The document calculates the voltage drop at various outlets for a building wiring system. It provides the conductor size, length, resistance, reactance, voltage drop in volts, and percentage voltage drop for 30 different outlets including lighting outlets, convenience outlets, and system points of use. The percentage voltage drops range from 0.65% to 3.85% with most outlets having voltage drops under 2%.
The document calculates the voltage drop at various outlets for a building wiring system. It provides the conductor size, length, resistance, reactance, voltage drop in volts, and percentage voltage drop for 30 different outlets including lighting outlets, convenience outlets, and system points of use. The percentage voltage drops range from 0.65% to 3.85% with most outlets having voltage drops under 2%.
The document calculates the voltage drop at various outlets for a building wiring system. It provides the conductor size, length, resistance, reactance, voltage drop in volts, and percentage voltage drop for 30 different outlets including lighting outlets, convenience outlets, and system points of use. The percentage voltage drops range from 0.65% to 3.85% with most outlets having voltage drops under 2%.
CONDUCTOR SIZE: 325 mm² COPPER WIRE; LENGTH: 15 m R= 0.023 OHM/305 m; XL = 0.039 OHM/305 m VDL-L= 2 x 398.6 x √(0.023²+0.039²) x 15/305 = 1.78 V %VD = 1.78/230 X 100 = 0.77%
2.) VOLTAGE DROP AT LIGHTING OUTLET (C1)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 160.82 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 2.28 x √3.1²+0.058²) x 160.82/305] + 1.33 = 8.78 V %VD = 8.78/230 X 100 = 3.82%
3.) VOLTAGE DROP AT LIGHTING OUTLET (C2)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH:162.54m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 2.28 x √(3.1²+0.058²) x 162.54/305] + 1.33= 5.29 V %VD = 5.29/230 X 100 = 3.85%
4.) VOLTAGE DROP AT LIGHTING OUTLET (C3)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 128.27 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 1.52 x √3.1²+0.058²) x 128.27/305] + 1.33 = 5.29 V %VD = 5.29/230 X 100 = 2.30%
5.) VOLTAGE DROP AT LIGHTING OUTLET (C4)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 91.43 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.76 x √3.1²+0.058²) x 91.43/305] + 1.33= 2.74V %VD = 2.74/230 X 100 = 1.19%
6.) VOLTAGE DROP AT LIGHTING OUTLET (C5)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 92.94 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 1.52 x √3.1²+0.058²) x 92.94/305] + 1.33 = 4.20 V %VD = 4.20/230 X 100 = 1.83%
7.) VOLTAGE DROP AT LIGHTING OUTLET (C6)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 76.05m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.87 x √3.1²+0.058²) x 76.05/305] + 1.33 = 2.67V %VD = 2.67/230 X 100 = 1.16%
8.) VOLTAGE DROP AT LIGHTING OUTLET (C7)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 78.39 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.87 x √3.1²+0.058²) x 78.39/305] + 1.33 = 2.72 V %VD = 2.72/230 X 100 = 1.18% 9.) VOLTAGE DROP AT LIGHTING OUTLET (C8) CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 199.9 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 1.52 x √3.1²+0.058²) x 199.9/305] + 1.33 = 3 V %VD = 3/230 X 100 = 1.30%
10.) VOLTAGE DROP AT LIGHTING OUTLET (C9)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 94.26 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.87 x √3.1²+0.058²) x 94.26/305] + 1.33 = 3.00 V %VD = 3.00/230 X 100 = 1.30%
11.) VOLTAGE DROP AT LIGHTING OUTLET (C10)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 133.82 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 1.30 x √3.1²+0.058²) x 133.82/305] + 1.33 = 3.61 V %VD = 3.61/230 X 100 = 1.57%
12.) VOLTAGE DROP AT CONVINIENCE OUTLET (C11)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 34.7m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.70 x √3.1²+0.058²) x 34.7/305] + 1.33 = 1.65 V %VD = 1.65/230 X 100 = 0.72%
13.) VOLTAGE DROP AT CONVINIENCE OUTLET (C12)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 46.58 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 2.35 x √3.1²+0.058²) x 46.58/305] + 1.33 = 2.77 V %VD = 2.77/230 X 100 = 1.20%
14.) VOLTAGE DROP AT CONVINIENCE OUTLET (C13)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 39.32 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.70 x √3.1²+0.058²) x 39.32/305] + 1.33 = 1.69 V %VD = 1.69/230 X 100 = 0.74%
15.) VOLTAGE DROP AT CONVINIENCE OUTLET (C14)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 15.34 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.78 x √3.1²+0.058²) x 15.34/305] + 1.33 = 1.49 V %VD = 1.49/230 X 100 = 0.65%
16.) VOLTAGE DROP AT CONVINIENCE OUTLET (C15)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 39.2 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 2.35 x √3.1²+0.058²) x 39.2/305] + 1.33 = 2.54 V %VD = 2.54/230 X 100 = 1.10% 17.) VOLTAGE DROP AT CONVINIENCE OUTLET (C16) CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 55.8 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 3.91 x √3.1²+0.058²) x 55.8/305] + 1.33 = 4.19 V %VD = 4.19/230 X 100 = 1.82%
18.) VOLTAGE DROP AT CONVINIENCE OUTLET (C17)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 26.56 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 1.57 x √3.1²+0.058²) x 26.56/305] + 1.33 = 1.88 V %VD = 1.88/230 X 100 = 0.82%
19.) VOLTAGE DROP AT CONVINIENCE OUTLET (C18)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 43.98 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 1.57 x √3.1²+0.058²) x 43.98/305] + 1.33 = 1.87 V %VD = 1.87/230 X 100 = 0.81%
20.) VOLTAGE DROP AT CONVINIENCE OUTLET (C19)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 47.6 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 0.78 x √3.1²+0.058²) x 47.6/305] + 1.33 = 1.62 V %VD = 1.62/230 X 100 = 0.71%
21.) VOLTAGE DROP AT ACU – S.P.O (C20)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 44 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 8 x √3.1²+0.058²) x 44/305] + 1.33 = 4.10 V %VD = 4.10/230 X 100 = 1.78%
22.) VOLTAGE DROP AT ACU – S.P.O (C21)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 20.7 m R= 3.1 OHM/305 m; XL = 0.058 OHM/305 m VDL-L= [2 x 8 x √3.1²+0.058²) x 20.7/305] + 1.33 = 2.63 V %VD = 2.63/230 X 100 = 1.15%
23.) VOLTAGE DROP AT ACU – S.P.O (C22)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 21.61 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 8 x √(2²+0.054²) x 21.61/305] + 1.33 = 2.69 V %VD = 2.69/230 X 100 = 1.17%
24.) VOLTAGE DROP AT ACU – S.P.O (C23)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 33 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 8 x √(2²+0.054²) x 33/305] + 1.33 = 3.41 V %VD = 3.41/230 X 100 = 1.48% 25.) VOLTAGE DROP AT ACU - S.P.O (C24) CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 27 m R= 0.78 OHM/305 m; XL = 0.052 OHM/305 m VDL-L= [2 x 8 x √(0.78²+0.052²) x 27/305] + 1.33 = 3.03 V %VD = 3.03/230 X 100 = 1.32%
26.) VOLTAGE DROP AT REEF – S.P.O (C25)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 11.72 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 3.48 x √(2²+0.054²) x 11.72/305] + 1.78 = 1.65 V %VD = 1.65/230 X 100 = 0.72%
27.) VOLTAGE DROP AT WD - S.P.O (C26)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 13.98 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 21.74 x √(1.2²+0.050²) x 13.98/305] + 1.33 = 3.72 V %VD = 3.72/230 X 100 = 1.62%
28.) VOLTAGE DROP AT MO – S.P.O (C27)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 16.1 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 5.22 x √(1.2²+0.050²) x 16.1/305] + 1.33 = 1.99 V %VD = 1.99/230 X 100 = 0.87%
29.) VOLTAGE DROP AT WH – S.P.O (C28)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 18.44 m R= 0.49 OHM/305 m; XL = 0.051 OHM/305 m VDL-L= [2 x 21.74 x √(0.49²+0.0501²) x 18.44/305] + 1.33 = 4.49 V %VD = 4.49/230 X 100 = 1.95%
30.) VOLTAGE DROP AT WP – S.P.O (C29)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 20.08 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 10 x √(2²+0.050²) x 20.08/305] + 1.33 = 2.97 V %VD = 2.97/230 X 100 = 1.29%
31.) VOLTAGE DROP AT DW – S.P.O (C30)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 36.6 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.74 x √(2²+0.050²) x 36.6/305] + 1.33 = 1.83 V %VD = 1.83/230 X 100 = 0.80%
32.) VOLTAGE DROP AT VM – S.P.O (C31)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 36.6 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 6.52 x √(2²+0.054²) x 36.6/305] + 1.33 = 3.21 V %VD = 3.21/230 X 100 = 1.40% 33.) VOLTAGE DROP AT SPECIAL OUTLET (C32) CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 42.6 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 6.52 x √(1.2²+0.050²) x 42.6/305] + 1.33 = 3.52 V %VD = 3.52/230 X 100 = 1.53%
34.) VOLTAGE DROP AT LIGHTING OUTLET (C33)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 132.77 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.09 x √(1.2²+0.050²) x 132.77/305] + 1.33 = 4.27 V %VD = 4.27/230 X 100 = 1.86%
35.) VOLTAGE DROP AT LIGHTING OUTLET (C34)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 123.37 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 1.2 x √(2²+0.054²) x 123.37/305] + 1.33 = 4.34 V %VD = 4.34/230 X 100 = 1.89%
36.) VOLTAGE DROP AT LIGHTING OUTLET (C35)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 175.68 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.96 x √(1.2²+0.050²) x 175.68/305] + 1.33 = 8.33 V %VD = 8.33/230 X 100 = 3.62%
