OBJECTIVE:
1. To provide design load analysis as required for verification of load schedule calculation.
2. To identify fault level at main protection for sizing of interrupting capacity of main circuit
breaker.
3. To check voltage drop to ensure good quality of power delivered to final load.
REFERENCE:
A. Philippine Electrical Code Part 1 – 2017 Edition
B. Proposed submitted electrical plan
PARAMETERS:
1. 5% maximum allowable voltage drop from Main power supply up to Final load
2. Main power supply : 230 Volt / 60Hz – Single Phase – 3 Wire service
3. Total floor area: 81 sq. m.
DESIGN ANALYSIS:
A. For Lighting Load :
Total floor area – 81 sq. m. (24 VA/sq. m.) - 1944
B. 1 small appliances load @ 1500 - 1500
Total Load - 3444
C. Net Load :
3000 VA @ 100% DF - 3000
Remainder of 444 @ 35% DF - 155.4
Total Load - 3155.4
D. Net Load & Specific Load:
Net Load - 3155.4
1 SPO : (6.9A × 230V) @ 100% DF - 1587
Total Load - 4742.4
THEREFORE: