MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-AC1B


CIRCUIT NO. 1, 2, 3, 4, 5, 6, 7
LOAD DESCRIPTION: VRF - 42 kW
TYPE OF MOTOR: ALTERNATING CURRENT
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 60.624 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (60.624 A) = 106.0.92 A

USE: 3 – 30mm2 + 1-8.0mm2 , THHN COPPER WIRE/115 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (60.624 A) = 106.0.92 A

Overload Device not more than 106.0.92 A

USE: 3P – 100 AT, 100 AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-AC1B


CIRCUIT NO. 8
LOAD DESCRIPTION: FAHU - 01 - 18 kW
TYPE OF MOTOR: ALTERNATING CURRENT
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 26.982 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (25.982 A) = 45.4685 A

USE: 3 – 8.0mm2 + 1-5.5mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (25.982 A) = 45.4685 A

Overload Device not more than 45.4685 A

USE: 3P – 40AT, 100 AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-AC1B


CIRCUIT NO. 9
LOAD DESCRIPTION: FAHU-CU - 84kW
TYPE OF MOTOR: ALTERNATING CURRENT
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 121.247 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (121.247 A) = 212.18225 A

USE: 3 – 80mm2 + 1-14mm2 , THHN COPPER WIRE/ 205 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (121.247 A) = 212.18225 A

Overload Device not more than 212.18225 A

USE: 3P – 225AT, 225 AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 1, 2
LOAD DESCRIPTION: EVERISING SAW - 12 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 17.321A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (17.321 A) = 30.31175 A

USE: 3 – 8mm2 + 1-5.5mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (17.321 A) = 30.31175 A

Overload Device not more than 30.31175 A

USE: 3P – 40AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 3,4
LOAD DESCRIPTION: VANTAGE - 30.4 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 43.880 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (43.880 A) = 76.79 A

USE: 3 – 22mm2 + 1-8.0mm2 , THHN COPPER WIRE/ 95 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (43.880 A) = 76.79 A
Overload Device not more than 76.79 A

USE: 3P – 80 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 5
LOAD DESCRIPTION: ANYK-6000 - 48 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 69.284 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (69.284 A) = 121.247A

USE: 3 – 38mm2 + 1-14mm2 , THHN COPPER WIRE/ 130 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (69.284 A) = 121.247A

Overload Device not more than 121.247A

USE: 3P – 125 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 6
LOAD DESCRIPTION: HBM - 16 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 23.095 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (23.095 A) = 28.86875 A

USE: 3 – 8.0mm2 + 1-5.5mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (23.095 A) = 28.86875 A

Overload Device not more than 28.86875 A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 7
LOAD DESCRIPTION: ANYK-800- 48kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 69.284 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (69.284 A) = 121.247 A

USE: 3 – 22mm2 + 1-8.0mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (69.284 A) = 121.247 A

Overload Device not more than 121.247 A

USE: 3P – 125AT, 225AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 8
LOAD DESCRIPTION: ANYK-3300- 48kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 69.284 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (69.284 A) = 121.247 A

USE: 3 – 22mm2 + 1-8.0mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (69.284 A) = 121.247 A

Overload Device not more than 121.247 A

USE: 3P – 125AT, 225AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 9
LOAD DESCRIPTION: VERTICAL HONE 4000 W
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 5.774 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.25) × (5.774 A) = 7.2175 A

USE: 3 – 22mm2 + 1-8.0mm2 , THHN COPPER WIRE/ A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (5.774 A) = 7.2175 A

Overload Device not more than 7.2175 A

USE: 3P – 30AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 10
LOAD DESCRIPTION: BUTTON PRESS 16 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 23.095 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (23.095 A) = 28.86875 A

USE: 3 – 8.0mm2 + 1-5.5mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (23.095 A) = 28.86875 A

Overload Device not more than 28.86875 A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 11
LOAD DESCRIPTION: MATTISON 30.4 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 44.880 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (44.880 A) = 78.54 A

USE: 3 – 22mm2 + 1-8.0mm2 , THHN COPPER WIRE/ 95 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (44.880 A) = 78.54 A

Overload Device not more than 78.54 A

USE: 3P – 80AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 12
LOAD DESCRIPTION:TOYODA 16.0 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 23.095 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (23.095 A) = 28.86875 A

USE: 3 – 8.0mm2 + 1-5.5mm2 , THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (23.095 A) = 28.86875 A

Overload Device not more than 28.86875 A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 13, 14
LOAD DESCRIPTION:COMPRESSOR 96.0 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 138.568 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (138.568 A) = 173.21A

USE: 3 – 80mm2 + 1-14mm2, THHN COPPER WIRE/ 205A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 65 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (138.568 A) = 173.21A

Overload Device not more than 173.21A

USE: 3P – 200AT, 225AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10A


CIRCUIT NO. 15, 16
LOAD DESCRIPTION: DRYER 8.0 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 11.547 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (11.547 A) = 20.20725A

USE: 3 – 8.0mm2 + 1- 5.5mm2, THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (11.547 A) = 20.20725A

Overload Device not more than 20.20725A

USE: 3P – 40AT, 225AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. 1
LOAD DESCRIPTION: EJECTOR DRILL 80 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 115.4734 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (115.4734 A) = 202.07845A

USE: 3 – 80mm2 + 1- 14mm2, THHN COPPER WIRE/ 205 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 65 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (115.4734 A) = 202.07845A

Overload Device not more than 202.07845 A

USE: 3P – 200AT, 225AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. 2, 3
LOAD DESCRIPTION: VANTAGE/L - 30.4kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 43.8799 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (43.8799 A) = 76.7898 A

USE: 3 – 22mm2 + 1- 8.0mm2, THHN COPPER WIRE/ 95A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (43.8799 A) = 76.7898 A

Overload Device not more than 76.7898 A

USE: 3P – 80 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. 4
LOAD DESCRIPTION: TREPANNER - 160kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 230.9469 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (230.9469A) = 404.1571A

USE: 3 – 250mm2 + 1- 30mm2, THHN COPPER WIRE/ 425A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (230.9469A) = 404.1571A

Overload Device not more than 404.1571A

USE: 3P – 400 AT, 400AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. 5
LOAD DESCRIPTION: PUMP BORE - 160 kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 230.9469 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (230.9469A) = 404.1571A

USE: 3 – 250mm2 + 1- 30mm2, THHN COPPER WIRE/ 425A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (230.9469A) = 404.1571A

Overload Device not more than 404.1571A

USE: 3P – 400 AT, 400AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. 6, 7
LOAD DESCRIPTION: CENTURY HONE - 32kW
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 46.1894 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (175%) × (IFL) = (1.75) × (46.1894A) = 80.83145A

USE: 3 – 22mm2 + 1- 8.0mm2, THHN COPPER WIRE/ 95 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (46.1894A) = 80.83145A

Overload Device not more than 80.83145A

USE: 3P – 80 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. 8
LOAD DESCRIPTION: DB-SPL10
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 45.7 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (45.7 A) =

USE: 3 – 22mm2 + 1- 8.0mm2, THHN COPPER WIRE/ 95 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 32 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.75) × (46.1894A) = 80.83145A

Overload Device not more than 80.83145A

USE: 3P – 80 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NUMBER: R1, Y1, B1, R2, Y2, B2, R3, Y3
LOAD DESCRIPTION: 250W LIGHTING
NO. OF LIGHTING OUTLETS: 3
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (3) x (250W)
= 750 VA
I
LOAD CURRENT, L:

I L = (VA/Crt) / (Operating Voltage)


=750 VA) / (230 V)
=3.2607 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/30A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NUMBER: B3
LOAD DESCRIPTION: 250W LIGHTING
NO. OF LIGHTING OUTLETS: 5
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (5) x (250W)
= 1250 VA
I
LOAD CURRENT, L:

I L = (VA/Crt) / (Operating Voltage)


=1250 VA) / (230 V)
= 5.4348 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/30A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NUMBER: R4, Y4, B4
LOAD DESCRIPTION: 250W LIGHTING
NO. OF LIGHTING OUTLETS: 3
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (3) x (250W)
= 750 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=750 VA) / (230 V)
=3.2607 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/30A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NUMBER: R1, Y1, B1, R2, Y2, B2
LOAD DESCRIPTION: 1-16A SWITCH OUTLET
NO. OF OUTLET: 1
FULL-LOAD CURRENT:10.4348A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (10.4348A) = 12.7935 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (10.4348A) = 12.7935 A