37.) VOLTAGE DROP AT LIGHTING OUTLET (C36)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 186.48 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 0.54 x √(1.2²+0.050²) x 186.48/305] + 1.33 = 3.38 V %VD = 3.38/230 X 100 = 1.47%
38.) VOLTAGE DROP AT LIGHTING OUTLET (C37)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 141.65 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 1.52 x √(2²+0.054²) x 141.65/305] + 1.33 = 5.71 V %VD = 5.71/230 X 100 = 2.48%
39.) VOLTAGE DROP AT LIGHTING OUTLET (C38)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 106.75 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 1.09 x √(2²+0.054²) x 106.75/305] + 1.33 = 3.70 V %VD = 3.70/230 X 100 = 1.61%
40.) VOLTAGE DROP AT LIGHTING OUTLET (C39)
CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 75.8 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.52 x √(1.2²+0.050²) x 75.8/305] + 1.33 = 3.67 V %VD = 3.67/230 X 100 = 1.60% 41.) VOLTAGE DROP AT LIGHTING OUTLET (C40) CONDUCTOR SIZE: 2.0 mm² COPPER WIRE; LENGTH: 134.32 m R= 2 OHM/305 m; XL = 0.054 OHM/305 m VDL-L= [2 x 1.2 x √(2²+0.054²) x 134.32/305] + 1.33 = 4.61 V %VD = 4.61/230 X 100 = 2.00%
42.) VOLTAGE DROP AT LIGHTING OUTLET (C41)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 118.11 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 2.39 x √(1.2²+0.050²) x 118.11/305] + 1.33 = 7.07 V %VD = 7.07/230 X 100 = 3.07%
43.) VOLTAGE DROP AT CONVINIENCE OUTLET (C42)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 61.68 m R= 0.49 OHM/305 m; XL = 0.051 OHM/305 m VDL-L= [2 x 1.57 x √(0.49²+0.0501²) x 29.7/305] + 1.33 = 2.60 V %VD = 2.60/230 X 100 =1.13%
44.) VOLTAGE DROP AT CONVINIENCE OUTLET (C43)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 67.54 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.57 x √(2²+0.050²) x 67.54/305] + 1.33 = 2.72 V %VD = 2.72/230 X 100 = 1.18%
45.) VOLTAGE DROP AT CONVINIENCE OUTLET (C44)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 44.2 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.57 x √(2²+0.050²) x 44.2/305] + 1.33 = 2.24 V %VD = 2.24/230 X 100 = 0.97%
46.) VOLTAGE DROP AT CONVINIENCE OUTLET (C45)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 67 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 2.35 x √(2²+0.050²) x 67/305] + 1.33 = 3.40 V %VD = 3.40/230 X 100 = 1.48%
47.) VOLTAGE DROP AT CONVINIENCE OUTLET (C46)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 73.44 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 5.48 x √(2²+0.050²) x 73.44/305] + 1.33 = 6.61 V %VD = 6.61/230 X 100 = 2.87%
48.) VOLTAGE DROP AT CONVINIENCE OUTLET (C47)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 30.1 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 2.35 x √(2²+0.050²) x 30.1/305] + 1.33 = 2.26 V %VD = 2.26/230 X 100 = 0.98% 49.) VOLTAGE DROP AT CONVINIENCE OUTLET (C48) CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 42.6 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 2.35 x √(2²+0.050²) x 42.6/305] + 1.33 = 2.64 V %VD = 2.64/230 X 100 = 1.15%
50.) VOLTAGE DROP AT CONVINIENCE OUTLET (C49)
CONDUCTOR SIZE: 3.5 mm² COPPER WIRE; LENGTH: 34.24 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 1.57 x √(2²+0.050²) x 34.24/305] + 1.33 = 2.03 V %VD = 2.02/230 X 100 = 0.88%
51.) VOLTAGE DROP AT ACU - S.P.O (C50)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 59.2 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 8 x √(2²+0.050²) x 59.2/305] + 1.33 = 5.06 V %VD = 5.06/230 X 100 = 2.20%
52.) VOLTAGE DROP AT ACU - S.P.O (C51)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 51.7 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 8 x √(2²+0.050²) x 51.7/305] + 1.33 = 4.59 V %VD = 4.59/230 X 100 = 1.99%
53.) VOLTAGE DROP AT ACU - S.P.O (C52)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 36.1 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 8 x √(2²+0.050²) x 36.1/305] + 1.33 = 3.60 V %VD =3.60/230 X 100 = 1.57%
54.) VOLTAGE DROP AT ACU - S.P.O (C53)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 27.6 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 8 x √(2²+0.050²) x 27.6/305] + 1.33 = 3.07 V %VD = 3.07/230 X 100 = 1.33%
55.) VOLTAGE DROP AT ACU - S.P.O (C54)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 26.3 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 8 x √(2²+0.050²) x 26.3/305] + 1.33 = 2.99 V %VD = 2.99/230 X 100 = 1.30%
56.) VOLTAGE DROP AT ACU - S.P.O (C55)
CONDUCTOR SIZE: 5.5 mm² COPPER WIRE; LENGTH: 15.9 m R= 1.2 OHM/305 m; XL = 0.050 OHM/305 m VDL-L= [2 x 8 x √(2²+0.050²) x 15.9/305] + 1.33 = 2.33 V %VD = 2.33/230 X 100 = 1.01%