Professional Documents
Culture Documents
15
Feeders
Feeders
Scope: [2.15.1.1](p.91)
Article 2.15(p.91) covers the installation and
minimum conductor sizing requirement for feeders,
Figure 1.
Feeder
Taps
at the load
side of main
disconnect
(3) The next higher standard rating selected does not exceed
800 amperes.
Feeders
Given
184 A
300
295
I = 184A x 1.25
= 230A (total load)
Notes:
(1) 125 mm2 (or 250 kcmil) THHN has an ampacity
after derating of 265 A x 0.80 (Column 4, Table
3.10.1.6, p.350) = 212 A (less than 230A)
Answers:
Use: (a) 150 mm2 (or 300 kcmil) THHN copper conductor
rated 236A at 75°C and
Feeder
Conductors
Figure 3. Feeder and Branch Grounding Conductors Must Terminate to Individual Terminals
Feeder High-Leg Conductor
Identification
[2.15.1.8](p.94)
Feeder High-Leg Conductor Identification
When a grounded conductor (which is
often called a neutral) is present with a high-leg
feeder conductor, the high-leg conductor must be
identified at each point where a connection is
made.
The identification of the high-leg conductor
shall be by using orange phase tape, painting the
conductor finish orange tagging, or other
effective means.
Feeder High-Leg Conductor Identification
Figure 3. Feeder High Leg Must Be Identified With Color Orange or Other Effective Means
Feeder High-Leg Conductor Identification
Feeder High-Leg Conductor Identification
Single Family Dwelling Unit
Computation
Fireplace recessed
fixtures
Branch Circuit No.1
Step 1:
Total = 1480 W
Branch Circuit No.1
CONDUCTORS
Raceway Size (mm)
Type Conductor 15 20 25 32 40 50 65 80 90 100 125 150
size [mm2(
mm dia.)]
THHN, 2.0 (1.6) 9 17 28 51 70 118 170 265 358 464 736 1055
THWN, 3.5 (2.0) 6 12 20 37 51 86 124 193 261 338 537 770
THWN-2 5.5 (2.6) 4 7 13 23 32 54 78 122 164 213 338 485
8.0 (3.2) 2 4 7 13 18 31 45 70 95 123 195 279
14 1 3 5 9 13 22 32 51 68 80 141 202
22 1 1 3 6 8 14 20 31 42 54 86 124
30 1 1 2 4 6 10 14 22 30 39 61 88
38 0 1 1 3 4 7 10 16 22 29 45 65
Branch Circuit No.1
AFCI
Valance lighting
AFCI
Closet
Paddle fan/light 2
AFCI
AFCI AFCI S 2 S2
Valence Lighting
Branch Circuit No.2
Step 1:
7 - receptacles @ 120 W each = 840 W
1 - weatherproof receptacles @ 120 W = 120 W
Storage
Hallway
S1
AFCI S1 AFCI
Bedroom 2
WP AFCI
Paddle fan/light
Closet
AFCI AFCI S1
Branch Circuit No.3
C. Lighting/Convenience Outlets: Bedroom 2
Step 1:
7 - receptacles @ 120 W each = 840 W
1 - weatherproof receptacle @ 120 W = 120 W
1 – closet fixture @ 75 W = 75 W
1 – storage fixture @ 100 W each = 100 W
1 – paddle fan/light , three 50W lamps = 150 W
fan motor (0.35A,230V) = 81 W
Total = 1366 W
Branch Circuit No.3
S2
Master Bedroom
attic
Dining
a
a attic
S2 Kitchen
S1 S3W
Hall 4
Sa
attic a
Living room
a attic
Bedroom
S1S3W
Branch Circuit No.4
Step 1:
4 – attic lights @ 75 W each = 300 W
1 – hall fixture @ 100 W = 100 W
Total = 900 W
Branch Circuit No.4
S2
Bathroom
Laundry
Sc,3W
S1 Sb
S1 Sc,3W
b b b
c c c
5
Garage Sd
d d
Branch Circuit No.5
E. Lighting Outlets: Bathroom, laundry, garage, outside lighting
Total = 1290 W
Branch Circuit No.5
GFCI
