You are on page 1of 5

Phoenix Hotel 25th June , 2007

Mumbai

Elevator Traffic Analysis - Passanger Elevators Option-1

Guest Elevators - 3 Guest Elevators -3


Sr. Selection elevators Ref \ Comments elevators Ref \ Comments
1 Elevators GE3,GE4 GE5,GE6,GE7
2 Speed 4 MPS 4 MPS
2750 mm X 1750 2600 mm (W) x
2 Shaft Size mm 2600 mm (D)
3 Machine room Top M/c Room Top M/c Room
Overhead reqd. from last
4 landing 6500 mm 6500 mm
5 Pit Depth reqd. 4600 mm 4600 mm
6 Number 2 3
7 Group operation 2 3

8 Floors 35 34
9 Capacity
9.1 Passanger 24 24
9.2 Weight(Kg) 1632 68 kg/person 1632 68 kg/person
10 Speed (m/s) 4 4
11 Type geareless geareless
12 Stops
12.1 Up 35 34
12.2 Down 35 34
13 Travel (Mtrs) 150 115
14 Probability
14.1 Up Stops 7 20% of total 7 20% of total
14.2 Down Stops 4 10% of total 3 10% of total
5.3 Avg. Pass. /Trip (Q) 8 35% of total 8 35% of total
5.4 Avg. Speed
Up Mtr./s 3.2 80% of rated 3.2 80% of rated
Down Mtr./s 3.6 90% of rated 3.6 90% of rated
6.0 Round Trip Time(RTT)
6.1 Up Travel(Sec.) 46.88 35.94
6.2 Down Travel(Sec.) 41.67 31.94
6.3 Loading/ Unloding

Up(Sec.) 17 2 sec/person - guest elevator 17 2 sec/person - guest elevator


Down(Sec.)
6.4 Door opening/Closing 31.5 3 - 4 sec. 30.6 3 - 4 sec.
(Sec.)
6.5 Lost Time(Sec.) 5 5
Total RTT 141.84 120.28

35 - 40 sec.waiting interval is 35-40 sec.waiting interval is


GOOD quality of service as per GOOD quality of service as per
7.0 Waiting Interval (T) 71 IS 14665 (Part 2 / Sec 1):2000 40 IS 14665 (Part 2 / Sec 1):2000

550 room bays x 1.5 550 room bays x 1.5


8.0 Total Population to be 825 person \ bay 825 person \ bay
Handled (P)
15 - 25 % for Single 15 - 25 % for Single
Occupancy building as Occupancy building as
per IS 14665 (Part 2 / per IS 14665 (Part 2 / Sec
9.0 % 5 Minutes Handling 9 Sec 1):2000 15 1):2000
Capacity.
Passenger Elevator Traffic Analysis
IT Building (North block)
Sr. Selection Passenger Lifts per Bank Remarks
1 Elevators PE-1, PE-2,PE-3,PE-4, PE-5,PE-6
1.1 Number 6
1.2 Floors 13
1.3 No. of Stops B2,B1,UGF,1F,2F,3F,4F,5F,6F,5F,6F,7F,8F,9
F,RF
2 Capacity
2.1 No. of Passengers 20
2.2 Weight(Kg) 1360

2.3 Speed (m/s) 2

2.4 Type gearless

3 Stops
3.1 Up 13

3.2 Down 13

4 Travel (Mtrs) 52

5 Probability

5.1 Up Stops 8 60% of total

5.2 Down Stops 4 30% of total

5.3 Avg. Pass. /Trip (Q) 16 80% of total

5.4 Avg. Speed

Up Mtrs./s 1.6 80% of rated speed

Down Mtrs./s 1.8 90% of rated speed

6 Round Trip Time(RTT)

6.1 Up Travel(Sec.) 32.5 Total travel/Average speed up

6.2 Down Travel(Sec.) 28.9 Total travel/Average speed down

6.3 Loading/ Unloading


Up(Sec.) 32 2 sec/person
Down(Sec.)
6.4 Door opening/Closing 35 3 - 4 sec.
(Sec.)
6.5 Lost Time(Sec.) 5
Total RTT 133
2 Waiting Interval (T) 22 Total RTT/No of Lifts
20-25 seconds - Excellent.
30-35 seconds - Good
35-40 seconds- Fair
45 seconds - Poor
as per IS:14665

3 Total Population to be 2633 Assuming 100 sqft per person(Carpet


Handled (P) area =263300 sqft.)

10 -15% for a diversified tenant office


building. as per IS: 14665.
4 % 5 Minutes Handling 8 15 - 25 % for Single Occupancy
building as per IS 14665 (Part 2 / Sec
1):2000
Capacity.
Passenger Elevator Traffic Analysis
IT Building (South block)
Sr. Selection Passenger Lifts per Bank Remarks
1 Elevators PE-1, PE-2,PE-3,PE-4, PE-5,PE-6
1.1 Number 6
1.2 Floors 14
1.3 No. of Stops B2,B1,LGF,UGF,1F,2F,3F,4F,5F,6F,7F,8F,9F
,RF
2 Capacity
2.1 No. of Passengers 20
2.2 Weight(Kg) 1360

2.3 Speed (m/s) 2

2.4 Type gearless

3 Stops
3.1 Up 14

3.2 Down 14

4 Travel (Mtrs) 56

5 Probability

5.1 Up Stops 8 60% of total

5.2 Down Stops 4 30% of total

5.3 Avg. Pass. /Trip (Q) 16 80% of total

5.4 Avg. Speed

Up Mtrs./s 1.6 80% of rated speed

Down Mtrs./s 1.8 90% of rated speed

6 Round Trip Time(RTT)

6.1 Up Travel(Sec.) 35.0 Total travel/Average speed up

6.2 Down Travel(Sec.) 31.1 Total travel/Average speed down

6.3 Loading/ Unloading


Up(Sec.) 32 2 sec/person
Down(Sec.)
6.4 Door opening/Closing 38 3 - 4 sec.
(Sec.)
6.5 Lost Time(Sec.) 5
Total RTT 141
2 Waiting Interval (T) 23 Total RTT/No of Lifts
20-25 seconds - Excellent.
30-35 seconds - Good
35-40 seconds- Fair
45 seconds - Poor
as per IS:14665

3 Total Population to be 2633 Assuming 100 sqft per person(Carpet


Handled (P) area =263300 sqft.)

10 -15% for a diversified tenant office


building. as per IS: 14665.
4 % 5 Minutes Handling 8 15 - 25 % for Single Occupancy
building as per IS 14665 (Part 2 / Sec
1):2000
Capacity.

Spectral Services Consultants pvt. ltd