER THE CERTIFICATE OF FINAL ELECTRICAL
INSPECTION.
3. NORMAL AND EMERGENCY CIRCUIT SHALL NOT BE
COMBINED IN ONE RACEWAY OR CONDUIT. USE
Roofdeck
SERVICE ENTRANCE POLE (See Detail 3-E1)
SOLDERLESS 3700mm High for residential property and driveways
2. CONTRACTOR SHALL CONDUCT EARTH GROUND TEST, 4. RECEPTACLES FOR GENERAL USE SHALL BE DUPLEX 20A, CONNECTORS
WIRE INSULATION AND LOAD TEST UPON COMPLETION OF 250VAC, GROUND TYPE. 5500mm High for public streets, alleys, roads,
WORKS. parking areas subject to truck traffic
5. ALL WIRES SHOULD HAVE A MAXIMUM LOAD OF 80% OF DRIP LOOP
3. INCASE OF DISCREPANCY BETWEEN PLANS AND SITE WIRE AMPACITY. at least 1500mm
CONDITION, SPECIFICATIONS & REVISIONS/ CHANGES, THE PB2
CONTRACTOR SHOULD IMMEDIATELY VERIFY & CONSULT 6. LIGHT SWITCHES MINIMUM RATING SHALL BE 16A 230VAC.
TO/WITH THE ELECTRICAL ENGINEER OF THE DPWH
REGIONAL OFFICE VI. 7. ALL MATERIALS TO BE USED SHALL BE BRAND NEW AND
15 mm Ø RSC with clamps
4-3.5mm² THHN Cu Wire 2ndFL
1-65 mmØ RIGID STEEL CONDUIT 2-38 mm sq THHN/THWN Cu Wire
SHALL HAVE THE "P.S." MARKS.
w/ COMPLETE SUPPORTS 1-14 mm sq THHN/THWN Cu Wire 2-38 mm² THW CU WIRE
4. ALL LOCATION & MOUNTING HEIGHTS ARE SUBJECT TO 1-14 mm² THW CU WIRE
APPROVAL OF ELECTRICAL ENGINEER OF PNPES, 8. MOUNTING HEIGHTS SHALL BE AS FOLLOWS: MDM in 40 mm Ø RSC Pipe
IN 40 mm Ø RSC PIPE
KWHR METER PROVIDE MAIN DISCONNECTING MEANS
5. CONTRACTOR SHALL BE RESPONSIBLE IN THE PREPARATION A. LIGHT SWITCHES - 1.37m above Floor finish CT RATED in NEMA 3R ENCLOSURES IN NEMA 3R ENCLOSURES for SERVICE
OF AS-BUILT PLANS DULY SIGNED AND SEALED BY A B. CONVENIENCE OUTLET - 0.3m above Floor 2-100 mm² THW CU WIRE MTS
LATERAL OF MORE THAN 30M
PROFESSIONAL ELECTRICAL ENGINEER, AND ELECTRONIC finish 1-22 mm² THW CU WIRE 200A PB1
AUTOCAD FILES. C. TELEPHONE OUTLET - 0.3m above Floor finish IN 90 mm Ø RSC PIPE 1-65 mm Ø RSC PIPES
6. FINAL LIGHTING FIXTURES AND WIRING DEVICES SHALL BE
D. PANEL BOARD - 1.8m ABOVE FLOOR FINISH
FOR PROVISION OF GEN SET GFL
APPROVED BY DPWH ELECTRICAL 9. CONDUIT EMBEDED WITHIN CONCRETE WALL SHALL HAVE 1 - 22 mm² THW Cu Wire (Grounding)
REPRESENTATIVE/ENGINEER, A MINIMUM CEMENT PLASTERED OF 20mm THICK. in 20 mm Ø PVC Pipe, Sched 40
1 - 22 mm² THW Cu Wire (Grounding)
7. CONTRACTOR SHALL BE RESPONSIBLE FOR PREPARATION 10. ALL CONDUIT/ PIPE ABOVE CEILING SHOULD HAVE PROVIDE GROUNDING ROD in 20 mm Ø PVC Pipe, Sched 40
OF SHOP OR CONSTRUCTION DRAWING REQUIRED BY INDEPENDENT HANGER/ SUPPORTS. COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm PROVIDE GROUNDING ROD
OWNER/ARCHITECH/ENGINEER, THIS INCLUDES DEVICES COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm
AND FIXTURES ELEVATION. 11. ALL LIGHTING FIXTURES SHOULD HAVE INDEPENDENT
HANGER/ SUPPORTS.
8. CONTRACTOR SHALL VISIT SITE CONDITION AND INCLUDE
ALL COST NECESSARY TO COMPLETE THE SYSTEM AT NO 12. ALL BOXES SHALL BE OCCUPIED ONLY OF 50% OF WIRE
COST TO OWNER, INCLUDING COST OF CORING SERVICE VOLUME.
AND EXPENSES FOR THE RESTORATION OF ANY DAMAGE/
AFFECTED CIVIL/ ARCHITECTURAL FINISHES OR 13. VOLTAGE DROP SHALL BE LIMITED TO 2.5% FROM SOURCE
RELOCATION OF EXISTING FACILITIES ON BUILDING. TO PANEL BOARD AS P.E.C. REQUIREMENT OR ACCEPTABLE

9. CONTRACTOR SHALL LOCATE ALL SPLICING BOXES TO


TO THE LABORATORY EQUIPMENT. SERVICE POLE DETAIL
ACCESSIBLE PLACE OR WITH ACCESS PANELS. 14. CIRCUIT BREAKERS SERVING MOTORS AND LIGHTING
SHALL BE INDUSTRIAL AND COMMERCIAL BOLT-ON TYPE
10. NOMINATED CONTRACTOR TO VERIFY ALL EQUIPMENTS RESPECTIVELY WITH MINIMUM OF 14kAIC. TOP
TO BE INSTALLED OR PLACE WITHIN THE BUILDING, AND 0.20
MAKE AN ADJUSTMENT WITH THE PROJECT ENGINEER/ 15. ALL WIRES AND CABLES SHALL BE BRAND NEW AND
ARCHITECT CONSENT. APPROVED TYPE.

11. THIS DRAWINGS ARE DIAGRAMATIC LAYOUT ONLY, ANY 16. USE SOLDERLESS CONNECTOR, MECHANICAL 1 PRESSURE
MATERIALS AND FITTINGS NOT SHOWN ON THIS PLANS TYPE COPPER LUGS FOR CONNECTION OF WIRES LARGER
BUT NEEDED TO COMPLETE THE SYSTEM AND OPERATION THAN 8mm².
SHALL BE INCLUDED WITH THE CONTRACTOR'S SCOPE OF
WORKS. STEELBARS
STRIRUPS
12. ADDITIONAL NOTES: NOTE:
Coordinate to the Structural Engineer the Size of

· USE OF MICA SHALL BE LIMITED TO 150mm MAXIMUM NG.L. Steel Bars

· USE OF FLEXIBLE METALLIC CONDUIT SHALL BE LIMITED


TO 1m
MAXIMUM 1.00
· PROVIDE PROPER CONDUIT SUPPORT, G.I. WIRES AS
SUPPORT
SHALL NOT BE ALLOWED
· PROVIDE DOUBLE COAT OF RUST PROTECTIVE PAINT 4STEELBARS

1.5
(RED OXIDE BOTHWAYS

1.00
PRIMER) ON HANGERS AND SUPPORTS.

0.35
0.30
1.00 0.40

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
FORT SAN PEDRO, ILOILO CITY SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.15 2.72 0.79 2.98 6.21 2.77 0.48 4.11 3.15 2.72 3.75 4.29 3.29 1.34 0.57 4.11
1.16

1.16
UP UP
DL DL
g a'.1
1 1
q DW S3W Sg LP-1 LANDING DW LANDING
PANTRY PWD CR DN
1.62

Ckt.3 d" IT/ DATA CENTER STAIR


DL
z a' b' DL s' t'

2.53

2.54
WCR PWD CR LOBBY

2.88
Sq c" Sd" KITCHEN

3.18
PANTRY
c' d' c' STAIR
p Sp KITCHEN
LOBBY UP WCR Sc" y' z' w' x' u' v' UP
LP-1
SzS2a'b'Sa'.1
4.76

4.76
S2s't'
1.53

Ckt.1 LP-1 e" LP-2 LP-2


PB-1 MDP Ckt.2 DL PB-2

0.64
S3W S2c'd' S2xy Ckt.1 S2y'z' Ckt.2 S2w'x' S2u'v'
f"

1.60
n o n o n LP-2
MCR Sm x y b" MCR DL
Ckt.3
q' r'
m DL DL DL DL DL Sb" S2e"f"
2.50

S2no

2.53
a² b² c² d² e² S2q'r'
2 2 Sa"
Sr Ss S3W S2tu a"

1.17
LP-1 LP-1 S2d²e²
1.07

1.07
STO STO DL
r DL s DL
Ckt.5 Ckt.4
MEETING ROOM 3 STORAGE
3 3

6.87
Sl OFFICE AREA
INFORMATION y x OFFICE AREA r' q'

15.14
l l S2hi DL DL t u e' f' S3a²b²c²
h i
13.98

13.98

13.98
a² b² c² d² e²

2.66
2.67

P.E. DL DL
P.E. DL DL
ELEVATOR LOBBY ELEVATOR LOBBY

3.69
3.57

3.57
a b S2e'f'
DL DL
MEETING ROOM 1 MEETING ROOM 2 LP-2
f S2g'h'
LANDING x y LANDING STAIR Ckt.4 q' r'
UP S3W u t UP LOBBY
LOBBY
4 k Sk S2ab 4 S2i'j' S2k'l' S2m'n'
2.92

Se S2f Sj'.1

3.34
Sj TOI g' h' i' j' k' TOI
S2cd m'
1.81

1.81
2.12

2.27
STORAGE v Sv DN o'
DL b a DL
EXECUTIVE
DL
So' EXECUTIVE
j OFFICE - 1
5 DL DL

u
5 OFFICE - 2

4.58
1.39

ENTRY PORCH MEETING ROOM


j' i' l'
2.76

2.76
LANDING c d w Sp' p' n'

2.45
SW

2.31
2.32
DL DL
DL DL
e DL
e DL
TOI TOI
1.34

RAMP

6 c d 6
DL UP DL

j'.1
FL

4.32 1.42 4.82 3.35 1.48 3.15 4.67 0.50 3.45 2.29 4.82 3.35 1.41 3.35 4.55

Ckt.
23.22 23.22 3

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

DL

CL

FL

FMO

WP

RA

REF

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
FORT SAN PEDRO, ILOILO CITY SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.20 1.39 3.11 3.02 3.19 3.30 1.41 4.59 3.16 2.59 8.17 1.31 0.93 2.40 4.67

LP-3 LP-3
Ckt.1 Ckt.2
1 1
TO
LETI
LANDING
B&ATH
DN PWD CR

1.68
T&B F*-

DOUBLE
w"

DECK
m" p" s" u"

BED
q" TO
LETI
2.44

v* DL y*

2.54
BED
CHANG
NG
I

DECK
WCR x* x*

DOUBLE
B&ATH
DL ROOM FEMALE
n* o* Sv*
Sq" T&B W/ u* Su*
EXECUTIVE EXECUTIVE STAFF STAFF CHANGING ROOM WELLNESS

1.21
Sw" PB-4 z.2*
4.76

S2n*o*

4.90
ROOM 1 ROOM 2 QUARTERS 1 QUARTERS 2 CENTER CL

IF
LE
O
DL

RON
5.83
y.1*

STORAGE
MALE y* y*
x*

DOUBLE
w*

DECK
BED
q* OPEN

BED
DECK
l" Sn" o" r" t" l* m*
DOUBLE

1.29
v" DL
2.45

2.30
TO
LETI S2l*m* CLEAN LINEN GAZEBO
n"T&BDL B&ATH MCR
CHANG
NG
I St*
DL
SW*
S2l"m" S2o"p" S2r"s" S2t"u" Sv" ROOM S2x*y*
2 2 t*

1.48
k" Sk" LP-4 S2x.1*y.1** Sz.2**
0.77
1.07

PB-3 LP-3 H A L L W A Y

1.49
DL
STORAGE Ckt.2
3 DL DL Ckt.4 DL z.1" S2j*k* j* 3
g" h" p* q* DL DL LP-4
Sz.1" DL DL
k* S2z*z.1** z* z.1* z*
s* Ckt.1
S2p*q* r* r* x.1*
DOUBLE

LP-3 p*

13.98

13.98
2.56
13.98

13.98
2.61

DECK
BED

ELEVATOR LOBBY S2r*s* BALCONY

4.50
P.E. P.E. ELEVATOR LOBBY EVENT AREA
DOUBLE DL DL Ckt.3 DL DL
DECK

IF
x" y"
3.57

3.57

LE
O
RON
S2g"h" DL DL BED LOUNGE AREA

3.12
h" g" STAFF q* p* S2p*q*
S2e'f' QUARTERS 3 DL DL
k* z.1* z* z.1*
DL S2s*r*
LANDING
F*-
S2x"y"
UP
4 T&B Sz" 4
S2d*e* S2g*h*
LP-3 z"

3.18
3.08

LANDING

1.20
DL
i" j" TOI
Ckt.5 s* r* DL DL
1.81

1.81
i* Si* x.1* y.1*
DN S2a*b* d* DN
Sc*
DL
g*
RON
O
LE
IF
c*
5 T&B
DL
STAFF 5

4.53
QUARTERS 4 EXECUTIVE EXECUTIVE

3.37
ROOM 3 ROOM 4
Sf*
2.76

2.76
a* b*
2.64

2.59
DL
f*
e*
DOUBLE

TOI h*
DECK
BED
BED
DECK
DOUBLE

6 6

2.04 1.39 1.27 3.46 1.41 3.40

0.50 3.58 2.16 4.70 3.46 4.81 4.50 0.50 5.75 8.35 4.44 4.67

Ckt.
23.22 23.22 3

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

DL

CL

FL

FMO

WP

RA

REF

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.15 2.72 0.79 2.98 6.21 2.77 0.48 4.11 3.15 2.72 3.75 4.29 3.29 1.34 0.57 4.11

PP-1 PP-1 PP-2 PP-1


1.16

1.16
UP UP Ckt.17
Ckt.16 Ckt.5 Ckt.15
1 1
DW LANDING DW LANDING
WP PANTRY WP
PWD CR WP DN
1.62

WP RA
PP-1 IT/ DATA CENTER STAIR

2.53

2.54
WCR PWD CR PP-1 Ckt.7 PP-2 FMO LOBBY

2.88
KITCHEN

3.18
Ckt.15 Ckt.6 PANTRY
STAIR PP-2
KITCHEN UP UP
LOBBY WCR PP-1 FMO
WP

RA Ckt.7
4.76

4.76
1.53

PP-1

REF
WP

REF
Ckt.13 PP-1
Ckt.14 PB-1 MDP

0.64
PB-2 Ckt.14 PP-2
WP Ckt.12
WP

PP-1 FMO FMO FMO

1.60
PP-1 Ckt.9 PP-1 PP-1 PP-2
MCR MCR
Ckt.6 Ckt.22 Ckt.19 Ckt.8 FMO
2.50

2.53
2 FMO FMO FMO 2

1.17
PP-1
1.07

1.07
STO STO STORAGE FMO FMO FMO FMO
MEETING ROOM 3
Ckt.17
3 3

6.87
FMO FMO PP-1 FMO FMO FMO FMO FMO PP-2 OFFICE AREA OFFICE AREA
INFORMATION

15.14
PP-1 Ckt.11 Ckt.18 FMO FMO FMO FMO
PP-1
Ckt.12
13.98

13.98

13.98
2.67

2.66
P.E. PP-1 P.E. Ckt.19
ELEVATOR LOBBY FMO FMO FMO ELEVATOR LOBBY

3.69
FMO FMO FMO FMO Ckt.8
3.57

3.57
PP-2 FMO FMO FMO FMO
MEETING ROOM 1 MEETING ROOM 2 Ckt.10 PP-1
PP-1 PP-2
PP-1 FMO PP-2 PP-1 Ckt.22 PP-1
LANDING Ckt.13 LANDING STAIR Ckt.11
Ckt.10 FMO FMO FMO FMO Ckt.9 Ckt.20 Ckt.21
UP UP LOBBY
LOBBY
4 PP-1
4
2.92

