1. FIRE ALARM SYSTEM DESIGN, INSTALLATION AND MATERIALS SHALL BE IN 1.

PROVIDE EQUIPMENT AND CONNECTIONS NECESSARY TO ACTIVATE


ACCORDANCE WITH NFPA 70 AND 72. SYSTEM SHALL ALSO MEET STAIR PRESSURIZATION FANS UPON A FIRE ALARM SIGNAL.
ALL APPLICABLE BUILDING CODES, FIRE CODES AND THE REQUIREMENTS
OF THE AUTHORITY HAVING JURISDICTION AND INSURANCE CARRIER. 2. PROVIDE AMPLIFIER TO POWER AUDIBLE NOTIFICATION APPLIANCES FOR
VERIFY REQUIREMENTS PRIOR TO BID SUBMITTAL. THIS FLOOR. CONNECT TO FIRE ALARM SYSTEM.

2. INFORMATION OF CONTRACT DOCUMENTS IS GENERAL INFORMATION AND 3. PROVIDE EQUIPMENT AND CONNECTION(S) REQUIRED FOR ELEVATOR
FOR BID PURPOSES ONLY. PERFORM REQUIRED CALCULATIONS AND RECALL.
COORDINATE WITH OTHER TRADES.
4. CONNECT EXTERIOR NOTIFICATION APPLIANCE TO FIRE ALARM SYSTEM.
3. DEVIATIONS FROM ENGINEERS LAYOUT WILL NOT BE CONSIDERED APPLIANCE SHALL ONLY ACTIVATE UPON WATERFLOW IN THE BUILDING'S
UNLESS A FORMALLY SUBMITTED RFI IS RECEIVED AND APPROVED. COMBINATION STANDPIPE / SPRINKLER SYSTEM.

4. PROVIDE ADDITIONAL MATERIALS AND LABOR REQUIRED DUE TO LACK 5. CONNECT STANDPIPE / FIRE SPRINKLER MONITORING DEVICES TO FIRE
OF COORDINATION OR TO MEET AUTHORITY HAVING JURISDICTION AND ALARM SYSTEM. COORDINATE QUANTITY AND LOCATION OF DEVICES
INSURANCE CARRIER REQUIREMENTS AT NO ADDITIONAL COST TO THE WITH FIRE PROTECTION SYSTEMS.
OWNER. EOL
6. PROVIDE MONITORING FOR THE FIRE PUMP CONTROL PANEL. REFER TO
5. PROVIDE ALL EQUIPMENT AND LABOR REQUIRED FOR A COMPLETE AND SEQUENCE OF OPERATION AND SPECIFICATIONS FOR ADDITIONAL
OPERATIONAL FIRE ALARM SYSTEM. INFORMATION.

6. THE FIRE ALARM CONTROL PANEL (FACP) SHOWN SHALL BE 7. INSTALL NOTIFICATION APPLIANCE TO BOTTOM OF EXPOSED JOIST OR AT
COORDINATED WITH THE FIRE DEPARTMENT AND AHJ PRIOR TO 30 FT AFF, WHICHEVER IS LOWER, IN ACCORDANCE WITH NFPA 72
INSTALLATION. REQUIREMENTS.

7. PROVIDE AUDIBLE AND VISIBLE NOTIFICATION APPLIANCES AS 8. PROVIDE EQUIPMENT AND CONNECTION(S) REQUIRED FOR ACCESS
INDICATED ON THE DRAWINGS. CONTROL DOOR RELEASE UPON GENERAL ALARM.

8. TAP ALL FIRE ALARM SPEAKERS AT 1/2 WATT UNLESS NOTED OTHERWISE 9. REMOTE FIR ALARM ANNUNCIATOR PANEL.
(BASED ON A SPEAKER OUTPUT OF 78 dBA).
10. PROVIDE LOW VOLTAGE WIRING FROM DUCT DETECTORS INSTALLED IN
9. DO NOT INSTALL SMOKE DETECTORS IN A DIRECT AIR FLOW NOR CLOSER RTU-1 AND RTU-2 ON THE 2ND LEVEL TO REMOTE TEST STATIONS.
THAN 3 FEET (1 METER) FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR INSTALL REMOTE TEST STATIONS AT 48-INCHES AFF.
OPENING.
11. PROVIDE KEY BOX FOR FIRE DEPARTMENT ACCESS. CONNECT TAMPER
10. CEILING MOUNTED DETECTION EQUIPMENT INSTALLED IN AREAS SWITCH TO FIRE ALARM CONTROL PANEL. KEY BOX INSTALLATION SHALL
EXPOSED TO STRUCTURE SHALL BE INSTALLED TO THE UNDERSIDE OF BE RECESSED INTO THE BUILDING CONSTRUCTION SO THAT THE DOOR IS
THE DECK UNLESS NOTED OTHERWISE. FLUSH WITH THE EXTERIOR WALL.