Overload Device not more than 12.7935 A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. (R3-Y3-B3)
LOAD DESCRIPTION: SHUTTER DOOR - 5000 W
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 7.2171 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (7.2171A) = 9.021375 A

USE: 3 – 8.0 mm2 + 1- 5.5 mm2, THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (7.2171A) x (3) = 27.0641 A

Overload Device not more than 27.0641 A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. (R4-Y4-B4)
LOAD DESCRIPTION: MF-AHU-010- 6000 W
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 8.6605 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (8.6605A) = 10.8256 A

USE: 3 – 8.0 mm2 + 1- 5.5 mm2, THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (8.6605A) x (3) = 32.4768 A

Overload Device not more than 32.4768 A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NUMBER: R5, Y5
LOAD DESCRIPTION: 1-16A SWITCH OUTLET
NO. OF OUTLET: 1
FULL-LOAD CURRENT: 10.4348A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (10.4348A) = 12.7935 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)

I(OVERLOAD DEVICE) = (1.25) × (10.4348A) = 12.7935 A

Overload Device not more than 12.7935 A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-SB10


CIRCUIT NO. (R6-Y6-B6), (R7-Y7-B7)
LOAD DESCRIPTION: JIB CRANES - 3000 W
NO. OF PHASE: 3 PHASE
FULL-LOAD CURRENT: 4.3303 A
OPERATING VOLTAGE: 400/230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (4.3303A) = 5.4129 A

USE: 3 – 3.5 mm2 + 1- 3.5 mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (4.3303A) x (3) = 16.2386 A

Overload Device not more than 16.2386 A

USE: 3P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-GLP


CIRCUIT NUMBER: 1
LOAD DESCRIPTION: DB-GLP - 17.82 kW
NO. OF CIRCUITS: 24
TOTAL CURRENT LOAD: 25.7217 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (25.7217) = 32.1521A

USE: 3 – 3.0 mm2 + 1- 5.5m2, THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (25.7217) = 32.1521A

Overload Device not more than 32.1521A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-GLP


CIRCUIT NUMBER: 2
LOAD DESCRIPTION: DB-ML - 12.10 kW
NO. OF CIRCUITS: 16
TOTAL CURRENT LOAD: 17.4654 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (17.4654) = 21.8318A

USE: 3 – 3.0 mm2 + 1- 5.5m2, THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (17.4654) = 21.8318A

Overload Device not more than 21.8318A

USE: 3P – 40 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: SMDB-GLP


CIRCUIT NUMBER: 3
LOAD DESCRIPTION: DB-MP - 23.04 kW
NO. OF CIRCUITS: 16
TOTAL CURRENT LOAD: 33.2564 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (33.2564 ) = 41.5705

USE: 3 – 3.0 mm2 + 1- 5.5m2, THHN COPPER WIRE/ 55 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 20 mm Ø IMT/RSC/EMT CONDUIT

MOTOR OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)
I(OVERLOAD DEVICE) = (1.25) × (17.4654) = 21.8318A

Overload Device not more than 21.8318A

USE: 3P – 60 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: R1
LOAD DESCRIPTION: 250W LIGHTING
NO. OF LIGHTING OUTLETS: 9
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (9) x (100W)
= 900 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=900 VA) / (230 V)
=3.9130 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: Y1
LOAD DESCRIPTION: 50 W LIGHTING
NO. OF LIGHTING OUTLETS: 13
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (13) x (50W)
= 650 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=650 VA) / (230 V)
=2.8261 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: B1
LOAD DESCRIPTION: 50 W LIGHTING
NO. OF LIGHTING OUTLETS: 22
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (22) x (50W)
= 1100 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=1100 VA) / (230 V)
=4.7826 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: R2
LOAD DESCRIPTION: 100 W LIGHTING
NO. OF LIGHTING OUTLETS: 6
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (6) x (100W)
= 600 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=600 VA) / (230 V)
=2.6087 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: Y2
LOAD DESCRIPTION: 9-100 W LIGHTING
3-50 W LIGHTING
NO. OF LIGHTING OUTLETS: 12
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (9) x (100W) + (3) x (50W)
= 1050 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=1050 VA) / (230 V)
=4.5652 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: B2
LOAD DESCRIPTION: 100 W LIGHTING
NO. OF LIGHTING OUTLETS: 12
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (12) x (100W) )
= 1200 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=1200 VA) / (230 V)
=5.2174 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: R3
LOAD DESCRIPTION: 100 W LIGHTING
NO. OF LIGHTING OUTLETS: 15
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (15) x (100W) )
= 1500 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=1500 VA) / (230 V)
=6.5217 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: R4
LOAD DESCRIPTION: 6-200W 13 A SWITCH OUTLET
NO. OF OUTLET: 6
FULL- LOAD CURRENT: 5.2174 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (5.2174A) = 6.5218 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)