PP-1

3.34
Ckt.23 TOI TOI
FMO FMO FMO FMO
1.81

1.81
PP-1 Ckt.23 PP-1

2.12

2.27
STORAGE Ckt.18 DN Ckt.16
EXECUTIVE EXECUTIVE
5 5 OFFICE - 1 OFFICE - 2
FMO FMO WP FMO FMO WP

4.58
WP WP
1.39

FMO FMO
ENTRY PORCH MEETING ROOM
2.76

2.76
LANDING

2.45

2.31
2.32
FMO FMO TOI FMO TOI
1.34

RAMP

6 6
UP PP-1
Ckt.21 PP-1
Ckt.20

4.32 1.42 4.82 3.35 1.48 3.15 4.67 0.50 3.45 2.29 4.82 3.35 1.41 3.35 4.55

Ckt.
23.22 23.22 3

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

DL

CL

FL

FMO

WP

RA

REF

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.20 1.39 3.11 3.02 3.19 3.30 1.41 4.59 3.16 2.59 8.17 1.31 0.93 2.40 4.67

4.28
PP-3 PP-3 PP-3
Ckt.11 Ckt.13 Ckt.14

1 1
TOLETI
B&ATH
LANDING
DN WP PWD CR WP

1.68
T&B F*-

DOUBLE
DECK
BED
TOLETI
2.44

2.54
BED
CHANG
NG
I

DECK
DOUBLE
B&ATH WCR PP-4
ROOM FEMALE
T&B W/ Ckt.6
EXECUTIVE WP EXECUTIVE STAFF STAFF CHANGING ROOM WELLNESS

1.21
PB-4
4.76

ROOM 1 ROOM 2 QUARTERS 1 QUARTERS 2

4.90
WP CENTER

O
RONIF
LE
PP-3

5.83
WP MALE

STORAGE
PP-4

DOUBLE
PP-3

DECK
BED
Ckt.9

BED
Ckt.7
DECK
OPEN
DOUBLE
Ckt.6

1.29
WP
2.45

2.30
TOLETI CLEAN LINEN PP-4 GAZEBO
B&ATH MCR
T&B CHANG
NG
I Ckt.5 WP
ROOM
2 2

1.48
PP-3
0.77

PP-3 PP-3
1.07

PB-3 H A L L W A Y

1.49
STORAGE Ckt.12 Ckt.7 Ckt.10
3 FMO 3
PP-3 PP-3 PP-3 PP-4
PP-3 PP-4
Ckt.22 Ckt.17 Ckt.15 PP-4
Ckt.18 Ckt.3 Ckt.8
DOUBLE

Ckt.4
13.98

13.98
2.61

2.56
13.98

13.98
DECK
BED

P.E. ELEVATOR LOBBY BALCONY

4.50
DOUBLE P.E. ELEVATOR LOBBY EVENT AREA
DECK PP-3
3.57

IF
3.57

LE
O
RON
BED LOUNGE AREA
Ckt.16 PP-4

3.12
STAFF PP-4 Ckt.10
QUARTERS 3 FMO Ckt.9
LANDING
F*- UP
4 T&B
4
WP
3.08

3.18
TOI LANDING

1.20
1.81

1.81
DN PP-3
DN
Ckt.8
WP

RON
O
LE
IF
5 T&B STAFF WP 5

4.53
QUARTERS 4 WP
EXECUTIVE EXECUTIVE
ROOM 3 ROOM 4

3.37
PP-3
2.76

2.76
2.64

2.59
Ckt.21
DOUBLE

TOI
DECK

WP WP
BED
BED
DECK
DOUBLE

6 6
PP-3 PP-3
Ckt.20 Ckt.19
2.04 1.39 1.27 3.46 1.41 3.40

0.50 3.58 2.16 4.70 3.46 4.81 4.50 0.50 5.75 8.35 4.44 4.67
Ckt.
23.22 23.22 3

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

DL

CL

FL

FMO

WP

RA

REF

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
SCHEDULE OF LOADS PB-1 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS SCHEDULE OF LOADS PB-2 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS
OUTLETS SWITCHES AMPERE OUTLETS SWITCHES AMPERE
CIRCUIT LOAD CIRCUIT SIZE AND TYPE OF SIZE OF CIRCUIT LOAD CIRCUIT SIZE AND TYPE OF SIZE OF
LOAD DESCRIPTIONS TOTAL VA LOAD DESCRIPTIONS TOTAL VA
NO. PROTECTION CONDUCTOR CONDUIT NO. PROTECTION CONDUCTOR CONDUIT
L.O. C.O. OTHERS S1 S2 S3 S3W A B C L.O. C.O. OTHERS S1 S2 S3 S3W A B C

10-1x9 W LED PIN LIGHT 6" DIA., 3-1x18 W LED 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. 6-1x9 W LED PIN LIGHT 6" DIA., 6-1x18 W LED FLUORESCENT 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
LP-1/Ckt.1 FLUORESCENT LAMP, 3-1x45W E. FAN
13 7 1 1.213 278.99
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC LP-2/1 LAMP, 4-1x45 W E. FAN
12 4 4 1.487 342.01
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC

3-2x18 W, LED TUBE LIGHT SURFACE


2 - 3.5 MM² THHN / THWN - 2CU. 10-2x18 W, LED TUBE LIGHT SURFACE 2 - 3.5 MM² THHN / THWN - 2CU.
MOUNTED MODULAR LIGHT FITTING, 8-1x9 W LED 20 At 2 P MCB 20 At 2 P MCB
LP-1/Ckt.2 PIN LIGHT 6" DIA., 2-1x18 W LED FLUORESCENT
13 3 2 1 1.135 261.05
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC LP-2/2 MOUNTED MODULAR LIGHT FITTING, 2-1x18 W LED 12 4 1.722 396.06
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC
FLUORESCENT LAMP
LAMP, 1-1x45 W E. FAN
6-2x18 W, LED TUBE LIGHT SURFACE 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. 10-2x18 W, LED TUBE LIGHT SURFACE 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
LP-1/Ckt.3 MOUNTED MODULAR LIGHT FITTING, 3-1x18 W LED 10 2 2 1.213 278.99
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC LP-2/3 MOUNTED MODULAR LIGHT FITTING
10 1 1 1.565 359.95
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC
FLUORESCENT LAMP, & 1-1x9 W LED PIN LIGHT

5-2x18 W, LED TUBE LIGHT SURFACE 8-2x18 W, LED TUBE LIGHT SURFACE
20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
LP-1/Ckt.4 MOUNTED MODULAR LIGHT FITTING, 2-1x9 W LED 7 2 1 1.252 287.96
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC LP-2/4 MOUNTED MODULAR LIGHT FITTING, 2-1x9 W LED 11 3 3 2.374 546.02
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC
PIN LIGHT 6" DIA., 2-1x45 W E. FAN PIN LIGHT 6" DIA., 2-1x45 W E. FAN, & 1-150W LED FLOOD LIGHTS

3-2x18 W, LED TUBE LIGHT SURFACE 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
LP-1/Ckt.5 MOUNTED MODULAR LIGHT FITTING, 6-1x9 W LED 10 1 2 1 1.356 311.88 20 MM Ø uPVC PP-2/5 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
PIN LIGHT 6" DIA. & 1-150 W BULB CHANDELIER
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
3 - 180 VA DUPLEX C.O, 4 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/6 1 - CONVENIENCE OUTLET RANGE 1 6.522 1,500.06
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.6 WEATHER PROOF
7 5.478 1,259.94
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/7 1 - CONVENIENCE OUTLET REFRIGERATOR 1 3.391 779.93
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.7 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
3 - 180 VA DUPLEX C.O, 4 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/8 WEATHER PROOF
7 5.478 1,259.94
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.8 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/9 7 - 180 VA DUPLEX C.O 7 5.478 1,259.94
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.9 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/10 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.10 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/11 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.11 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. PP-2/12 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
PP-1/Ckt.12 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC
2 - 30 MM² THHN / THWN - 2CU.
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU. T O T A L ( PB-2 ) 45 48 - 7 12 1 - 13.513 19.722 19.826 12,204.03 100 At 2 P CB
1 - 14 MM² THHN / THWN - 2CU.
40 MM Ø RSC
PP-1/Ckt.13 7 - 180 VA DUPLEX C.O 7 5.478 1,259.94
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC

30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2CU.