11. PROVIDE DUCT DETECTION AND SHUTDOWN FOR AIR DISTRIBUTION 12. PROVIDE EQUIPMENT SUITABLE FOR ENVIRONMENTAL CONDITIONS.
SYSTEMS EXCEEDING 2000 CFM. DUCT SMOKE DETECTION SHALL
TRANSMIT A SUPERVISORY SIGNAL TO THE FACP. 13. PROVIDE FIREFIGHTER PHONE JACK IN LOCATION INDICATED. INSTALL AT
48-INCHES AFF.
12. PROVIDE FIRE ALARM EQUIPMENT AND CONNECTIONS REQUIRED TO
SHUTDOWN FAN POWERED AIR DISTRIBUTION EQUIPMENT THAT IS LESS 14. PROVIDE FIREFIGHTER PHONE JACK IN ELEVATOR CAR. COORDINATE
2000 CFM AND IS NOT PROVIDED WITH DUCT SMOKE DETECTION WHEN INSTALLATION AND LOCATION WITH ELEVATOR CONTRACTOR.
IT'S RESPECTIVE AIR HANDLING UNIT IS SHUTDOWN.
15. FIRE ALARM CONTROL PANEL LOCATED WITHIN FIRE COMMAND CENTER.
13. FORWARD COMPLETED FIRE ALARM CERTIFICATE OF COMPLETION TO THE CONTROL PANEL TO PROVIDE THE FOLLOWING AUXILIARY FUNCTIONS
OWNER. AND MONITORING IN ADDITION TO TYPICAL FIRE ALARM SYSTEM
FUNCTIONS:
14. REFER TO SPECIFICATIONS FOR ADDITIONAL INFORMATION. A. EMERGENCY VOICE / ALARM COMMUNICATIONS
B. FIRE DEPARTMENT TWO-WAY COMMUNICATIONS
C. FIRE PUMP STATUS INDICATORS
D. DIGITAL ALARM COMMUNICATOR TRANSMITTER
F. RELEASE OF ACCESS CONTROLLED DOORS
G. ACTIVATION OF STAIR PRESSURIZATION SYSTEM(S) THROUGH INPUT TO
HVAC CONTROLS.

16. FIRE COMMAND CENTER TO INCLUDE THE FOLLOWING ADDITIONAL ITEMS


AND FUNCTIONS PER CODE:
A. FIREFIGHTER'S CONTROL PANEL FOR SMOKE CONTROL SYSTEMS
B. GENERATOR STATUS PANEL
C. ELEVATOR STATUS PANEL
D. WORK TABLE WITH SCHEMATIC BUILDING PLANS INDICATING THE
TYPICAL FLOOR PLANS, MEANS OF EGRESS, FIRE PROTECTION SYSTEMS,
FIRE FIGHTING EQUIPMENT AND FIRE DEPARTMENT ACCESS.
E. REFER TO SPECIFICATIONS FOR ADDITIONAL DETAILS.

17. PROVIDE KEY ACTIVATED MANUAL SWITCH FOR DOOR AND ELEVATOR
ACCESS CONTROL OVERRIDE. THE SWITCH SHALL BE CLEARLY LABELED
AND INSTALLED ADJACENT TO THE FIRE ALARM CONTROL PANEL.

18. PROVIDE KEY ACTIVATED MANUAL SWITCH FOR ELEVATOR RECALL


OVERRIDE. THE SWITCH SHALL BE CLEARLY LABELED AND INSTALLED
ADJACENT TO THE FIRE ALARM CONTROL PANEL.

1 LEGENDS, SYMBOLS AND GENERAL NOTES 19. PROVIDE KEY ACTIVATED MANUAL SWITCH FOR AIR HANDLING
EQUIPMENT SHUTDOWN OVERRIDE. THE SWITCH SHALL BE CLEARLY
FDAS-01 SCALE NTS LABELED AND INSTALLED ADJACENT TO THE FIRE ALARM CONTROL
PANEL.
OWNER PROFESSIONAL ELECTRICAL ENGINEER PROJECT TITLE LOCATION SHEET CONTENT REVISIONS DESIGNED BY: SHEET NO.
REV.NO. REASON FOR REVISION DATE AUTOCAD BY:
DATE:
26-DOOR TWO STOREY RESIDENTIAL KM. 38 PEREZ ST., GREEN VALLEY SUBD. CHECK BY: FDAS-01
MR. & MRS. JOHNNY PRONACI PULONG BUHANGIN, SANTA MARIA, BULACAN AS SHOWN
APARTMENT BUILDING DATE:
APPROVED BY:
SCALE: NTS JOB NO.

You might also like