I(OVERLOAD DEVICE) = (1.25) × (5.2174A) = 6.5218 A

Overload Device not more than 6.5218 A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: Y4
LOAD DESCRIPTION: 8-200W 13 A SWITCH OUTLET
NO. OF OUTLET: 8
FULL- LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × ( 6.9565 A ) = 8.15225 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)

I(OVERLOAD DEVICE) = (1.25) × ( 6.9565 A ) = 8.15225 A

Overload Device not more than 8.15225 A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: B4
LOAD DESCRIPTION: 7-200W 13 A SWITCH OUTLET
NO. OF OUTLET: 7
FULL- LOAD CURRENT: 6.0870A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × ( 6.0870A ) = 7.6088 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)

I(OVERLOAD DEVICE) = (1.25) × ( 6.0870A ) = 7.6088 A

Overload Device not more than 7.6088 A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-GLP


CIRCUIT NUMBER: R5
LOAD DESCRIPTION: 7-200W 13 A SWITCH OUTLET
NO. OF OUTLET: 7
FULL- LOAD CURRENT: 6.0870A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × ( 6.0870A ) = 7.6088 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)

I(OVERLOAD DEVICE) = (1.25) × ( 6.0870A ) = 7.6088 A

Overload Device not more than 7.6088 A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DP-GLP


CIRCUIT NO. Y5, B5, R6,
LOAD DESCRIPTION: 1.5 KVA WATER HEATER
NO. OF PHASE: SINGLE PHASE
FULL-LOAD CURRENT: 6.5217A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B)(16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.5217A) = 8.1521A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (NON-METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

USE: 2P -20 AT, MCCB, 400/240 V, 60 Hz


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DP-GLP


CIRCUIT NO. Y6
LOAD DESCRIPTION: 1.5 KVA HAND DRYER
NO. OF PHASE: SINGLE PHASE
FULL-LOAD CURRENT: 6.5217A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B)(16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.5217A) = 8.1521A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (NON-METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

USE: 2P -20 AT, MCCB, 400/240 V, 60 Hz


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DP-GLP


CIRCUIT NO. R7, Y7, B7, R8, Y8, B8
LOAD DESCRIPTION: 1-200W - FAN COIL UNIT
NO. OF PHASE: SINGLE PHASE
FULL-LOAD CURRENT: 0.8696A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B)(16), page 174)

IBF = (125%) × (IFL) = (1.25) × (0.8696A) = 1.087A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (NON-METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

USE: 2P -20 AT, MCCB, 400/240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: R1
LOAD DESCRIPTION: 9-100W LIGHTING
NO. OF LIGHTING OUTLETS: 9
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (9) x (100W) )
= 900 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=900 VA) / (230 V)
=3.9130 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: Y1
LOAD DESCRIPTION: 8- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 8
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (8) x (100W) )
= 800 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=800 VA) / (230 V)
=3.4782 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: B1
LOAD DESCRIPTION: 3- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 3
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (3) x (100W) )
= 300 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=300 VA) / (230 V)
=1.3043 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: R2
LOAD DESCRIPTION: 9- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 9
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (9) x (100W) )
= 900 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=900 VA) / (230 V)
=3.9130 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: Y2
LOAD DESCRIPTION: 8- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 8
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (8) x (100W) )
= 800 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=800 VA) / (230 V)
=3.4782 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: B2
LOAD DESCRIPTION: 10- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 10
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (10) x (100W) )
= 1000 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=1000 VA) / (230 V)
=4.3478 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: R3
LOAD DESCRIPTION: 15 - 100W LIGHTING
NO. OF LIGHTING OUTLETS: 15
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (15) x (100W) )
= 1500 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=1500 VA) / (230 V)
=6.5217 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: Y3
LOAD DESCRIPTION: 4 - 100W LIGHTING
NO. OF LIGHTING OUTLETS: 4
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (4) x (100W) )
= 400VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


=400 VA) / (230 V)
=1.739 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: B3
LOAD DESCRIPTION: 12- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 12
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (12) x (100W) )
= 1200 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 1200 VA) / (230 V)
=5.2174 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: R4
LOAD DESCRIPTION: 8- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 8
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (8) x (100W) )
= 800 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 800 VA) / (230 V)
= 3.4783 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: Y4
LOAD DESCRIPTION: 4- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 4
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (4) x (100W) )
= 400 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 400 VA) / (230 V)
= 1.7391 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: B4
LOAD DESCRIPTION: 4- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 4
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (4) x (100W) )
= 400 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 400 VA) / (230 V)
= 1.7391 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: R5
LOAD DESCRIPTION: 12- 100W LIGHTING
NO. OF LIGHTING OUTLETS:12
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (12) x (100W) )
= 1200 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 1200 VA) / (230 V)
=5.2174 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: Y5
LOAD DESCRIPTION: 9- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 9
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (9) x (100W) )
= 900 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 900 VA) / (230 V)
= 3.9130 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: B5
LOAD DESCRIPTION: 8- 100W LIGHTING
NO. OF LIGHTING OUTLETS: 8
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (8) x (100W) )
= 800 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 800 VA) / (230 V)
= 3.4783 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-ML


CIRCUIT NUMBER: R6
LOAD DESCRIPTION: 3 - 100W LIGHTING
NO. OF LIGHTING OUTLETS: 3
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

CALCULATIONS

VOLT-AMPERE/CIRCUIT:

VA/Ckt = (No. Of Lighting Outlet) x (Watts)


= (3) x (100W) )
= 300 VA
LOAD CURRENT, I L:

I L = (VA/Crt) / (Operating Voltage)


= 300 VA) / (230 V)
= 1.3044 A

SIZING OF CONDUCTOR

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6 (B)(16),P.174)

Use: 2-3.5mm2 + 1-3.5mm2 ,THHN Copper Wire/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

Use: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

Use: 2P – 15 AT, 100 AF, MCCB, 240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R1
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: Y1
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: B1
LOAD DESCRIPTION: 3-200W SWITCH OUTLET
NO. OF OUTLET: 3
FULL-LOAD CURRENT: 2.6087A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (2.6087A) = 3.2609A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (2.6087A) = 3.2609A

Overload Device not more than 3.2609A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R2
LOAD DESCRIPTION: 6-200W SWITCH OUTLET
NO. OF OUTLET: 6
FULL-LOAD CURRENT: 5.2174A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (5.2174A) = 6. 5218A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) ×(5.2174A) = 6. 5218A
Overload Device not more than 6. 5218A
USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: Y2
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


MOTOR BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DP-MP


CIRCUIT NO. B2
LOAD DESCRIPTION: 1.5 KVA WATER HEATER
NO. OF PHASE: SINGLE PHASE
FULL-LOAD CURRENT: 6.5217A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B)(16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.5217A) = 8.1521A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (NON-METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

USE: 2P -20 AT, MCCB, 400/240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R3
LOAD DESCRIPTION: 4-200W SWITCH OUTLET
NO. OF OUTLET: 4
FULL-LOAD CURRENT: 3.4783 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × ( 3.4783A) = 4.3479A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × ( 3.4783A) = 4.3479A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: Y3
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: B3
LOAD DESCRIPTION: 1- 1.5 KVA HAND DRYER
NO. OF PHASE: SINGLE PHASE
FULL-LOAD CURRENT: 6.5217A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B)(16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.5217A) = 8.1521A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (NON-METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERCURRENT PROTECTION: (From Article 2.10.2.6, Section A, page 45)

USE: 2P -20 AT, MCCB, 400/240 V, 60 Hz


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R4
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: Y4
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: B4
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R5
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: Y5
LOAD DESCRIPTION: 8-200W SWITCH OUTLET
NO. OF OUTLET: 8
FULL-LOAD CURRENT: 6.9565 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (6.9565A) = 8.6956A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × (6.9565A) = 8.6956A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: B5
LOAD DESCRIPTION: 4-200W SWITCH OUTLET
NO. OF OUTLET: 4
FULL-LOAD CURRENT: 3.4783 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × ( 3.4783A) = 4.3479A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × ( 3.4783A) = 4.3479A