PP-1/Ckt.14 1 - CONVENIENCE OUTLET REFRIGERATOR 1 3.391 779.93
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU.


PP-1/Ckt.15 1 - CONVENIENCE OUTLET RANGE 1 6.522 1,500.06
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC

2 - 30 MM² THHN / THWN - 2CU.


T O T A L ( PB-1 ) 53 64 - 15 8 - 2 20.465 18.404 25.735 14,858.92 110 At 2 P CB
1 - 14 MM² THHN / THWN - 2CU.
40 MM Ø RSC

SCHEDULE OF LOADS PB-1A 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS SCHEDULE OF LOADS PB-2A 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS
OUTLETS SWITCHES AMPERE OUTLETS SWITCHES AMPERE
CIRCUIT LOAD CIRCUIT SIZE OF CIRCUIT LOAD CIRCUIT SIZE AND TYPE OF SIZE OF
TOTAL VA SIZE AND TYPE OF TOTAL VA
LOAD DESCRIPTIONS LOAD DESCRIPTIONS
NO. PROTECTION CONDUCTOR CONDUIT NO. PROTECTION CONDUCTOR CONDUIT
L.O. C.O. OTHERS S1 S2 S3 S3W A B C L.O. C.O. OTHERS S1 S2 S3 S3W A B C

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
1PP-1/Ckt.16 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/13 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.17 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/14 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.18 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/15 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.19 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/16 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.20 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/17 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.21 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/18 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.22 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/19 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-1/Ckt.23 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN - 2CU.
25 MM Ø uPVC PP-2/20 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

2 - 30 MM² THHN / THWN - 2CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


T O T A L ( PB-1A ) - 8 - - - - - 32.700 38.500 33.400 24,058.00 110 At 2 P CB
1 - 14 MM² THHN / THWN - 2CU.
40 MM Ø RSC PP-2/21 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


PP-2/22 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


PP-2/23 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

2 - 30 MM² THHN / THWN - 2CU.


T O T A L ( PB-2A ) - 11 - - - - - 49.400 43.600 44.300 32,913.00 100 At 2 P CB
1 - 14 MM² THHN / THWN - 2CU.
40 MM Ø RSC

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
FORT SAN PEDRO, ILOILO CITY SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
SCHEDULE OF LOADS PB-3 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS SCHEDULE OF LOADS PB-4 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS
OUTLETS SWITCHES AMPERE
OUTLETS SWITCHES AMPERE
CIRCUIT LOAD CIRCUIT SIZE AND TYPE OF SIZE OF
CIRCUIT LOAD CIRCUIT SIZE AND TYPE OF SIZE OF TOTAL VA
TOTAL VA LOAD DESCRIPTIONS
LOAD DESCRIPTIONS NO. PROTECTION CONDUCTOR CONDUIT
NO. PROTECTION CONDUCTOR CONDUIT L.O. C.O. OTHERS S1 S2 S3 S3W A B C
L.O. C.O. OTHERS S1 S2 S3 S3W A B C
6-2x18 W LED TUBE LIGHT SURFACE MOUNTED MODULAR 2 - 3.5 MM² THHN / THWN - 2CU.
20 At 2 P MCB
20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. LP-4/1 LIGHT FITTING, 2-1x18 W LED FLUORESCENT LAMP, 12 4 2 1 1.839 422.97 20 MM Ø uPVC
LP-3/1 8-1x18 W LED FLUORESCENT LAMP, 2-1x45 W E. FAN 8 2 3 0.861 198.03 20 MM Ø uPVC 30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU. 4-1x9 W LED PIN LIGHT 6" DIA., 3-1x45 W E. FAN

6-2x18 W LED TUBE LIGHT SURFACE MOUNTED MODULAR 2 - 3.5 MM² THHN / THWN - 2CU.
20 At 2 P MCB
3-1x9 W LED PIN LIGHT 6" DIA., 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. LP-4/2 LIGHT FITTING, 4-1x9 W LED PIN LIGHT 6" DIA., 2-1x18W LED 13 1 3 1.330 305.90 20 MM Ø uPVC
LP-3/2 7 3 0.430 098.90 20 MM Ø uPVC 30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
4-1x18 W LED FLUORESCENT LAMP 30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU. FLUORESCENT LAMP, 1-1x18 W LED CIRCULAR LAMP

4 - 180 VA DUPLEX C.O, 3 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
1-1x150 W BULB CHANDELIER, 2-1x18 W LED
20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU. PP-4/3 WEATHER PROOF
7 5.478 1,259.94
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
LP-3/3 FLUORESCENT LAMP, 11 1 3 1.317 302.91
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC
8-1x9 W LED PIN LIGHT 6" DIA., 1-1x45 W E. FAN
4 - 180 VA DUPLEX C.O, 4 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
PP-4/4 WEATHER PROOF
8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
6-1x18 W LED FLUORESCENT LAMP, 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
LP-3/4 4-1x9 W LED PIN LIGHT 6" DIA., 3-1x45 W E. FAN
10 4 3 1.213 278.99
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-4/5 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC
25 MM Ø uPVC
1 - 3.5 MM² THHN / THWN GROUND
4-1x18 W LED FLUORESCENT LAMP, 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
LP-3/5 7-1x9 W LED PIN LIGHT 6" DIA., 2-1x45 W E. FAN
11 3 3 0.978 224.94
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-4/6 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

6 - 180 VA DUPLEX C.O, 2 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/6 WEATHER PROOF
8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC PP-4/7 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
6 - 180 VA DUPLEX C.O, 1 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/7 WEATHER PROOF
7 5.478 1,259.94
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC PP-4/8 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
6 - 180 VA DUPLEX C.O, 2 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/8 WEATHER PROOF
8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC PP-4/9 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 16.700 3,841.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
7 - 180 VA DUPLEX C.O, 1 - 180 VA DUPLEX C.O 30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU. 30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/9 WEATHER PROOF
8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC PP-4/10 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 10.900 2,507.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND

30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU. 2 - 30 MM² THHN / THWN - 2CU.


PP-3/10 8 - 180 VA DUPLEX C.O 8 6.261 1,440.03
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND 25 MM Ø uPVC T O T A L ( PB-4 ) 25 19 - 5 5 - 1 29.900 34.730 38.878 23,806.84 100 At 2 P CB 40 MM Ø RSC
1 - 14 MM² THHN / THWN - 2CU.
2 - 30 MM² THHN / THWN - 2CU.
T O T A L ( PB-3 ) 47 39 - 10 15 - - 13.813 7.667 13.839 8,123.83 100 At 2 P CB
1 - 14 MM² THHN / THWN - 2CU.
40 MM Ø RSC

MDP 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS


AMPERE
LOAD CIRCUIT SIZE AND TYPE OF SIZE OF
LOAD DESCRIPTION 3ɸ TOTAL VA
PROTECTION CONDUCTOR CONDUIT
A B C

20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.


PB-1 20.465 4,706.95
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
20 MM Ø uPVC

20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.


18.404 4,232.92 20 MM Ø uPVC
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.

20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.