Bathroom GFCI
EF
Branch Circuit No.6
Step 1:
Total = 907 W
Table 4.30.14.2(p.732) Full-Load Currents in Amperes, Single –
Phase Alternating-Current Motors
GFCI
EF
Laundry Room
Branch Circuit No.7
Step 1:
Total = 1207 W
Branch Circuit No. 7
ECD
Laundry Room
Branch Circuit No.8
WH
Bathroom
Branch Circuit No.9
= 5500W/230V = 23.91A
Branch Circuit No.9
Step 3: Overcurrent Protection:
Sf,d
GFCI
GFCI
10
DO
GFCI
Garage GFCI
f e f e
e
Post Lamp Post Lamp Post Lamp Post Lamp Post Lamp
Branch Circuit No.10
Step 1:
Total = 1487 W
Branch Circuit No.10
I = P/V = 1487W/230V
= 6.25 A
= 7.3 A
Branch Circuit No.10
Peninsula
GFCI
rator Range GFCI
Kitchen
GFCI
Dining Island
GFCI
11
Nook
Branch Circuit No.11
GFCI GFCI
Refrige
Peninsula
GFCI
rator Range GFCI
GFCI
Island
Kitchen 12
GFCI
GFCI
Branch Circuit No.12
FL Fixture FL Fixture
Peninsula
C
13
Clock
Hood
Outlet
Fan
Recessed
Ceiling Fixture
Fixtures
Kitchen
Track light
Nook
Branch Circuit No.13
Step 1:
1 – 4 nook track light @ 15W each = 60 W
1 – recessed fixture over sink = 100 W
2– ceiling fixtures, 2-40W FL lamps @1.125 = 80 W
1– clock outlet = 90 W
2 – FL under cabinet lighting fixture @ 40W = 180 W
1 – range hood fan = 360 W
Total = 870 W
Branch Circuit No.13
Step 2: Demand Load (Ampere):
I = P/V = 870W/230V = 3.78 A
Peninsula
Exhaust
Fan EF
Kitchen 14
Nook
Branch Circuit No.14
Electric
Peninsula
Range ER
15
Kitchen
Nook
Branch Circuit No.15
Peninsula
Ref
16
Kitchen
Nook
Branch Circuit No.16
Note: The current listed shall be permitted for system voltage ranges
of 110 to 120volts and 220 to 240 volts.
Branch Circuit No.16
Peninsula
Dishwasher DW
17
Kitchen
Nook
Branch Circuit No.17
Peninsula
Kitchen Waste
Disposer
WD
Nook
17
Branch Circuit No.18
Water Pump
WP
Peninsula
Kitchen
20
Nook
Branch Circuit No.19
Note: The current listed shall be permitted for system voltage ranges
of 110 to 120volts and 220 to 240 volts.
Branch Circuit No.19
ACU
20
Master Bedroom
Branch Circuit No.20
Front Bedroom
21
ACU
Branch Circuit No.21
Dining
Hall 4
22
Living room
ACU
Branch Circuit No.22
1 2
Master Bedroom Lighting 1 Front Bedroom Lighting
20A 20A 2
and Receptacles(2) 3 4 and Receptacles(3)
9 10
Bathroom Attic fan and 5 20A 20A 6 Laundry attic fan and
receptacles (6) 11 12 Receptacles (7)
13 14
7 30A 40A 8 Bathroom Water Heater (9)
Electric clothes dryer (8) 15 16
17 18
Garage receptacles, overhead 9 20A 20A 10 Master Bedroom ACU(20)
Opener and post lamps (10) 19 20
21 22
Front Bedroom ACU (21) 11 15A 20A 12 Living room ACU (22)
23 24
25 26
Sub feeder Panel “B” 13 20A 14 Spare
27 28
Circuit Schedule of
Feeder
Subpanel “B”
1 2
1 Kitchen Receptacles (12)
Kitchen (Dining (11) 20A 20A 2
peninsular) receptacles
3 4 (countertops and island)
5 6
Kitchen/nook lighting(13) 3 15A 15A 4 Kitchen attic,
7 8
exhaust fan (14)
Counter-mounted 9 10
cooking unit(15)
5 30A 15A 6 Refrigerator(16)
11 12
13 14
Dishwasher(17) 7 20A 20A 8 Food waste Disposer(18)
15 16
17 18
Water Pump(19) 9 20A 20A 10 Living room lighting
19 20 and outside receptacles(1)
21 22
Spare 11 20A 20A 24
12 Spare
23