Overload Device not more than 8.6956A

USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ


BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R6
LOAD DESCRIPTION: 6-200W SWITCH OUTLET
NO. OF OUTLET: 6
FULL-LOAD CURRENT: 5.2174A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (5.2174A) = 6. 5218A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) ×(5.2174A) = 6. 5218A
Overload Device not more than 6. 5218A
USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: Y6
LOAD DESCRIPTION: 6-200W SWITCH OUTLET
NO. OF OUTLET: 6
FULL-LOAD CURRENT: 5.2174A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × (5.2174A) = 6. 5218A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) ×(5.2174A) = 6. 5218A
Overload Device not more than 6. 5218A
USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 HZ
BRANCH CIRCUIT CALCULATIONS

GENERAL INFORMATION

PANEL CODE: DB-MP


CIRCUIT NUMBER: R7, Y7, B7, R8, Y8, B8, R9, Y9, B9, R10, Y10, B10
LOAD DESCRIPTION: 1-200W FCU
NO. OF OUTLET: 1
FULL-LOAD CURRENT: 0.8696 A
OPERATING VOLTAGE: 230 V
OPERATING FREQUENCY: 60 Hz

SIZE OF BRANCH CIRCUIT CONDUCTOR: (From Table 3.10.2.6(B) (16), page 174)

IBF = (125%) × (IFL) = (1.25) × ( 0.8696 A) = 1.087 A

USE: 2 – 3.5 mm2 + 1- 3.5mm2, THHN COPPER WIRE/ 30 A

SIZE OF CONDUIT (METALLIC): (From Table C.10, page 1021)

USE: 15 mm Ø IMT/RSC/EMT CONDUIT

OVERLOAD PROTECTION: (Refer to 4.30.3.2 (1) (Separate Over Load Protection)


I(OVERLOAD DEVICE) = (1.25) × ( 0.8696 A) = 1.087 A
Overload Device not more than 1.087 A
USE: 2P – 20 AT, 100AF, MCCB, 400/230 V, 60 Hz
VOLTAGE DROP

FORMULA: VD=KI √ R L2 + X L2 x ¿ )

FEEDER
GIVEN:
I= 136.4626
1Ф = 50mm²
L= 30meters
R L= 0.12
X L= 0.044
SOLUTION:

VD=2 x (136.4626) √ 0.12 +0.044 ∗¿ )


2 2

VD = 3.4311
3.4311
% VD = x 100
230
% VD = 1.4918%

FARTHEST MOTOR LOAD


GIVEN:
I= 10
1Ф = 3.5 mm²
L= 17 meters
R L= 2.0
X L= 0.054
SOLUTION:

VD=2 x (10) √ 2.0 +0.054 ∗¿ )


2 2

VD =2.2303
2.2303
% VD = x 100
230
% VD =0.9697%
FARTHEST ACU LOAD
GIVEN:
I= 10
1Ф = 3.5 mm²
L= 15 meters
R L= 2.0
X L= 0.054
SOLUTION:

VD=2 x (10) √ 2.0 +0.054 ∗¿ )


2 2

VD =1.9679
1.9679
% VD = x 100
230
% VD =0.8556%

FARTHEST HEATER LOAD


GIVEN:
I= 15.2174
1Ф = 3.5 mm²
L= 15 meters
R L= 2.0
X L= 0.054
SOLUTION:

VD=2 x (15.2174) √ 2.0 +0.054 ∗ ¿)


2 2

VD =2.9947
2.9947
% VD = x 100
230
% VD =1.3020%

THEREFORE WE CONSIDER HEATER AS THE FARTHEST LOAD


TOTAL VD = %VD FEEDER + HIGHEST %VD OF FARTHEST LOADS
TOTAL VD = 1.4918% + 1.3020%
= 2.7938 % < 5%
=ACCEPTABLE
SINCE 2.7938% IS LESSER THAN 5% , IT WILL PROVIDE REASONABLE EFFICIENCY
OF OPERATION