25.735 5,919.05 20 MM Ø uPVC
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
SCHEDULE OF LOADS PB-3A 230 V. 3Ø, 60 Hz., 3 WIRES + GROUNDS 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
PB-1A 32.700 7,521.00 20 MM Ø uPVC
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
OUTLETS SWITCHES AMPERE
LOAD 20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
CIRCUIT TOTAL VA CIRCUIT SIZE AND TYPE OF SIZE OF 38.500 8,855.00 20 MM Ø uPVC
LOAD DESCRIPTIONS 30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
NO. PROTECTION CONDUCTOR CONDUIT
L.O. C.O. OTHERS S1 S2 S3 S3W A B C
20 At 2 P MCB 2 - 3.5 MM² THHN / THWN - 2CU.
33.400 7,682.00 20 MM Ø uPVC
30 AF, 10 KAIC 1 - 2.0 MM² THHN / THWN - 2CU.
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/11 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
PB-2 13.513 3,107.99 25 MM Ø uPVC
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/12 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
19.722 4,536.06 25 MM Ø uPVC
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/13 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
19.826 4,559.98 25 MM Ø uPVC
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/14 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
PB-2A 49.400 11,362.00 25 MM Ø uPVC
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/15 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
43.600 10,028.00 25 MM Ø uPVC
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/16 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 3.5 MM² THHN / THWN - 2 CU.
44.300 10,189.00 25 MM Ø uPVC
40 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/17 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PB-3 13.813 3,176.99
50 AF, 10 KAIC
25 MM Ø uPVC
1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/18 1 - 4.0 HP A.C.U CEILING CASSETTE( 3,100 watts ) 1 16.700 3,841.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
7.667 1,763.41 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/19 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
13.839 3,182.97 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/20 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 16.700 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PB-3A 43.600 10,028.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/21 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
55.200 12,696.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PP-3/22 1 - 2.5 HP A.C.U CEILING CASSETTE( 2,000 watts ) 1 10.900 2,507.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
55.200 12,696.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
2 - 30 MM² THHN / THWN - 2CU.
T O T A L ( PB-3A ) - 12 - - - - - 43.600 55.200 55.200 42,209.83 100 At 2 P CB
1 - 14 MM² THHN / THWN - 2CU.
40 MM Ø RSC
30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.
PB-4 29.900 6,877.00 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


34.730 7,987.90 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


38.878 8,941.94 25 MM Ø uPVC
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


ELEVATOR ( 10HP ) 28.000 6,440.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

30 At 3 P CB 2 - 5.5 MM² THHN / THWN - 2 CU.


FIRE PUMP ( 15HP ) 42.000 9,660.00
50 AF, 10 KAIC 1 - 3.5 MM² THHN / THWN GROUND
25 MM Ø uPVC

2 - 125 MM² THHN / THWN - 2CU.


T O T A L LOAD 203.391 217.823 231.178 70.000 166,150.16 400 At 2 P CB
1 - 22 MM² THHN / THWN - 2CU.
40 MM Ø RSC

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
DESIGN ANALYSIS: PB-1A
DESIGN ANALYSIS: PB-1 DESIGN ANALYSIS: PB-2 DESIGN ANALYSIS: PB-3 DESIGN ANALYSIS: PB-4
PP-1/Ckt. 16-17,19-20 & 22 ( IDENTICAL ) AIR CONDITIONING UNIT LOAD, 2.50 HP
LP-1/Ckt. 1 - LIGHTING LOAD I = 10.900 A. LP-2/Ckt. 1 - LIGHTING LOAD LP-3/Ckt. 1 - LIGHTING LOAD LP-4/Ckt. 1 - LIGHTING LOAD
I = ( 3 x 18 ) + ( 10 x 9 ) + ( 3 x 45 ) / 230 = 1.213 A. Ic = 10.900 A x 1.25 = 13.625 A. I = ( 6 x 18 ) + ( 6 x 9 ) + ( 4 x 45 ) / 230 = 1.487 A. I = ( 6 x 18 ) + ( 2 x 45 ) / 230 = 0.861 A. I = ( 6 x 18 ) + ( 2 x 18 ) + ( 4 x 9 ) + ( 3 x 45 ) / 230 = 1.839 A.
Ic = 1.213 x 1.25 = 1.516 A. USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT Ic = 1.487 x 1.25 = 1.859 A. Ic = 0.861 x 1.25 = 1.076 A. Ic = 1.839 x 1.25 = 2.299 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT
20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING
PP-1/Ckt. 18, 21 & 23 ( IDENTICAL ) AIR CONDITIONING UNIT LOAD, 4.00 HP
LP-1/Ckt. 2 - LIGHTING LOAD I = 16.700. A. LP-2/Ckt. 2 - LIGHTING LOAD LP-3/Ckt. 2 - LIGHTING LOAD LP-4/Ckt. 2 - LIGHTING LOAD
I = ( 8 x 9 ) + ( 3 x 36 ) + ( 2 x 18 ) + ( 1 x 45 ) / 230 = 1.135 A. Ic = 16.700 A x 1.25 = 20.875 A. I = ( 10 x 36 ) + ( 2 X 18 ) / 230 = 1.722 A. I = ( 3 x 9 ) + ( 4 X 18 ) / 230 = 0.430 A. I = ( 6 x 36 ) + ( 4 x 9 ) + ( 1 x 18 ) + ( 2 x 18 ) / 230 = 1.330 A.
Ic = 1.135 x 1.25 = 1.419 A. USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT Ic = 1.722 x 1.25 = 2.152 A. Ic = 0.430 x 1.25 = 0.537 A. Ic = 1.330 x 1.25 = 1.662 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT
20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

SUB-MAIN CIRCUIT COMPUTATION (PB-1A)


LP-1/Ckt. 3 - LIGHTING LOAD I = 1.732 x (38.50 + (16.70 x 0.25) = 73.913 A. LP-2/Ckt. 3 - LIGHTING LOAD LP-3/Ckt. 3 - LIGHTING LOAD PP-4/Ckt. 3 - CONVENIENCE OUTLET
I = ( 3 x 18 ) + ( 6 x 36 ) + ( 1 x 9 ) / 230 = 1.213 A. Ic = 73.913 x 1.25 = 92.391 A. I = ( 10 x 36 ) / 230 = 1.565 A. I = ( 2 x 18 ) + ( 1 x 150 ) + ( 8 x 9 ) + ( 1 x 45 ) / 230 = 1.317 A. I = ( 7 x 180 ) / 230 = 5.478 A.
Ic = 1.213 x 1.25 = 1.516 A. USE: 3-38 MM² THHN/THWN CU. ON 50 MM Ø RSC PIPE Ic = 1.565 x 1.25 = 1.956 A. Ic = 1.317 x 1.25 = 1.646 A. Ic = 5.478 x 1.25 = 6.847 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT 1-14 MM² THW CU WIRE ( GROUNDING WIRE ) USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 125 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

LP-1/Ckt. 4 - LIGHTING LOAD LP-2/Ckt. 4 - LIGHTING LOAD LP-3/Ckt. 4 - LIGHTING LOAD PP-4/Ckt. 4 - CONVENIENCE OUTLET
I = ( 5 x 36 ) + ( 2 x 9 ) + ( 2 x 45 ) / 230 = 1.252 A. I = ( 8 x 36 ) + ( 2 x 9 ) + ( 2 x 45 ) + ( 1 x 150 ) / 230 = 2.374 A. I = ( 6 x 18 ) + ( 4 x 9 ) + ( 3 x 45 ) / 230 = 1.213 A. I = ( 8 x 180 ) / 230 = 6.261 A.
Ic = 1.252 x 1.25 = 1.565 A. Ic = 2.374 x 1.25 = 2.967 A. Ic = 1.213 x 1.25 = 1.516A. Ic = 6.261 x 1.25 = 7.826 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

LP-1/Ckt. 5 - LIGHTING LOAD PP-2/Ckt. 5,10,11 & 12 ( IDENTICAL ) - CONVENIENCE OUTLET LP-3/Ckt. 5 - LIGHTING LOAD PP-4 /Ckt. 5-6 & 8-9 ( IDENTICAL ) - AIR CONDITIONING UNIT LOAD, 5.00 HP
I = ( 3 x 36 ) + ( 6 x 9 ) + (1 x 150 ) / 230 = 1.356 A. I = ( 8 x 180 ) / 230 = 6.261 A. I = ( 4 x 18 ) + ( 7 x 9 ) + ( 2 x 45 ) / 230 = 0.978 A. I = 16.700 A.
Ic = 1.356 x 1.25 = 1.695 A. Ic = 6.261 x 1.25 = 7.826 A. Ic = 0.978 x 1.25 = 1.222 A. Ic = 16.700 A x 1.25 = 20.875 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 20 At, 30 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

PP-1/Ckt. 6 & 13 ( IDENTICAL) - CONVENIENCE OUTLET PP-2/Ckt. 6 - CONVENIENCE OUTLET ( RANGE ) PP-3/Ckt. 6, 8-10 (IDENTICAL) - CONVENIENCE OUTLET PP-4 /Ckt. 7 & 10 ( IDENTICAL ) - AIR CONDITIONING UNIT LOAD, 5.00 HP
I = ( 7 x 180 ) / 230 = 5.478 A. I = 1,500 / 230 = 6.522 A. I = ( 8 x 180 ) / 230 = 6.261 A. I = 10.900 A.
Ic = 5.478 x 1.25 = 6.847 A. Ic = 6.522 x 1.25 = 8.152 A. Ic = 6.261 x 1.25 = 7.826 A. Ic = 10.900 A x 1.25 = 13.625 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

PP-1/Ckt. 7 & 12 (IDENTICAL) - CONVENIENCE OUTLET PP-2/Ckt. 7 CONVENIENCE OUTLET ( REFRIGERATOR ) PP-3/Ckt. 7 - CONVENIENCE OUTLET PP-4 /Ckt. 5-8 ( IDENTICAL ) - AIR CONDITIONING UNIT LOAD, 5.00 HP
I = ( 8 x 180 ) / 230 = 6.261 A. I = 780 / 230 = 3.391 A. I = ( 7 x 180 ) / 230 = 5.478 A. I = 22.000 A.
Ic = 6.261 x 1.25 = 7.826 A. Ic = 3.391 x 1.25 = 4.239 A. Ic = 5.478 x 1.25 = 6.847 A. Ic = 22.000 A x 1.25 = 27.500 A.
USE: 2 - 3.5 MM² THHN./THWN C.U. IN 20 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

SUB-MAIN CIRCUIT COMPUTATION (PB-3)


PP-1/Ckt. 14 CONVENIENCE OUTLET ( REFRIGERATOR ) PP-2/Ckt. 8 & 9 CONVENIENCE OUTLET I = 1.732 x ( 13.839 + (6.261 x 0.25) = 26.679 A. SUB-MAIN CIRCUIT COMPUTATION (PB-4)
I = 780 / 230 = 3.391 A. I = ( 7 x 180 ) / 230 = 5.478 A. Ic = 26.679 x 1.25 = 33.349 A. I = 1.732 x (38.878 + (16.700 x 0.25) = 74.568 A.
Ic = 3.391 A x 1.25 = 4.239 A. Ic = 5.478 x 1.25 = 6.847 A. USE: 3-30 MM² THHN/THWN CU. ON 40 MM Ø RSC PIPE Ic = 74.568 x 1.25 = 93.210 A.
USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 3.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT 1-14 MM² THW CU WIRE ( GROUNDING WIRE ) USE: 3-30 MM² THHN/THWN CU. ON 40 MM Ø RSC PIPE
30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 100 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION 1-14 MM² THW CU WIRE ( GROUNDING WIRE )
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING 125 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION
MAIN CIRCUIT COMPUTATION
SUB-MAIN CIRCUIT COMPUTATION (PB-2) I = 28.00 + 42.00 + (1.732 x 231.178 ) + (42.00 x 0.25) = 480.90 A
PP-1/Ckt. 15 CONVEINCE OUTLET ( RANGE )
I = 1500 / 230 = 6.522 A.
I = 1.732 x (19.826 + (6.522 x 0.25) = 37.162 A.
Ic = 37.162 x 1.25 = 46.452 A.
DESIGN ANALYSIS: PB-3A Ic = 480.90 x 1.25 = 601.125 A
USE: 2 SETS,3-200 MM² THW CU WIRE ON 80 MMØ RSC Pipe
Ic = 6.522 A x 1.25 = 8.152 A. USE: 3-30 MM² THHN/THWN CU. ON 40 MM Ø RSC PIPE PER PHASE SET OF WIRE
USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT 1-14 MM² THW CU WIRE (GROUNDING WIRE) PP-3/Ckt. 11-14 , 16, & 19-22 ( IDENTICAL ) AIR CONDITIONING UNIT LOAD, 2.50 HP
1-38 MM² THW CU WIRE ( GROUNDING WIRE )
30 At, 40 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 100 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION I = 10.900 A.
500 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING Ic = 10.900 A x 1.25 = 13.625 A.
USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
SUB-MAIN CIRCUIT COMPUTATION (PB-1)
I = 1.732 x (25.735 + (6.261 x 0.25) = 47.284 A.
DESIGN ANALYSIS: PB-2A 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

Ic = 47.284 x 1.25 = 59.105 A.


USE: 3-30 MM² THHN/THWN CU. ON 40 MM Ø RSC PIPE
PP-2/Ckt. 13-14,16-17,20-23 ( IDENTICAL ) - AIR CONDITIONING UNIT LOAD, 2.50 HP PP-3/Ckt. 15, 17-18 ( IDENTICAL ) - AIR CONDITIONING UNIT LOAD, 4.00 HP
1-14 MM² THW CU WIRE ( GROUNDING WIRE ) I = 10.900 A. I = 16.700. A.
100 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION Ic = 10.900 A x 1.25 = 13.625 A. Ic = 16.700 A x 1.25 = 20.875 A.
USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT
30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 1 - 3.5 MM² THHN/THWN. CU. GROUNDING

PP-2/Ckt. 15,18-19 ( IDENTICAL ) - AIR CONDITIONING UNIT LOAD, 4.00 HP SUB-MAIN CIRCUIT COMPUTATION (PB-3A)
I = 16.700 A. I = 1.732 x ( 55.20 + (16.70 x 0.25) = 102.837 A.
Ic = 16.700 A x 1.25 = 20.875 A. Ic = 102.837 x 1.25 = 128.546 A.
USE: 2 - 5.5 MM² THHN./THWN C.U. IN 25 MM Ø uPVC CONDUIT USE: 3-50 MM² THHN/THWN CU. ON 50 MM Ø RSC PIPE
30 At, 50 AF, 10 KAIC 2P CB FOR BRANCH CIRCUIT PROTECTION 1-14 MM² THW CU WIRE ( GROUNDING WIRE )
1 - 3.5 MM² THHN/THWN. CU. GROUNDING 150 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION

SUB-MAIN CIRCUIT COMPUTATION (PB-2A)


I = 1.732 x (49.40 + (16.70 x 0.25) = 92.792 A.
Ic = 92.792 x 1.25 = 115.99 A.
USE: 3-50 MM² THHN/THWN CU. ON 50 MM Ø RSC PIPE
1-14 MM² THW CU WIRE ( GROUNDING WIRE )
150 At 3P BOLT- ON CB FOR MAIN CIRCUIT PROTECTION

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
3-50KVA,13.2 KV/240V, 60Hz
OIL IMMERSE DISTRIBUTION 2SETS,3-200mm² THW C.U WIRE
TRANSFORMER IN 80mmØ RSC Pipe
per Phase Set of Wire

SERVICE
ENTRANCE
3-WIRE, THREE PHASE KW-HR METER
+ GROUND

500AT, BOLT ON
IN NEMA-1
METALLIC ENCLOSURE
200KVA STANDBY
GEN. SET
3ɸ,230V, 60Hz
~
G
150AT 500AT,3P

ATS/MTS 1-38mm² THW Cu WIRE


(Grounding)
PROVIDE GROUNDING ROD
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm

2SETS,3-125mm² THHN/THWN Cu Wire


in 100mm Ø RSC Pipe

3-50mm² THHN/THWN Cu Wire


in 50mm Ø RSC Pipe
3-30mm² THHN/THWN Cu Wire
in 40mm Ø RSC Pipe

MDP 1-38mm² THW Cu WIRE


(Grounding)
PROVIDE GROUNDING ROD
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm

3-30mm² THHN/THWN Cu Wire 3-30mm² THHN/THWN Cu Wire


in 40mm Ø RSC Pipe in 40mm Ø RSC Pipe

3-50mm² THHN/THWN Cu Wire


PANELBOARD 3 1-14mm² THW Cu WIRE in 50mm Ø RSC Pipe
(Grounding) 1-14mm² THW Cu WIRE
PANELBOARD 2A
PROVIDE GROUNDING ROD (Grounding)
3-30mm² THHN/THWN Cu Wire
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm PROVIDE GROUNDING ROD
in 40mm Ø RSC Pipe
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm

3-38mm² THHN/THWN Cu Wire


in 50mm Ø RSC Pipe

PANELBOARD 3A 1-14mm² THW Cu WIRE


1-14mm² THW Cu WIRE (Grounding)
PANELBOARD 4
1-14mm² THW Cu WIRE (Grounding) PROVIDE GROUNDING ROD
PANELBOARD 2
(Grounding) PROVIDE GROUNDING ROD COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm
PROVIDE GROUNDING ROD COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm
PANELBOARD 1A 1-14mm² THW Cu WIRE
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm
(Grounding)
PROVIDE GROUNDING ROD
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm

SINGLE LINE DIAGRAM

PANELBOARD 1 1-14mm² THW Cu WIRE


(Grounding)
PROVIDE GROUNDING ROD
COPPER CLAD STEEL ROD 16 mm Ø x 2400 mm

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
FORT SAN PEDRO, ILOILO CITY SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.15 2.72 0.79 2.98 6.21 2.77 0.48 4.11 3.15 2.72 3.75 4.29 3.29 1.34 0.57 4.11

1.16

1.16
UP UP

1 1
DW LANDING DW LANDING
PANTRY PWD CR DN
1.62 C C IT/ DATA CENTER STAIR
STAIR

2.53

2.54
PWD CR W EOLR LOBBY

2.88
LOBBY KITCHEN W

3.18
C H S S C H
PANTRY
S S
KITCHEN UP UP
WCR WCR
4.76

4.76
1.53

0.64
M W W
W S
M
S EOLR

1.60
MCR MCR W
S S S S
C FACP
2.50

2.53
S
2 S 2 S S S

1.17
W STORAGE
1.07

1.07
STO STO
MEETING ROOM 3
3 3

6.87
FACP S
OFFICE AREA OFFICE AREA

15.14
W M INFORMATION S S W M
13.98

13.98

13.98
2.67

2.66
P.E. EOLR S S S P.E. S
ELEVATOR LOBBY ELEVATOR LOBBY

3.69
S
3.57

3.57
S S S
MEETING ROOM 1 MEETING ROOM 2
S
LANDING LANDING STAIR
LOBBY
UP UP LOBBY W
4 S S
4
2.92

W W

3.34
S S TOI TOI
1.81

1.81
2.12

2.27
STORAGE W C DN C
EXECUTIVE EXECUTIVE
TO FACP TO FACP
5 5 OFFICE - 1 OFFICE - 2

4.58
S S S S
1.39

ENTRY PORCH MEETING ROOM


S S
2.76

2.76
LANDING

2.45

2.31
2.32
C C
TOI TOI
1.34

RAMP

6 6
UP

EOLR

4.32 1.42 4.82 3.35 1.48 3.15 4.67 0.50 3.45 2.29 4.82 3.35 1.41 3.35 4.55

23.22 23.22

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

CEILING LINE
W W C C C EOLR

S M S S S S
1 1 2 3 4
EOLR S
5

ROOF DECK FLOOR

CEILING LINE
W W C C W C C C C W C C W EOLR

NOTES : FDAS LEGEND M S S S S S S S S S S S


1 2 3 4 5 6 7 8 9 10 11

1208(1) - FIRE ALARM SYSTEM : ROUGH-INS ONLY EOLR S S S S S M S


SYMBOLS DESCRIPTION OF ITEM 5 4 3 2 1 12

1101(1) - AUXILIARY SYSTEM : ROUGH-INS ONLY THIRD FLOOR


M MANUAL CALL POINT
CEILING LINE
S SMOKE DETECTOR W W C C C W W W W C C EOLR

W WALL MOUNTED BELL M S S S S S S S S S S


1 2 3 4 5 6 7 8 9 10

C EOLR S H S S S S M S
CEILING MOUNTED STROBE
1 4 3 2 1 11

W WALL MOUNTED HORN/SOUNDER/STROBE SECOND FLOOR

H HEAT DETECTOR CEILING LINE


W W C C C W W C C W W EOLR

EOLR
END OF LINE RESISTOR S S S S S S S S S S S S S S
1 2 3 4 5 6 7 8 9 10 11 12 13 14
FACP FIRE ALARM CONTROL PANEL EOLR S M S S H S S S S M S
FACP 3 2 1 4 3 2 1 15

GROUND FLOOR

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.20 1.39 3.11 3.02 3.19 3.30 1.41 4.59 3.16 2.59 8.17 1.31 0.93 2.40 4.67

4.28

1 1
TOLETI
LANDING
B&ATH
DN PWD CR

1.68
T&B F*-

DOUBLE
C EOLR

DECK
BED
TOLETI
2.44

2.54
BED
CHANG
NG
I

DECK
WCR

DOUBLE
C ROOM C
FEMALE
B&ATH W
C
T&B W/
EXECUTIVE EXECUTIVE STAFF STAFF CHANGING ROOM WELLNESS OPEN

1.21
4.76

4.90
ROOM QUARTERS 1 QUARTERS 2
S 1 ROOM
S 2 S S S CENTER S GAZEBO

O
RONIF
LE
5.83

STORAGE
MALE EOLR

DOUBLE
DECK
BED
S

BED
DECK
DOUBLE

1.29
2.45

2.30
C C TOLETI S
MCR
B&ATH CLEAN LINEN
EOLR T&B CHANG
NG
I
ROOM C
2 2

1.48
M FACP
0.77
1.07

W M W

1.49
STORAGE S H A L L W A Y S S
3 S 3
S LOUNGE AREA

DOUBLE

2.56
13.98

13.98
13.98

13.98
2.61

DECK
BED
ELEVATOR LOBBY BALCONY S EOLR S S

4.50
P.E. P.E. ELEVATOR LOBBY EVENT AREA
DOUBLE W
DECK

IF
3.57
3.57

LE
O
RON
BED S

3.12
STAFF S S
QUARTERS 3 S
LANDING W M
UP
4 T&B 4

3.18
3.08

C
FACP

W W

1.20
TOI
LANDING
1.81

1.81
DN C DN
TO FACP TO FACP RON
O
LE
IF
5 C 5
T&B STAFF
S S

4.53
QUARTERS 4
EXECUTIVE EXECUTIVE
S ROOM 3 ROOM 4

3.37
2.76

2.76
2.64

2.59
DOUBLE C
TOI
DECK
BED
BED
DECK
DOUBLE

6 6

2.04 1.39 1.27 3.46 1.41 3.40

0.50 3.58 2.16 4.70 3.46 4.81 4.50 0.50 5.75 8.35 4.44 4.67

23.22 23.22

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

CEILING LINE
W W C C C EOLR

S M S S S S
1 1 2 3 4
EOLR S
5

ROOF DECK FLOOR

CEILING LINE
W W C C W C C C C W C C W EOLR

NOTES : FDAS LEGEND M S S S S S S S S S S S


1 2 3 4 5 6 7 8 9 10 11

1208(1) - FIRE ALARM SYSTEM : ROUGH-INS ONLY EOLR S S S S S M S


SYMBOLS DESCRIPTION OF ITEM 5 4 3 2 1 12

1101(1) - AUXILIARY SYSTEM : ROUGH-INS ONLY THIRD FLOOR


M MANUAL CALL POINT
CEILING LINE
S SMOKE DETECTOR W W C C C W W W W C C EOLR

W WALL MOUNTED BELL M S S S S S S S S S S


1 2 3 4 5 6 7 8 9 10

C CEILING MOUNTED STROBE EOLR S H S S S S M S


1 4 3 2 1 11

W WALL MOUNTED HORN/SOUNDER/STROBE SECOND FLOOR

H HEAT DETECTOR CEILING LINE


W W C C C W W C C W W EOLR

EOLR
END OF LINE RESISTOR S S S S S S S S S S S S S S
1 2 3 4 5 6 7 8 9 10 11 12 13 14
FACP FIRE ALARM CONTROL PANEL EOLR S M S S H S S S S M S
FACP 3 2 1 4 3 2 1 15

GROUND FLOOR

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F A B C D E F
23.22 23.22

5.75 4.82 3.35 4.63 4.67 5.75 4.82 3.35 4.63 4.67

3.15 2.72 0.79 2.98 6.21 2.77 0.48 4.11 3.15 2.72 3.75 4.29 3.29 1.34 0.57 4.11

TO DVR
TO DVR
CCTV
CCTV
TO DVR
1.16

1.16
UP UP
CCTV
CCTV
STEEL BOX STEEL BOX
1 1
DW RISER LANDING DW MDF PAD LANDING
PANTRY PWD CR DN
1.62

TO DVR CCTV TO DVR IT/ DATA CENTER STAIR CCTV


STAIR

2.53

2.54
PWD CR LOBBY

2.88
LOBBY KITCHEN

3.18
TO DVR PANTRY
KITCHEN UP UP
WCR WCR
4.76

4.76
1.53

CCTV

0.64
TO DVR

1.60
MCR MCR TO DVR
CCTV
2.50

CCTV

2.53
2 TO DVR 2

1.17
STORAGE
1.07

1.07
STO STO
MEETING ROOM 3
3 3

6.87
OFFICE AREA OFFICE AREA

15.14
INFORMATION
CCTV CCTV CCTV TO DVR
13.98

13.98

13.98
2.66
2.67

P.E. TO DVR P.E.


ELEVATOR LOBBY TO DVR ELEVATOR LOBBY

3.69
3.57

3.57
MEETING ROOM 1 MEETING ROOM 2
LANDING LANDING STAIR
LOBBY TO DVR
UP UP LOBBY
CCTV CCTV
4 4
TO DVR
2.92

TO DVR

3.34
TOI TOI
TO DVR
1.81

1.81
2.12

2.27
STORAGE DN
CCTV CCTV EXECUTIVE EXECUTIVE
CCTV OFFICE - 1
5 5 OFFICE - 2
CCTV

4.58
CCTV
1.39

ENTRY PORCH TO DVR MEETING ROOM


TO DVR
2.76

2.76
LANDING

2.45

2.31
2.32
TO DVR
TO DVR TOI TOI
1.34

RAMP
CCTV
6 CCTV 6
TO DVR UP
CCTV
CCTV
TO DVR
CCTV

TO DVR
4.32 1.42 4.82 3.35 1.48 3.15 TO DVR 4.67 0.50 3.45 2.29 4.82 3.35 1.41 3.35 4.55

23.22 23.22

S C A L E : 1 : 1 0 0 M T S S C A L E : 1 : 1 0 0 M T S

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.
CHECKED:
FORT SAN PEDRO, ILOILO CITY DPWH REGIONAL OFFICE VI - R.E.S. AREA
SEVERO A. RUIZ OIC-PLANNING AND DESIGN DIVISION OIC-ASST. REGIONAL DIRECTOR REGIONAL DIRECTOR HEAD - PRESIDENTIAL MANAGEMENT STAFF
FORT SAN PEDRO, ILOILO CITY
OIC-ASST., PLANNING & DESIGN DIVISION DATE: DATE: DATE: DATE:
A B C D E F
23.22 CEILING LINE

5.75 4.82 3.35 4.63 4.67


1 2 3 6 7 8 9 10

3.20 1.39 3.11 3.02 3.19 3.30 1.41 4.59

ROOF DECK FLOOR

CEILING LINE

TO DVR

1 1 2 3 4 5 6
RISER TOLETI
B&ATH
LANDING
T&B DN F*-

DOUBLE
CCTV

DECK
BED
TOLETI
2.44

2.54
BED
CHANG
NG
I

DECK
DOUBLE
B&ATH
ROOM FEMALE THIRD FLOOR
T&B W/
EXECUTIVE EXECUTIVE STAFF STAFF CHANGING ROOM CEILING LINE
4.76

ROOM 1 ROOM 2 QUARTERS 1 QUARTERS 2

MALE

DOUBLE
DECK
BED
BED
DECK
DOUBLE
2.45

2.30
TOLETI 1 2 3 4 6 7 8 9 10
B&ATH CLEAN LINEN
T&B CHANG
NG
I TO DVR
ROOM
2 SECOND FLOOR
CCTV
0.77
1.07

CEILING LINE

1.49
STORAGE H A L L W A Y
CCTV
3 COMPUTER

LOUNGE AREA UPS

DOUBLE
DVR
13.98

13.98
2.61

DECK
BED
P.E. ELEVATOR LOBBY BALCONY
TO DVR DOUBLE 1 2 3 4 14 15 16 17
DECK
3.57

ROUTER
BED
TO DVR TO DVR

3.12
STAFF
QUARTERS 3 GROUND FLOOR
LANDING
UP CCTV CCTV
4 T&B
3.08

TOI
1.81

DN
CCTV
5 T&B STAFF

4.53
QUARTERS 4
EXECUTIVE EXECUTIVE
TO DVR ROOM 3 ROOM 4
2.76

2.64

DOUBLE

TOI
DECK
BED
BED
DECK
DOUBLE

2.04 1.39 1.27 3.46 1.41 3.40 LEGEND:


CCTV SYSTEM LEGEND
METALLIC WIREWAYS INSTALLED UNDER
0.50 3.58 2.16 4.70 3.46 4.81 4.50 SYMBOLS DESCRIPTION OF ITEM CONCRETE SLAB/FLOORING

METALLIC WIREWAYS INSTALLED


ABOVE CEILING
23.22 WIDE ANGLE CCTV CAMERA
2-GANG DATA PLATE W/ DATA
MODULAR JACK
DVR DIGITAL VIDEO RECORDER
25mm∅ PVC CONDUIT W/
M MONITOR 2 Cat 6/ Cat 5 UTP CABLE

S C A L E : 1 : 1 0 0 M T S
PB W/ POE
SWITCH PULL BOX WITH POE SWITCH
CORE SWITCH/ROUTER/VIDEO
CRVS
RECORDER/SERVER

N NETWORK SWITCH
NOTES :
COMPUTER COMPUTER (WORK STATION)
1208(1) - FIRE ALARM SYSTEM : ROUGH-INS ONLY
UPS UNINTERRUPTED POWER SUPPLY

PATCH PANEL PATCH PANEL 1101(1) - AUXILIARY SYSTEM : ROUGH-INS ONLY

DRAWN:
PROJECT TITLE / LOCATION: SHEET CONTENTS: SUBMITTED: RECOMMENDING APPROVAL: APPROVED: CONCURRED: SHEET NO.:
DWIGHT H. CARIAS
REPUBLIC OF THE PHILIPPINES ADMIN ASST. III

DESIGNED: (SEE COVER SHEET) (SEE COVER SHEET) (SEE COVER SHEET)
DEPARTMENT OF PUBLIC WORKS AND HIGHWAYS THE PMS-OP INTEGRATED OPERATIONS &
SERVICE CONTINUITY BUILDING ALEXANDER C. PARREÑO
REGION VI, WESTERN VISAYAS AS SHOWN ENGINEER II
MARILOU G. ZAMORA JOSE AL V. FRUTO, CESE LEA N. DELFINADO, CESO III USEC. FERDINAND B. CUI, JR.